Product Description; Type Plate; Tech Data; Product Data For Energy Consumption - Bosch Stora BP 200 EK Installation And Service Instructions Manual

Buffer cylinder
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 17
2.3

Product description

Pos.
Description
1
Heating water inlet
2
Heating water outlet
3
Rigid foam thermal insulation
4
Vent valve
5
Foil jacket
6
Data plate
7
Heating water outlet
8
Heating water inlet
9
Installation options, electric heating
10
Installation options, electric heating
11
Installation options, electric heating
12
Installation options, electric heating
13
Installation options, electric heating
14
Installation options, electric heating
15
Sensor pocket at bottom (only with BP 1000 E)
16
Sensor pocket at centre (with BP 200 EK+BP 500 EP
accessory)
17
Sensor pocket at top (with BP 200 EK+BP 500 EP accessory)
18
Inspection aperture (only with BP 500 EP)
Table 17 Product description (
2.5

Tech data

Dimensions and specifications
Memory
Available capacity
Maximum heating water temperature
Maximum operating pressure of heating water
Standby heat loss (24 h) in accordance with DIN 4753 Part 8
1) Excluding distribution losses outside the cylinder.
Table 19 Tech data
2.6

Product data for energy consumption

The following product data satisfy the requirements of the
EU Regulations No. 811/2013 and No. 812/2013 supplementing
EU Regulation 2017/1369.
Manufacturers who implement these guidelines and state the ErP values
are permitted to use the "CE" mark.
3

Regulations

Observe the following guidelines and standards:
• Local regulations
• EnEG (Building Regulations) (in Germany)
• EnEV (in Germany)
Installation of, and equipment for, heating and water heating systems:
• DIN and EN standards
– EN 12828 – Heating systems in buildings - Design and installation
of DHW heating systems
– DIN 18380 – German construction contract procedures (VOB) -
Installation of central heating systems and hot water supply
systems
Stora – 6721835329 (2021/04)
Fig. 1 - 3, page 33 - 34)
1)
2.4

Type Plate

Pos.
Description
1
Type designation
2
Serial number
3
Nominal volume
4
Nominal volume of heat exchanger
5
Standby heat loss
6
Corrosion protection
7
Year of manufacture
8
Maximum DHW temperature, cylinder
9
Maximum flow temperature, heat source
10
Maximum flow temperature, solar side
11
Heating water heat input
12
Volumetric flow rate of heating water for heating water input
power
13
Maximum operating pressure on the domestic water side
14
Highest design pressure
15
Maximum operating pressure, heat source side
16
Maximum operating pressure, solar side
17
Maximum operating pressure on the domestic water side CH
18
Maximum test pressure on the domestic water side CH
Table 18 Type Plate
Unit
BP 200 EK
-
l
199
°C
95
bar
3
kWh/24 h
1.22
Product
Product type Cylinder
number
8735100973 BP 200 EK 1 B 199,4 l
8735100974 BP 500 EP 1 C 480,0 l
8735100978 BP 1000 E 1 C 867,0 l
Table 20 Product data for energy consumption
– DIN 18381– German construction contract procedures (VOB) -
Installation of gas, water and drainage systems inside buildings
– EN 16297, Part 1/2 – Centrifugal pumps - Wet running heating
pumps
• VDE regulations
Product data for energy consumption
• EU Regulation and Directives
– EU Regulation 2017/1369
– EU Regulation 811/2013 and 812/2013
BP 500 EP
 Fig. 4 - 6, page 35 - 36
480
95
6
2.41
Heat
volume
retention
(V)
loss (S)
50,7 W
100,5 W
134,0 W
Regulations
BP 1000 E
867
95
3
3.22
Energy
efficiency class
for DHW
treatment
B
C
C
19