Upright, pendent, and recessed pendent sprinklers standard response, standard coverage
Hide thumbs Also See for TY-B Series:

Advertisement

Quick Links

Series TY-B, 5.6 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Standard Response, Standard Coverage
General
Description
The TYCO Series TY-B, 5.6 K-factor,
Upright (TY315) and Pendent (TY325)
Sprinklers described in this data sheet
are standard response, standard cover-
age, decorative 5 mm glass bulb type
spray sprinklers designed for use in
light, ordinary, or extra hazard, com-
mercial occupancies such as banks,
hotels, shopping malls, factories,
refineries, and chemical plants.
The recessed version of the Series
TY-B Pendent Sprinkler, where appli-
cable, is intended for use in areas with a
finished ceiling. This recessed pendent
sprinkler uses one of the following:
• A two-piece Style 15 Recessed
Escutcheon with recessed adjust-
ment up to 5/8 inch (15,9 mm) from
the flush pendent position.
• A two-piece Style 20 Recessed
Escutcheon with recessed adjust-
ment up to 1/2 inch (12,7 mm) from
the flush pendent position.
The adjustment provided by the
Recessed Escutcheon reduces the
accuracy to which the fixed pipe drops
to the sprinklers must be cut.
Intermediate level versions of Series
TY-B Sprinklers are described in
Technical Data Sheet TFP352. Sprinkler
guards and shields are described in
Technical Data Sheet TFP780.
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with
respect
to
handling
Installation of sprinkler systems and
components. Improper handling and
installation can permanently damage
a sprinkler system or its components
and cause the sprinkler to fail to
operate in a fire situation or cause it
to operate prematurely.
Page 1 of 4
NOTICE
The TYCO Series TY-B Sprinklers
described herein must be installed
and maintained in compliance with
this document, as well as with the
applicable standards of the National
Fire Protection Association, in addition
to the standards of any other authori-
ties having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted with
any questions.
Sprinkler
Identification
Numbers (SINs)
TY315 . . . . . . Upright 5.6K, 1/2˝ NPT
TY325 . . . . . Pendent 5.6K, 1/2˝ NPT
Technical
Data

Approvals

UL and C-UL Listed
FM and VdS Approved
CE Certified

Maximum Working Pressure

175 psi (12.1 bar)
250 psi (17.2 bar)*
* The maximum working pressure of 250 psi
(17.2 bar) only applies to the listing by Un-
derwriters Laboratories, Inc. (UL).

Discharge Coefficient

K = 5.6 GPM/psi
1/2

Temperature Ratings

135°F (57°C)
and
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
360°F (182°C)†
†UL, C-UL, and VdS Approved only
JANUARY 2013
Worldwide
Worldwide
Contacts
Contacts

Finishes

Sprinkler: Natural Brass, Chrome
Plated, Pure White (RAL 9010) and
Signal White (RAL 9003).
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated

Physical Characteristics

Frame . . . . . . . . . . . . . . . . . . . Bronze
Button. . . . . . . . . . . . . . Brass/Copper
Sealing Assembly
Bulb . . . . . . . . . . . . . . . . . . . . . .Glass
Compression Screw. . . . . . . . Bronze
Deflector. . . . . . . . . . . . . . . . . Bronze
(80,6 LPM/bar
1/2
www.tyco-fire.com
www.tyco-fire.com
. . . . . . . . . Stainless
Steel w/TEFLON
TFP152

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TY-B Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Tyco TY-B Series

  • Page 1 The TYCO Series TY-B Sprinklers Description described herein must be installed and maintained in compliance with The TYCO Series TY-B, 5.6 K-factor, this document, as well as with the Upright (TY315) and Pendent (TY325) applicable standards of the National Fire Protection Association, in addition...
  • Page 2 5.6 K-FACTOR, 1/2 INCH NPT, STANDARD RESPONSE Operation Installation The glass bulb contains a fluid which The TYCO Series TY-B, 5.6 K-factor, expands when exposed to heat. When Upright (TY315) and Pendent (TY325) WRENCH RECESS the rated temperature is reached, the...
  • Page 3 Closure over the Mounting Plate until FLUSH its flange contacts the ceiling. Care and Maintenance 1/8" MOUNTING (3,2 mm) SURFACE The TYCO Series TY-B, 5.6 K-factor, Upright (TY315) and Pendent (TY325) 1-3/8" (34,9 mm) CLOSURE SERIES MOUNTING Sprinklers must be maintained and ser- TY-B PLATE 7/8"...
  • Page 4 Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700 Copyright © 2013 Tyco Fire Products, LP. All rights reserved. TEFLON is trademark of The DuPont Corporation.

This manual is also suitable for:

Ty315Ty32556-000-6-38756-850-4-001

Table of Contents