Leak Test And Air Evacuation - ActronAir Cascade URC-071AS Installation Manual

Super slim four-way cassette
Table of Contents

Advertisement

9. Leak Test and Air Evacuation

Leak Test
1.
Run interconnecting pipe work from condenser to
evaporator.
2.
Connect the liquid and suction pipe to the indoor and
outdoor unit flare connections (please see refrigerant piping
connection instruction).
3.
Fit service gauge to the service port on the outdoor unit.
4.
Fit a nitrogen to the service gauge.
5.
Pressurise the system to 4000kPa. A recommended
pressure test is to be performed for no less than 1 hour at
4000kPa Bubble test system and ensure pressure does not
drop during this time.
Evacuation Instructions
CAUTION
• Use a vacuum pump and a vac stat reading lower than 500 microns and an air discharge capacity above 40L/min.
• The outdoor unit does not need vacuuming DO NOT open the outdoor unit's gas and liquid stop valves.
• Ensure that your vac stat reads 500 micron or below after 2 hours. If after three hours of operation and the vac stat
reading is still above 500 microns, re-pressurise system amd check for a gas leak. If there is no leakage, perform
another evacuation for 1 to 2 hours or until the vac stat reads 500 microns or below.
• DO NOT use refrigerant gas during a leak test of a system.
Super Slim Four-Way Cassette
4000 kPa leak
for 1 hour
N
I
T
R
o
G
E
N
Fig. 9.1
Page 25
refrigerant pipes
test
To indoor unit

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents