Page 2
Overview: Altronix eFlow102N power supply/chargers convert a 120VAC / 60Hz input to a 12VDC nominal output (see Power Supply Configuration Reference Chart and Specifications). eFlow102N Series Power Supply Configuration Reference Chart: Nominal DC Outputs [DC] [AUX] eFlow102N – – –...
@ 1A (unswitched). • AC input and DC output LED indicators. Fuse/PTC Ratings: • Overvoltage protection. • Refer to eFlow102N Series Power Supply Battery Backup: Configuration Reference Chart, pg. 2. • Built-in charger for sealed lead acid or Additional Features: gel type batteries.
Loss of AC. Stand-by battery is supplying power. No DC output. Loss of AC. Discharged or no stand-by battery. No DC output. Power Distribution Module Green (AC) Power Distribution Module Status Normal operating condition. No Power Output. - 4 - eFlow102N Series Installation Guide...
Connect the circuit to the Batt Fail relay contacts to an appropriate input of a UL Listed Burglar Alarm or Access Control Panel. The following figure shows the circuitry needed for local annunciation. eFlow102N Series Installation Guide - 5 -...
Page 6
From From Power Power Supply Supply Board Board (Factory (Factory Installed) Installed) For continuous protection against risk of fire replace fuses with same type and rating 3.5A 250V - 6 - eFlow102N Series Installation Guide...
Page 7
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing. 7AH Rechargeable batteries are the largest batteries that can fit in this enclosure. A UL Listed external battery enclosure must be used if using 12AH, 40AH or 65AH batteries. eFlow102N Series Installation Guide - 7 -...
Page 8
Correct Wire Handling Handling External Jacketed Shield Wire Insulation * Outputs are non power-limited: eFlow102N, eFlow102N8, eFlow102N16. Outputs are Class 2 power-limited: eFlow102N8D, eFlow102N16D. Pull back Solid Copper external jacketed Conductors shield approx. 1/2”. - 8 - eFlow102N Series Installation Guide...
Page 9
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing. 12AH Rechargeable batteries are the largest batteries that can fit in this enclosure. A UL listed external battery enclosure must be used if using 40AH or 65AH batteries. eFlow102N Series Installation Guide - 9 -...
Page 10
Correct Wire Handling Handling External Jacketed Shield Wire Insulation * Outputs are non power-limited: eFlow102NX, eFlow102NX8, eFlow102NX16. Outputs are Class 2 power-limited: Pull back eFlow102NX8D, eFlow102NX16D. Solid Copper external jacketed Conductors shield approx. 1/2”. - 10 - eFlow102N Series Installation Guide...
Projected Beam 28.4 Beam 1224(S) Projected Beam 38.5 * Contact manufacturer for current draws. –––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– A.2 Relays Table A-2 below lists relays compatible with eFlow102N output. Manufacturer Model Current (mA) System Sensor EOLR-1 eFlow102N Series Installation Guide - 13 -...
Page 14
- UL Listed in the U.S. and Canada. - Local or remote control of up to (2) two Altronix eFlow power output(s) via LAN and/or WAN. - Monitor real time diagnostics: DC output voltage, output current, AC & battery status/service, input trigger state change, output state change and unit temperature.
Page 15
Altronix is not responsible for any typographical errors. 140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056 website: www.altronix.com | e-mail: info@altronix.com | Lifetime Warranty | Made in U.S.A. IIeFlow102N Series G23U MEMBER eFlow102N Series Installation Guide - 15 -...
Page 16
3.5A – 760mV eFlow102NX, eFlow102NX8, Flow102NX8D, eFlow102NX16, eFlow102NX16D Overview: The eFlow102N series power supply/chargers convert a 120VAC, 60Hz input to a 12VDC output. Stand-by Specifications: Burg. Applications Fire Applications 4 hr. Stand-by/ 24 hr. Stand-by/ Access Control Battery 15 min.