6 Electrical installation
Item
Alarm output
See
"6.3.6 To connect the alarm
output" [ 4  18].
Space cooling/heating
See
"6.3.7 To connect the space cooling/
operation control
heating ON/OFF
Changeover to
See
"6.3.8 To connect the changeover to
external heat source
external heat
control
Power consumption
See
"6.3.9 To connect the power
digital inputs
consumption digital
Safety thermostat
See
"6.3.10 To connect the safety
thermostat (normally closed
contact)" [ 4  20].
Smart Grid
See
"6.3.11 To connect a Smart
Grid" [ 4  21].
WLAN cartridge
See
"6.3.12 To connect the WLAN
cartridge (delivered as
Room thermostat
See below table.
(wired or wireless)
Wires: 0.75 mm²
Maximum running current: 100 mA
For the main zone:
▪ [2.9] Control
▪ [2.A] Thermostat type
For the additional zone:
▪ [3.A] Thermostat type
▪ [3.9] (read-only) Control
Heat pump convector
There are different controllers and
setups possible for the heat pump
convectors.
Depending on the setup, you also
need to implement a relay (field
supply, see addendum book for
optional equipment).
For more information, see:
▪ Installation manual of the heat
▪ Installation manual of the heat
▪ Addendum
Wires: 0.75 mm²
Maximum running current: 100 mA
For the main zone:
▪ [2.9] Control
▪ [2.A] Thermostat type
For the additional zone:
▪ [3.A] Thermostat type
▪ [3.9] (read-only) Control
Installation manual
14
Description
output" [ 4  19].
source" [ 4  19].
inputs" [ 4  20].
accessory)" [ 4  23].
pump convectors
pump convector options
book
for
optional
equipment
Item
Remote outdoor
See:
sensor
▪ Installation manual of the remote
▪ Addendum
Wires: 2×0.75 mm²
[9.B.1]=1 (External sensor =
Outdoor)
[9.B.2] Ext. amb. sensor offset
[9.B.3] Averaging time
Remote indoor sensor
See:
▪ Installation manual of the remote
▪ Addendum
Wires: 2×0.75 mm²
[9.B.1]=2 (External sensor = Room)
[1.7] Room sensor offset
Human Comfort
See:
Interface
▪ Installation and operation manual of
▪ Addendum
Wires: 2×(0.75~1.25 mm²)
Maximum length: 500 m
[2.9] Control
[1.6] Room sensor offset
(in case of DHW tank)
See:
3‑way valve
▪ Installation manual of the 3-way
▪ Addendum
Wires: 3×0.75 mm²
Maximum running current: 100 mA
[9.2] Domestic hot water
(in case of DHW tank)
See:
Domestic hot water
▪ Installation manual of the domestic
tank thermistor
▪ Addendum
Wires: 2
The thermistor and connection wire
(12 m) are delivered with the domestic
hot water tank.
[9.2] Domestic hot water
(in case of DHW tank)
See:
Power supply for
▪ Installation manual of the DHW
booster heater (from
indoor unit to thermal
▪ Addendum
protector of booster
heater)
Wires: (2+GND)×2.5 mm²
[9.4] Booster heater
Description
outdoor sensor
book
for
optional
equipment
indoor sensor
book
for
optional
equipment
the Human Comfort Interface
book
for
optional
equipment
valve
book
for
optional
equipment
hot water tank
book
for
optional
equipment
tank
book
for
optional
equipment
EHBH/X04+08EF
Daikin Altherma 3 R W
4P642727-1A – 2021.11