PPLICATION UIDE Trip Circuit Supervision (TCS) in EuroProt+ devices ANSI: 74 ID: PP-13-21875 OCUMENT ROTECTION AUTOMATION AND : 1.2 AST VERSION CONTROL FOR POWER INDUSTRY 2019-08-07, B UDAPEST...
Page 2
ERSION INFORMATION VERSION INFORMATION ERSION ODIFICATION OMPILED BY Erdős 2019-03-11 First edition Erdős 2019-05-10 Notes for parallel-connected circuits added Additional technical data, withstand voltage Erdős 2019-08-07 raised for TRIP+/2101, corrections Trip Circuit Supervision (TCS) in EuroProt+ devices www.protecta.hu...
TCS signal handling ...................... 8 Technical data ....................... 9 Software application ......................10 Binary inputs ........................ 10 The TCS macro ......................10 3.2.1 Binary input signals ..................... 11 3.2.2 Binary output signals ................... 11 Trip Circuit Supervision (TCS) in EuroProt+ devices www.protecta.hu...
Page 4
SED SYMBOLS USED SYMBOLS Additional information Useful information for settings. Important part for proper usage. Trip Circuit Supervision (TCS) in EuroProt+ devices www.protecta.hu...
For more details please refer to the EuroProt+ Hardware description from which these were extracted. Note that there are other modules without trip circuit supervision, those are not listed here. Table 1-1 Modules with Trip Circuit Supervision TRIP+4201 TRIP+2101 TRIP+2201 PSTP+4201...
It is possible to use parallel connected TRIP+ modules. In this case the negative contacts must be common. TRIP+ module Circuit breaker – – (TRIP Circuit Supervision) – TRIP+ module – (TRIP Circuit Supervision) Figure 2-2 3-wire TRIP+ wiring using parallel connected TRIP+ modules Trip Circuit Supervision (TCS) in EuroProt+ devices www.protecta.hu...
*The inputs of some relay testers might sense the states of the Trip contacts active even if they are not. In such cases the “–“ pin must be wired in for the tests. Trip Circuit Supervision (TCS) in EuroProt+ devices www.protecta.hu...
ARDWARE APPLICATION 2.3 Technical data The following tables contain information according to the wiring connections described in Chapter 2.1. Table 2-1 Technical data for the TRIP+ modules TRIP+4201 TRIP+2101 TRIP+2201 ODULE TYPE ALUE OF 10 kΩ 73 kΩ 130 kΩ...
1 trip circuit it is enough to simply leave the TCS2 input open (naturally in this case the TC_Failure2 output cannot be used). Figure 3-2 Internal logic of the Trip Circuit Supervision macro Trip Circuit Supervision (TCS) in EuroProt+ devices www.protecta.hu...
Note that these are the outputs of a macro, and not a function block, so they must be connected to a physical or a logical output (ConnOut, create status) to make them usable in other parts of the configuration. For further information please refer to the EuroCAP software description. Trip Circuit Supervision (TCS) in EuroProt+ devices www.protecta.hu...