Vcs Ii Can Bus Interface; Vcs Ii Can Bus Message Specification - Bergey VCSII Owner's Manual

Table of Contents

Advertisement

The CAN Bus utilizes an isolated input to provide a galvanic isolation rating of 2500 V
connection (CN20) is provided on the controller with a pinout of:
Pin 1 – NC
Pin 2 – NC
Pin 3 – V+
Pin 4 – CANH
Pin 5 – CANL
Pin 6 – GND
Pin 7 – NC
Pin 8 - NC
1. The baud rate is fixed to 250k.
2. "Little endian" is used for CAN transmission — least significant byte is
transmitted/received first.
3. Only standard identifier (11bit) is supported.
4. Message ID Specifications:
Message
ID
1
DLC: 1
Mailbox 0 is reserved
to receive this
message.
2
DLC: 4
Mailbox 1 is reserved
to receive this
message.
Data format: single
precision float.
Rev: 0
VCS II User Guide – Bergey WindPower Co.

VCS II Can Bus Interface

VCS II CAN Bus Message Specification

Request
DLC: 1
Mailbox 16 is reserved
to echo back the
original message
DLC: 4
Mailbox 17 is reserved
to echo back the
original message.
Data format: single
precision float.
June 17, 2016
Response
This message is for command:
1 = Start (Reset), 0 = Stop.
If the system is in regular charge
or equalizer mode, the "Stop"
command will stop the system
operation.
If the system is in stop mode, the
"Start" command will start the
system.
If the system is in fault state, the
"Start(Reset" command will clear
the fault and prepare the system to
go to run state.
This message sets the battery
regulation voltage for normal
operation.
. An RJ45
RMS