Econar GeoSource DualTEK GV Series Installation And Operating Instructions Manual page 15

Vertical and horyzonal forced air/hydronic
Table of Contents

Advertisement

The
condensate
line
as
it
leaves the
U
bend
ofthe
condensate
trap must
be at least
3" below
the base
ofthe
heat
pump.
This requires
the
U
bend
to
be
6,'below
the
unit
to give
the
upward
portion of
the
U bend
a
3"
lift.
The
condensate
trap
should
be
vented
after
the
U
bend.
The
condensate
line
should
be
pitched away
from
the
unit
a
minimum
of
1/8" per
foot. ff
the
unit produces
an
odor
in
the
cooling
mode,
the condensate
ftap or
line
may
be
plugged,
or
the
unit
may not
be
pitched
correctly.
Bleach
may
be
poured down
the condensate
drain
in
the heat
pump to
kill
any
bacterial
gowth
in
the condensate
line.
V[I.
UNIT SIZING
Selecting
the
unit
capacity
of
a
GeoSource
DualTEK
geothermal
heat
pump requires
four
things:
A)
Earth
Loop Configuration
and
Design Water
Temperatures.
B)
Hydronic
Side
Heat Exchanger Operating
Temperatures.
C)
Building
Heat Loss/Heat Gain.
D)
Temperature
Limitations.
A. Earth Loop Configuration
and
Design
Water Temperatures
Loop
configurations include
the open and
closed
loop
varieties.
Heat
pump
flow
rate requirements vary
depending on loop
conhguration
(see
Table
6).
Consult
ECONAR'
s
Engineering Specifications Manual
for
capacities
at
different
loop entering water
temperatures
and
hydronic
leaving
water temperatures. Remember to
use
the
correction factors
for
GeoSource
DualTEK
units
found
in
the
Engineering Specifications manual.
2.
Open Loop Systems
On
an open
loop
system the
design water temperature
will
be the
well
water temperature
in your
geographic region.
Many
cold climates
are
in
the
50oF
range
for
well
water
temperature.
If
your
well
water
temperatures are
lower
than 50oF,
for
instance
Canadian
well
water
can be
as
low
as
43T,
the
flow
rate must
be increased
to
avoid leaving
water
temperatures
below
the
freezing
point.
If
well
water
temperafures are above 50nF,
as
in
some
southern
states
where
well
water
temperatures are above 70oF, the
flow
rates
may
need
to
be increased
to dump
heat
more
efficiently in
the
cooling
mode.
Varying well
water temperatures
will
have
little
effect on
unit
capacity
in
the
cooling
mode
(since the
well
is
connected
to
the heat
pump
condenser),
but
can have
large effects on
the
capacity
in
the
heating mode (since
the
well
is
connected
to
the
evaporator).
If
well
water
temperatures are
to
exceed 70oF,
special considerations,
such
as
closed
loop
systems,
should
be addressed.
B.
Hydronic
Side
Heat Exchanger
Operating Temperatures
The
hydronic
side heat exchangers discussed
in
section
IV
are designed
to
operate at
a
speciflc
fluid
supply
temperature. This operating temperature
will
have
to
be
supplied to
the selected
space
conditioning
heat
exchanger
by
the heat
pump.
The manufacturers
or
distributors
of
the
hydronic
side heat exchangers
publish
the
capacity
of
their equipment
at
different
operating
temperatures and
fluid flow
rates.
These
capacities
and
operating
temperatures
are
required to
select the heat
pump to
be used
in
the
system.
When sizing
the
hydronic
side
of
the
GeoSource
DualTEK
heat
pump, remember to
use
the
minimum
hydronic
loop temperature that
will
supply
the necessary
heating capacity to
the
conditioned
space.
If
an
intermediate
heat exchanger is used
between
the
closed
hydronic loop
and the open
hydronic loop
as
pictured
in
Figure
3,
expect a
10oF
operating temperature
difference between
the
two
circuits.
For example,
if
the
direct coupled
storage
tank is at
120oF,
expect
the
maximum
operating temperature
of
the open
circuit
connected
through
an
intermediate
heat
exchanger
to be
110T.
This occurs when connecting
open
loop
applications to
the closed
loop
systems
with
plate
heat
exchangers
or
with indirect
water
heaters.
C.
Building Heat Loss/fleat Gain
The
space
load
must be
estimated accurately
for
any
successful
HVAC installation.
There
are
many
guides
or
computer programs available
for
load estimation
including
the
ECONAR
GeoSource
Heat Pump
Handbook, Manual
J, and
others.
After
the heat
loss/heat
gain is completed, loop
EWT's
are
established,
and
hydronic
side heat
exchanger conditions
are
determined,
the heat
pump
can
now
be selected
using
the
hydronic
and
forced air
heat
pump
data
found
in
the
Engineering
Specifications.
Remember to
use
the
correction factors
for
the
GeoSource
DuaITEK
models that
are
listed
in
the
Engineering Specifications
manual.
Choose the
capacity
of
the heat
pump
based on
both
the
forced air heating
and
cooling
loads,
and the
hydronic heating load.
13
L.
Closed Loop Systems
Closed
loop
systems
use
a
heat exchanger
of high
density
polyethylene pipe buried underground to supply
a
tempered water solution back to
the heat
pump.
Closed
loops
operate at
higher
flow
rates than open
loops
since
the
entering water temperature
(EWT)
is
lower.
The
loop
EWT
supplied to
the heat
pump
has
a
great
effect
on
the
capacity
of
the
unit in
the
heating
mode.
Earth loops
in
cold climates
are
normally
sized
to
supply
a
wintertime
EWT
to
the heat
pump
from
32oF
down to
25oF,
which
minimizes
the
installation
cost
of
the earth
loop
and
still
maintains proper
system
operation.
The
GPM
requirements
and pressure
drops
for
loop pump sizing
are
shown
in
Table
6.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents