Tyco TY-FRL Series Quick Start Manual
Tyco TY-FRL Series Quick Start Manual

Tyco TY-FRL Series Quick Start Manual

2.8, 5.6, and 8.0 k-factor upright, pendent, and recessed pendent sprinklers quick response, standard coverage

Advertisement

Quick Links

Series TY-FRL — 2.8, 5.6, and 8.0 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The Series TY-FRL, 2.8, 5.6, and 8.0 K-
factor, Upright and Pendent Sprinklers
described in this data sheet are quick
response -standard coverage, solder
type spray sprinklers designed for use
in light and ordinary hazard, commer-
cial occupancies such as banks, ho-
tels, shopping malls, schools, hospi-
tals, etc.
The recessed version of the 2.8 and
5.6 K-factor, Series TY-FRL Pendent
Sprinkler, where applicable, is intend-
ed for use in areas with a finished ceil-
ing. It uses a two-piece Style 20 (1/2
inch NPT) Recessed Escutcheon. The
Recessed Escutcheon
provides 1/4
inch (6,4 mm) of recessed adjustment
or up to 1/2 inch (12,7 mm) of total ad-
justment from the flush pen-dent po-
sition. The adjustment provided by
the Recessed Escutcheon reduces
the accuracy to which the fixed pipe
drops to the sprinklers must be cut.
An intermediate level version of the
5.6 and 8.0 K-factor, Series TY-FRL
Pendent Sprinkler can be obtained
by utilizing the Series TY-FRL Pen-
dent Sprinkler in combination with the
Model S4 Shield.
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 6
NOTICE
The Series TY-FRL Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the appli-
cable standards of the National Fire
Protection Association, in addition to
the standards of any other authorities
having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condi-
tion. The installing contractor or sprin-
kler manufacturer should be contact-
ed with any questions.
Sprinkler
Identification
Numbers
TY1121. . . . . . Upright 2.8K, 1/2"NPT
TY1221 . . . . Pendent 2.8K, 1/2"NPT
TY3121 . . . . . Upright 5.6K, 1/2"NPT
TY3221 . . . . Pendent 5.6K, 1/2"NPT
TY4121 . . . . . . Upright 8.0K, 3/4"NPT
TY4221 . . . . Pendent 8.0K, 3/4"NPT
TY1121 is a redesignation for S1879
and G8973.
TY1221 is a redesignation for S1880
and G8971.
TY3121 is a redesignation for S1864
and G8974.
TY3221 is a redesignation for S1865
and G8972.
TY4121 is a redesignation for S1866
and G8174.
TY4221 is a redesignation for S1867
and G8172.
MARCH 2013
Worldwide
Worldwide
www.tyco-fire.com
www.tyco-fire.com
Contacts
Contacts
TFP130

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TY-FRL Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Tyco TY-FRL Series

  • Page 1 Worldwide Worldwide www.tyco-fire.com www.tyco-fire.com Contacts Contacts Series TY-FRL — 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General NOTICE The Series TY-FRL Sprinklers de- Description scribed herein must be installed and maintained in compliance with this The Series TY-FRL, 2.8, 5.6, and 8.0 K-...
  • Page 2 TFP130 Page 2 of 6 Frame Link Button Temperature rating Pipe thread connections per Strut Assembly Seal is indicated on ISO 7-1 can be provided on ESCUTCHEON 6 - Ejection 9 - Bushing De ector. special request. De ector PLATE SEATING Hook Spring SURFACE...
  • Page 3 TFP130 Page 3 of 6 6 - Ejection DEFLECTOR CEILING PLATE Frame SEATING SURFACE Strut Spring De ector Button Hook Seal Link WRENCH 2-13/16" Assembly AREA (71,4 mm) 2-15/16" Temperature rating is 1/2" (74,6 mm) indicated on De ector. (12,7 mm) NOMINAL 2-3/16"...
  • Page 4 TFP130 Page 4 of 6 Step 3. Tighten the sprinkler into the SPRINKLER FINISH sprinkler fitting using only the W-Type TYPE TEMP. FRAME NATURAL CHROME 9 Sprinkler Wrench (Ref. Figure RATING COLOR BRASS PLATED With reference to Figures 1, 2, and 3, CODE the W-Type 9 Sprinkler Wrench is to be applied to the wrench area.
  • Page 5 TFP130 Page 5 of 6 1/2±1/8" 2-7/8" DIA. 1/2" (12,7 mm) (12,7±3,2 mm) (73,0 mm) 1/4" (6,4 mm) FACE OF 2-1/4" DIA. MOUNTING SPRINKLER (57,2 mm) PLATE FITTING 1/8" WRENCH (3,2 mm) RECESS MOUNTING SURFACE 1-3/4" (44,5 mm) FIGURE 6 1-1/2"...
  • Page 6 Specify: W-Type 9 Sprinkler Wrench, P/N 56-000-1-849. Specify: W-Type 12 Sprinkler Wrench, P/N 56-798-1-001. GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700 Copyright © 2013 Tyco Fire Products, LP. All rights reserved. TEFLON is trademark of The DuPont Corporation.