Econar GeoSource DualTEK GV Series Installation And Operating Instructions Manual page 12

Vertical and horyzonal forced air/hydronic
Table of Contents

Advertisement

Table
6
-
Side
Flow
Rates
Pressure/Temperature
(P/T) ports should
be
installed
in
the
entering
and
leaving water lines
of
the heat
pump on
a
closed
loop
system
(see
Figure4). A
thermometer
can be
inserted
into
the
P/T ports to
check
entering
and
leaving
water temperatures.
A
pressure gauge can also be
inserted
into
these
P/T ports to determine
the pressure
differential
between
the
entering
and
leaving
water. This
pressure
differential
can then be
compared to
the
specification
data on each
particular
heat
pump to
determine
the
flow
rate
of
the
svstem.
A
PumpPAKrM that is
individually
sized
for
each
application
can
supply pumping requirements
for
the
earth
loop
fluid.
The PumpPAKrM
can also be used
to
purge
the
loop
system. The PumpPAKrM is wired
directly
to
the
contactor
and operates
whenever
the
compressor
runs
(see
Electrical
Diagrams
-
Figures
8 and
9).
If
a
PumpPAKrM
is
not
used,
a
separate
pump
can be used
which
is
energized
with
a
pump relay (note: electrical
code
will
require
a
fused
disconnect
for
pumps other than
PumpPAKsrM).
Filling
and
purging
a
closed
loop
system are
very
important
steps
to
assure
proper
heat
pump operation.
Each
loop
must be
purged
with
enough water
flow
to
assure a
two feet per
second
flow
rate
in
each
circuit
in
the
loop.
This
normally
requires a
lYz
to
3
HP high
head
pump to circulate
fluid
through
the
loop
to
remove
all
the
air out
of
the
loop
and
into
a
purging
tank. Allow
the
pump to
run
10
to
15
minutes after
the
last air bubbles
have been
removed.
Enough
antifreeze
must
be added
to
give a
10oF
to
15oF
freeze
protection to
the earth
loop
system.
This amount should
be
calculated
and added
to
the
loop
after purging is
complete.
After
antifreeze
has
been
installed
it
should
be measured
with
a
hydrometer,
refractometer or
any
other device to determine
the
actual
freezing
point of
the
solution. Remember that
a
low
arftifreeze
level
will
lock
the heat
pump out on
low
pressure
during
wintertime
operation.
The
purge
pump
can be used
to
pressurize
the
system
to
an
initial
static
pressure
of
30-40
psi.
Make
sure
the
system
is
at
this
pressure
after
the
loop pipe
has
had
enough
time
to stretch. In
order to
achieve the 30
to 40
psi
initial
pressure, the
loop may
need
to
be
pressurized to
60 to
65
psi.
This
static pressure
will
fluctuate
from
heating to
cooling
season,
but
the pressure
should always
remain
above
zero
so
circulation
pumps
do not cavitate
and
air
cannot be
pulled into
the
system.
SFor
information
regarding
earth
loop
installations contact
your
local
installer,
distributor
or factory representative.
B.
Open Loop
Applications
An
open
system gets
its
name
from
the open
discharge
of
water after
it
has
been used
by
the heat
pump. A
well
must be
available that can supply
all of
the
water
requirements
(see
Table 6)
of
the heat
pump along
with
any
other water requirements drawing
off
that
same
well.
The
well
must
be capable
of
supplying
the heat
pump's
required
flow
rate
for
up to 24
hours
per day on
the
coldest
winter
day.
Figure 5
shows the necessary
components
for
water
piping of
an
open system.
First,
a
bladder type
pressure
tank
with
a
"draw
down" of
at
least
lYz
times
the
well
pump capacity
must be
installed
on the
supply
side
of
the
heat
pump.
Shut
off
valves
and
boiler
drains
on the
entering
and
leaving water lines
are
necessary
for future
maintenance issues.
A
screen
strainer
is
placed
on the
supply
line with
a
mesh size
of
40 or 60
and enough
surface area
to
allow for
particle
buildup
between
cleanings.
Pressure/Temperature
(P/T) ports
are
placed
in
the
supply
and
discharge lines
so
that thermometers or
pressure
gauges can be
inserted
into
the
water
stream.
On the
well
water discharge
side
of
the heat
pump,
a
flow
control
valve must
be
mounted next to
the heat
pump to
regulate
the
maximum
water
flow
through
the
unit. A
solenoid valve is
then
installed
and
wired to
the accessory
plug
(P2) on
the
controller.
This valve
will
open
when
the
unit
is
running
and
close when
the
unit
stops.
A
visual
flow
meter
is
then
installed to
allow visual
inspection
of
the
flow
requirements.
The
flow
meter
is
useful
in
determining when maintenance is
required.
(If
you
can't
read
the
flow,
cleaning is
required.
See
Water
Coil
Maintenance
for
cleaning instructions.)
Schedule
40 PVC
piping,
copper tubing, polyethylene
or
rubber
hose can be used
for
supply
and
discharge water
lines.
Make
sure
line
sizes are
large
enough
to supply
the
required
flow
with
a
reasonable pressure
drop (generally
1"
diameter
minimum).
NOTE:
Do not
use
plastic
female
fittings with
metal male
fittings,
or fractures may
result
in
the
female
fittings.
Always
use
plastic male
into
steel
female!
Water
discharge
is generally
made
to
a
drain
field,
stream,
pond,
surface
discharge,
tile line,
or storm
sewer.
VCAUTION:
Using
a
drain
field
requires
soil
conditions
and adequate
sizing
to
assure
rapid percolation,
or
the
required
flow
rates
will
not
be
achieved.
Consult
local
codes and
ordinances to
assure
compliance.
p
pf
discharge water to
a
septic
system.
10
lI&1-
r:E
,t;;dEit=.:,
€=an+=,::
*ttrm1=
rffi;:
={re,
=?*iiiiliS
Gry.IN36
8
5.5
4
1.3
Gry.m52
1l
5.2
6
t.6
Gry.m59
13
6.0
9
3.1
Gry.IN57
t4
7.0
10
3.8
I
f

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents