ETC Echoflex ER6CD Installation Manual page 6

Phase adaptive dimmer
Table of Contents

Advertisement

Echoflex Installation Guide
Phase Adaptive Dimmer
Blink Codes and Operations
The tables below describe the controller's LED blink codes and operations.
• If the controller is in factory default state, the red Power LED is solid
ON.
• If the controller has one or more devices linked to it, the red Power
LED repeats a blink code to indicate the type and number of linked
devices. Long blinks = type. Short blinks = count.
Blink Codes
Description
Factory default
Switches
Occupancy sensors
Photo sensor
(maximum of 1)
Gateways and
TimeClocks
Demand Response
Entry Door Switches
Keycard Switches
Operations
Activity
Link mode
Store link ID
Clear link ID
Factory default
Phase Adaptive Dimmer (ER6CD/ER12CD)
Power LED (red)
On solid
1 long blink followed by short
blinks that count the switches
2 long blinks followed by short
blinks that count the sensors
3 long blinks followed by short
blink that counts the sensor
4 long blinks followed by short
blinks that count the devices
5 long blinks followed by short
blinks that count the devices
6 long blinks followed by short
blinks that count the switches
7 long blinks followed by short
blinks that count the switches
Power LED
(red)
Blink
On 4 seconds
Off 4 seconds
On solid
Page 6 of 12
Learn LED
(green)
On solid
On solid
On solid
One blink
(on power-up)
Learn LED
Off
Off
Off
Off
Off
Off
Off
Off
Light
Toggle
On 4 seconds
Off 4 seconds
On solid
Echoflex

Advertisement

Table of Contents
loading

This manual is also suitable for:

Echoflex er12cd

Table of Contents