Summary of Contents for EFLOW Altronix eFlow6NV Series
Page 1
eFlow6NV Series Power Supply/Chargers Models Include: eFlow6NV/ eFlow6NXV - 6A @ 12VDC or 24VDC eFlow6N8V/ eFlow6N8DV/ eFlow6NX8V eFlow6NX8DV - 6A @ 12VDC or 24VDC - 6A @ 12VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Protected eFlow6N16V/ eFlow6N16DV/ eFlow6NX16V...
Page 2
Overview: Altronix eFlow6NV power supply/chargers convert a 220VAC (working range 198VAC - 256VAC), 50/60Hz input to a 12VDC or 24VDC nominal output (see Power Supply Configuration Reference Chart and Specifications). eFlow6NV Series Power Supply Configuration Reference Chart: Nominal DC Outputs [DC] [AUX] Altronix...
Specifications: Input: Supervision: • 220VAC (working range 198VAC - 256VAC), • AC fail supervision (form “C” contacts). 50/60Hz. • Battery fail and presence supervision (form “C” contacts). Output: • Low power shutdown. Shuts down DC output • For output voltage and supply current refer to terminals if battery voltage drops below 71-73% for eFlow6NV Series Power Supply Configuration 12V units and 70-75% for 24V units (depending on...
6. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in the loss of the output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type.
Terminal Identification: Power Supply/Charger Terminal Legend Function/Description Connect 220VAC 50/60Hz to these terminals: L to hot, N to neutral (non power-limited) L, N (Fig. 1a, pg. 5). – DC + 12VDC or 24VDC nominal @ 6A continuous output (power-limited output) (Fig. 1h, pg. 5). Trigger EOL Fire Alarm Interface trigger input from a short or FACP.
Page 6
Fig. 2 - Battery trouble indication For Canadian use, a red indicating lamp must be visible from the exterior of this enclosure. Wire one leg of a power source to the indicating lamp. Wire the second leg of the power source to the indicating lamp in series with the battery fail relay contact terminals marked [BAT FAIL - C, NO] (Fig.
Page 7
Fig. 5 - eFlow6NV Configuration Enclosure Edge of Enclosure Tamper Switch (included) To Access Control Panel or UL Listed Reporting Device Ground PD8/PD8CB 220VAC PD16W/ power mains PD16WCB Switch Detail Switch On - 12V Switch Off - 24V DC Output to Devices Battery &...
Page 8
NEC Power-Limited Wiring Requirements for eFlow6N Models: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below.
Page 9
Fig. 7 - eFlow6NXV Configuration Enclosure Edge of Enclosure Tamper Switch (included) To Access Control Panel or UL Listed Reporting Device OFF - 24V ON - 12V Switch Detail Ground Switch On - 12V Switch Off - 24V Battery & AC Supervision Circuit AC DC NC C NO NC C NO...
Page 10
NEC Power-Limited Wiring Requirements for eFlow6NXV Models: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below.
Appendix A - Compatible Devices –––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– A.1 Four (4) Wire Smoke Detectors Table A-1 below lists four (4) wire smoke detectors compatible with eFlow6NV output. Alarm System Sensor Smoke Detector Type Stand-by Current Detector/Base Current (mA) (mA) B112LP Base 0.12 B114LP Base B404B...
Page 14
- UL Listed in the U.S. and Canada. - Local or remote control of up to (2) two Altronix eFlow power output(s) via LAN and/or WAN. - Monitor real time diagnostics: DC output voltage, output current, AC & battery status/service, input trigger state change, output state change and unit temperature.
Page 15
Notes: Altronix is not responsible for any typographical errors. –––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– 140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056 website: www.altronix.com | e-mail: info@altronix.com | Lifetime Warranty IIeFlow6NV Series G23U MEMBER eFlow6NV Series Installation Guide - 15 -...
Page 16
Installing Company: _______________ Service Rep. Name: __________________________________ Address: _____________________________________________ Phone #: __________________ Refer to the eFlow Power Supply/Chargers Installation Guide: IIeFlow6NV Series, Rev. 6NVRP052213 for complete instructions. This sheet is to be removed, framed and posted next to the unit.