7 Remove Cable Entry Points
]
]
Only use knockouts
]
shown
in
shaded
]
areas.
9 Wiring
Connect using the two way + and - terminals, observing
correct polarity.
Pass the cable through the premade entry points.
Cabling can be extended up to 30m if required, using a closed
electrical connector.
A maximum of one detector is to be fitted to the Remote
Indicator
Closed Electrical
Connector
www.emsgroup.co.uk
Radio Detector Base
IDENT
PRESS HERE TO
LOG ON
Specification
Operating
Temperature
Storage
Temperature
Humidity
Supply
CAUTION!
Fitting of an incorrect battery type invalidates the product certification and
may result in poor performance.
IP Rating
Operating
Frequency
Output
Transmitter
Power
Dimensions (mm)
Weight
Location
©2018 EMS Ltd. All rights reserved
All manuals and user guides at all-guides.com
-10°C to 55°C
5°C to 30°C
Up to 95% non-condensing
6x AA Alkaline (Panasonic LR6AD Powerline /
Varta 4006 Industrial)
IP23
868MHz
Auto adjusting 0 - 14 dB (0 - 25 mW)
85(H) x 85(W) x 45(D) (Remote Indicator Unit)
113 (Ø) 81 (D) (Wireless Detector)
0.15kg (Remote Indicator Unit)
0.40kg (Wireless Detector)
Type A: For indoor use
8 Fix to the Wall
Use suitable fasteners
and fixings.
Use all four mounting
holes.
!
IMPORTANT
Remove dust cover before use.
The device should be tested upon installation and in accordance
with local requirements.
Testing should only be carried out by a fully trained competent
person.
The Manufacturer recommends regular functional testing of at
least once per annum or in accordance with local codes of
practice.
Cleaning and repairs must be undertaken by the Manufacturers
authorised representative.
Do not open the case to clean inside the detector.
Regulatory Information
Manufacturer
EMS Ltd. Technology House, Herne Bay, Kent,
CT6 8JZ, United Kingdom
Year of
manufacture
See devices serial number label
Certification
0359
Certification body
CPR Certificate
See part listing for associated products:
DOP
[1]0359-CPR-0015, [2]0359-CPR-0017 &
[3]0359-CPR-0041
Approved to
See part listing for associated products:
EN54-5:2001. Incorporating Amendment No. 1.
Fire detection and fire alarm systems.
Part 5: Heat detectors - Point Detectors.
EN54-7:2001. Incorporating Amendment No. 1. Fire
detection and fire alarm systems.
Part 7: Smoke detectors - Point detectors using
scattered light, transmitted light or ionization.
EN54-25:2008.Incorporating corrigenda September
2010 and March 2012. Fire detection and fire alarm
systems.
Part 25: Components using radio links.
European Union
EMS declares that the radio equipment type FireCell
directives
Detector c/w Remote Indicator is in compliance with
Directive 2014/53/EU. The full text of the EU
declaration of conformity is available at the
following internet address:
www.emsgroup.co.uk
2012/19/EU (WEEE directive):
Products marked with this symbol cannot be
disposed of as unsorted municipal waste in the
European Union. For proper recycling, return this
product to your local supplier upon purchase of
equivalent new equipment, or dispose of it at
designated collection points. For more information
see www.recyclethis.info
Dispose of your batteries in an environmentally
friendly
regulations.
Page 2 of 2
40mm
10
[1]
[3]
manner
according
to
your
TSD033 Iss 3 05/09/2018
40mm
[2]
local
AJM

Advertisement

loading

This manual is also suitable for:

Firecell fcx-120-101Firecell fcx-120-111Firecell fcx-170-101