Contec CONPROSYS CPS-CNT-3202I Reference Manual page 34

Counter module
Table of Contents

Advertisement

 Ambient Temperature
The ambient temperature is decided from the multiple measurement points which are a 50mm-
distance from the product.
During the operation, adjust the air current to make certain that the temperatures measured in the
points stay within the specified temperature. (-20 - +60°C)
Configurable controller and module(s)
Front
50
mm
Note that although the ambient temperature is within the specified range, an operational
malfunction may occur if there is other device generating high heat; the radiation will
influence the product to increase its temperature.
Do not install this product into the fully-sealed space except the case in which the internal
temperature is adjustable by equipment such as air conditioner. Long-term usage might
increase the temperature of the product and lead to malfunctions or other troubles.
When using the product in a high temperature environment, its life time will be shorten.
Perform the forced air cooling to counteract.
Installation
CPS-CNT-3202I Reference Manual (Hardware)
Temperature measurement point
50
mm
50
mm
50
mm
CAUTION
— 34 —
Side
50
mm
*   
Temperature measurement points are
shown as circles.

Advertisement

Table of Contents
loading

Table of Contents