Econar GeoSource DualTEK GV Series Installation And Operating Instructions Manual page 16

Vertical and horyzonal forced air/hydronic
Table of Contents

Advertisement

D. Temperature
Limitations
Be
aware
of
the
operating
range
of
the
geothermal
system
when sizing
the
particular
heat
pump.
An
operating
range
of
15oF
(minimum for
heating)
to
110oF
(maximum
for
cooling)
is
required
for
the
earth
loop side.
These
limits
have been established based
on
efficiency limitations
and
safety pressure
switch
limits
(25-psi low-pressure cutout
and
400-psi high-pressure
cutout).
Hvdronic
side
limitations
have
a
minimum of
50"F
hydronic
entering
water temperature
and
a
maximum
of
130"F
hydronic
leaving water temperature range (entering water to
the
hydronic
side
below50oF
gives
low
head pressures
that
drives
the
suction
pressure
below
cutout conditions).
IX.
ELECTRICAL SERVICE
The main
electrical
service
must be
protected by
a
fuse
or
circuit
breaker,
and be capable
ofproviding
the amperes
required by
the
unit
at
nameplate
voltage.
All
wiring
shall
comply with
the
national electrical
code
and/or
any
local
codes
that may
apply.
Access
to
the
line
voltage
contactor
is
gained through
the
knockouts provided on
either
side
of
the heat
pump next to
the
front
corner.
Route
EMT
or
flexible
conduit
with
appropriate
3-
conductor wire to
the
contactor.
9WARNING
- The
unit
must
be
properlv erounded!9
VCAUTION:
Three-phase
units
![sf
be
wired
properly
to
insure
proper
compressor
rotation.
Improper
phasing may result
in
compressor damage.
An
electronic
phase sequence
indicator
must be used
to check supply-
wiring
phase.
Also,
the
"Wild"
leg
of
the three-phase
power
must be connected
to
the
middle
leg
on the
contactor.
When supplying power to extemal water pumps
with
the
heat
pump's power supply,
use
only
impedance protected
motors. An ECONAR
PumpPAKrM
can be
wired
directly
to
the
contactor
and
grounded
in
the
grounding
lug. A
relay (M6)
and
terminal
block
(BP) is supplied in
the
electrical box
for
the
hydronic
side
pump.
The relay
will
start the
pump
with
a
call from
the aquastat.
The
use
of
impedance
protected
pumps
eliminates
the need
for
additional
fusing.
Do
not connect more than
a
1/3
horsepower pump to
the
internal pump relay.
If
larger pumps
are
required,
a
separate
power supply is
required
to
supply
the
pump. To
start
this pump
use
a24-
volt
relay
pulled in from
the
Y
and
X
terminals.
X.
24
VOLT
CONTROL
CIRCUIT
The
wiring
diagrams in Figures
8 and
9
shows the
low
voltage controls
of
the heat
pump
and some
generic
extemal
control
schemes.
This
section
will
break down
the three basic
components
of
the
low
voltage
circuit;
transformer, thermostat/aquastat,
and
conroller.
A. Transformer
Electrical
diagrams
are
provided in Figures
8 and
9,
and
on
the
electrical box
coverpanel
ofthe heatpump. An
internal 24-volt,75
VA
ffansformer
is
provided
to
operate
all
control features
of
the heat
pump.
Even though
the 75
VA
transformer is larger than
the
industry
standrlrd
40
VA
transformer,
it
can
still
be
overloaded
quickly
when
using
it
for control
equipment
like
zone
valves or
zone
circulators.
Table 7
shows the
transformer
usage
for
the
GeoSource
DualTEK
heat pumps.
Table
7
-
Transformer
If
the system's external controls require more than
the
VA
available
for
external
use
from
the
transformer,
an
extemal transformer
must be
used. You
can
see
t}tat
in
Figure 2,
the heat
pump's
internal transformer
can
easily
power
the
extemal
24-Yolt system. In
contrast,
if
a
system
contains components that
have
their own power
supply, they must
be
coupled
to
the heat
pump.
This
can
be
accomplished using
an
isolation relay
which
isolates
the
external
systems
power supply
from
the heat
pump's
transformer
(e.g. use the
external
systems
independent
power supply to
energize the
coil
of
a
relay,
passing a
signal
across the
Normally
Open
contacts
from
the
heat
pump's transformer).
The
heat pumprs
transformer
can
generally power simpler
control
systems
consisting
of
a
few
relays
or
zone
valves
(depending,
ofcourse,
on the
VA
draw
ofthe
components).
On more complicated
control
systems the
transformers capacity is
used
up very
quickly.
GNote:
For units operating
on
208V
electrical
service,
the
transformer
must be
switched to
the
correct lead
(see
electrical
diagrams
-
Figures
8 and
9).
Units
are
factory
shipped
with
the
ffansformer
set
for 240V
service.
Operating
a
unit
on
208V with
the
transformer
set
to
240V
will
cause the
unit
to
operate
with
less
than normal
control
voltage.
B. Thermostat/Aquastat
Consult
the
instructions
ia
the
thermostat box
for
proper
mounting
and
thermostat
operaLion.
7
.,
6
4
1
I
JJ
55
VA
20VA
14
I
Contactor
Pump Relav
BlowerRelay
Reversine
Valve
Controller
Thermostat
Solenoid
Valve
Total
Available

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents