WARNING:
Confirm factory default settings are appropriate for you battery bank prior to
commissioning to avoid potential battery damage. See the "VCS II User
Configuration" section.
The internal portion of the enclosure is sealed with no need for ventilation. The heatsinks, breaker and
external inductors are re not sealed to the enclosure and results in a NEMA 1 rating. The bottom and
top of the enclosure needs at least 12" of clearance to allow for natural convection through the rear
heatsinks and inductors. Mount the enclosure indoors away from excess heat, vibration and moisture,
and as close to the battery bank as possible.
The mounting bracket must be secured to the wall before mounting the enclosure. The hardware to
mount the bracket is not included. There are three main mounting holes at the top of the bracket on 16"
centers and two holes at the bottom of the bracket. There are also 10 additional mounting holes at the
top that can be used if necessary. Make certain that the combined mounting screws used are capable of
holding the weight of 110 lb. (50 kg).
Rev: 0
VCS II User Guide – Bergey WindPower Co.

VCS II Mounting

June 17, 2016
4