Connection Of Wiring - Fujitsu Airstage AUXS018GLEH Installation Manual

Indoor unit (3d flow cassette type)
Hide thumbs Also See for Airstage AUXS018GLEH:
Table of Contents

Advertisement

6.3.2. Transmission and Remote controller cable
Transmission cable
30 mm
Shield cable
45 mm
(no film)
• Connect remote controller and transmission cables as shown in following figure.
GOOD
Different diameter
Tighten the terminal screws to the specified torques, otherwise, abnormal overheating
may be produced and possibly cause heavy damage inside the unit.
Tightening torque
M3 screw (Transmission / X1, X2)
(Remote controller / Y1, Y2)
To peel the film from the lead cable, use a dedicated tool that will not damage the
conductor cable.
When installing a screw on the terminal block, do not cut the cable by overtightening the
screw. On the other hand, an undertightened screw can cause faulty contact, which will
lead to a communication failure.

6.4. Connection of wiring

(1) Use a screw driver to loosen one screw at the bottom of the Indoor unit and remove
the cover.
(2) Disconnect the connector from the switch circuit board. Then, loosen one screw and
remove the sheet metal.
Connector
Remote controller cable
30 mm
PROHIBITED
Connect to 1 side
WARNING
0.5 to 0.6 N·m
(5 to 6 kgf·cm)
CAUTION
(3) After wiring is complete, secure the cables with the cable clamps.
Earth (ground)
(4) Connect the transmission and remote controller cables by passing the cables through
the hole shown in the diagram below. Once all cables are connected, tie the power
cable using a push mount cable tie, and tie the transmission and remote controller
cables using a cable tie.
Push mount
cable tie
(accessories)
Y1, Y2: Remote controller cable
X1, X2: Transmission cable
(5) Attach the hook wire. As show below, loosen the screw at the specified location and
attach the hook wire.
(6) Once all cables are connected, replace the cover and fix it with the screws. Cure the
wiring connecting port and remote controller connecting port with putty or heat insula-
tion so that insects or dust will not enter the unit.
Do not bundle the remote controller cable, or wire the remote controller cable in parallel,
with the indoor unit connection wire (to the outdoor unit) and the power supply cable. It
may cause erroneous operation.
Power supply cable
Cable clamp
Cable tie (medium)
(accessories)
Hook wire
(accessories)
CAUTION