7. FIELD SETTING

There are 3 methods for address setting by FIELD SETTING as follows.
Please set by either of the methods.
Each setting method is described in below (1) to (3).
(1)
IU AD, REF AD SW settings: This section (7.1. Setting the address)
(2)
Remote controller settings:
(3)
Automatic address settings: Refer to the outdoor unit manual for detailed setting

7.1. Setting the address

Use an insulated screwdriver to set the dip switches.
The rotary switches and slide switches to configure are located at the location shown
below.
7.1.1. Indoor unit address
• Rotary switch (IU AD × 1)...Factory setting "0"
• Rotary switch (IU AD × 10)...Factory setting "0"
When connecting multiple indoor units to 1 refrigerant system, set the address at IU AD
SW as shown in the Table A.
7.1.2. Refrigerant circuit address
• Rotary switch (IU AD × 1)...Factory setting "0"
• Rotary switch (IU AD × 10)...Factory setting "0"
In the case of multiple refrigerant systems, set REF AD SW as shown in the Table A for
each refrigerant system.
Set to the same refrigerant circuit address as the outdoor unit.
Setting
Setting range
Indoor unit ad-
0 to 63
dress
Refrigerant
0 to 99
circuit address
• If working in an environment where the wireless remote controller can be used, the ad-
dresses can also be set using the remote controller.
• If setting the addresses using the wireless remote controller, set the indoor unit address
and refrigerant circuit address to "00".
(For information on setting using the wireless remote controller.)
Table A
Address
Rotary Switch Setting
REF AD SW
Refrigerant circuit
× 10
0
0
1
0
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
0
10
1
11
1
12
1
99
9
Do not set the indoor unit address (IU AD SW) at 64 to 99.
It may result in failure.
En-11
Refer to the wired or wireless remote controller
manual for detailed setting information. (Set IU AD,
REF AD SW to 0)
information. (Set IU AD, REF AD SW to 0)
CAUTION
For indoor unit
address
For refrigerant circuit
address
Type of switch
Setting ex-
ample
2
IU AD × 10
Setting ex-
ample
63
REF AD × 10
Address
Rotary Switch Setting
Indoor unit
× 1
× 10
0
0
0
1
1
0
2
2
0
3
3
0
4
4
0
5
5
0
6
6
0
7
7
0
8
8
0
9
9
0
0
10
1
1
11
1
2
12
1
9
63
6

7.2. Custom code setting

• Selecting the custom code prevents the indoor unit mix-up. (figure below)
(Up to 4 codes can be set.)
• Perform the setting for both the indoor unit and the remote controller.
Indoor unit
Remote
controller
Custom code setting for indoor unit
Set the DIP switch SET3 SW1, 2, referring to
the figure and table below.
ON
OFF

7.3. Function setting

• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
• Refer to "7.1. Setting the address" for indoor unit address and refrigerant circuit address
settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air tight
test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Filter
indicator
interval
Filter
indicator
action
Ceiling
airflow
(Forbidden)
(Forbidden)
IU AD × 1
Installation
REF AD × 1
position
setting
Cool air
tem-
IU AD SW
perature
× 1
trigger
0
1
2
3
Heat air
4
tempera-
5
ture trigger
6
7
8
Auto restart
9
0
1
Cool Air
2
Prevention
3
Confusion
DIP switch "SET3"
DIP switch
SET3
SW1
SW2
SW
SW
SW
SW
1
2
3
4
Function
Setting number
Default
number
00 Standard
01 Longer
11
02 Shorter
00 Enable
01 Disable
Display only
13
on central
02
remote
controller
00 Standard
20
High
01
Ceiling
23
24
00 Center
01 Right
27
02 Left
00 Standard
01 Adjust (1)
30
02 Adjust (2)
00 Standard
01 Adjust (1)
02 Adjust (2)
31
03 Adjust (3)
00 Enable
40
01 Disable
00 Super low
Follow the
43
setting on
01
the remote
controller
Code change
A
B
C
D
A
B
C
D
×10 IU AD ×1
×10 REF AD ×1
DIP switch
"SET3"
SET3
SET4
Custom code
A (Factory
B
C
D
setting)
OFF
ON
OFF
ON
OFF
OFF
ON
ON
Details
Adjust the filter cleaning interval
notification. If the notification is too
early, change to setting 01. If the
notification is too late, change to
setting 02.
Enable or disable the filter indica-
tor. Setting 02 is for use with a
central remote controller.
Regulate the airflow accordingto
the needs of the installationloca-
tion. When set to 01, the airflow
will be stronger.
Setting to switch the airflow
direction based on the installation
position of the indoor unit.
Left
Center
Right
Adjust the cool air trigger
temperature. To lower the trigger
temperature, use setting 01. To
raise the trigger temperature, use
setting 02.
Adjust the heat air trigger tempera-
ture. To lower the trigger tempera-
ture by 6 degrees C, use setting
01. To lower the trigger temperature
by 4 degrees C, use setting 02. To
raise the trigger temperature, use
setting 03.
Enable or disable automatic system
restart after a power outage.
Restrain the cold airflow with mak-
ing the airflow lower when starting
heating operation. To correspond to
the ventilation, set to 01.