1 1 1 1 General Description ® ® Model C14521-001 provides the Elite Pro V3 series of drives with an EtherNet/IP ® interface. The card uses a Lantronix XPort gateway module to translate EtherNet/IP ® ® Modbus RTU. When installed, the card overrides the Elite Pro V3's integrated RS422/485 communication channel.
2 2 2 2 Specifications 2.1 Electrical Power Input ® Powered internally from Elite Pro V3 drive • Network Interface RJ45 • 10/100M Ethernet • Temperature Range 0-55º C • 2.2 Physical (All dimensions are in inches) Figure 1: Dimensions...
3 3 3 3 Installation 3.1 Physical Installation ® The C14521-001 option card installs onto the control board of the Elite Pro V3 drive. ® 1. Remove all power from the Elite Pro V3 drive. This includes main and control power.
4 4 4 4 I/O Details 4.1 Module LEDs Right LED State Solid Amber 10 Mbps Solid Green 100 Mbps No Connection Table 1: Connection LED Left LED State Blinking Amber Half Duplex Activity Blinking Green Full Duplex Activity No Activity Table 2: Activity LED...
® 4.2 Ethernet/IP Input Assembly (T → The table below lists the Input Assembly (Target to Originator) information. These ® values are read from the Elite Pro drive. Index Address Name Notes Option Card Status Refer to Table 4 H1.16 16528 Drive Running 0=Stopped, 1=Running...
U1.13 with the value of L2.14. Refer to the Elite Pro V3 drive manual for additional information on using the Internal Links. Carotron can also provide a customized mapping if needed for your application. Please consult Carotron...
U1.17 in the output assembly, the internal link will write the value of U1.17 to L4.01. ® Refer to the Elite Pro V3 drive manual for additional information on using the Internal Links. Carotron can also provide a customized mapping if needed for your application. Please consult Carotron for more info.
EtherNet/IP devices. 4. Select the Elite Pro V3 item in the list. The current TCP/IP settings for the device will be displayed. Edit the values per your needs and then click Apply. After approximately 10-20 seconds, the new settings should take affect.
Page 11
Step 2: Drive Programming Certain parameters must be changed in the drive to allow the EtherNet/IP option card to communicate and function properly. The following list of parameters can be changed via the drive's keypad or by using the free CaroLink software available on our website. Also be aware that parameters U1.13-U1.20 are used in the preconfigured I/O objects and therefore should not be used for general purpose functions in the drive.
Step 3: PLC Configuration The following describes how to setup an Allen Bradley CompactLogix L16ER PLC using the Logix5000 software. Similar steps should be used for other devices and manufacturers. 1. Right click the Ethernet item under I/O Configuration in the Controller Organizer window and select New Module...
2. Type "generic" in the search box to quickly display the ETHERNET-MODULE item. Select it and click Create. Figure 4: Logix 5000: Select Module Type...
In the New Module window, fill in the following items below. Click OK when done. • Name. We suggest using a descriptive name like "EliteProV3" • Com Format: Data-INT (i.e. 16 bits) • IP Address: Enter the IP address of the option module. In this example, we used 192.168.0.181.
1. General charges any such system to so perform, which system is found to the The Standard Terms and Conditions of Sale of Carotron, Inc. (hereinafter Company’s satisfaction to have failed to so perform, or refund to the called “Company”) are set forth as follows in order to give the Company Purchaser the purchase price paid by the Purchaser to the Company in and the Purchaser a clear understanding thereof.