Residential sprinklers 4.4 k-factor horizontal sidewall, wet pipe systems
Hide thumbs Also See for RAPID RESPONSE LFII Series:

Advertisement

Quick Links

RAPID RESPONSE Series LFII Residential Sprinklers
4.4 K-factor Horizontal Sidewall
Wet Pipe Systems
General
Description
The TYCO RAPID RESPONSE Series
LFII Residential Horizontal Sidewall
Sprinklers (TY2334) are decorative,
fast response, frangible bulb sprinklers
designed for use in residential occu-
pancies such as homes, apartments,
dormitories, and hotels. When aesthet-
ics and optimized flow characteristics
are the major consideration, the Series
LFII Residential Sprinklers (TY2334)
should be the first choice.
The Series LFII Residential Sprinklers
are intended for use in the following
scenarios:
• wet pipe residential sprinkler sys-
tems for one-and two-family dwell-
ings and mobile homes per NFPA
13D
• wet pipe residential sprinkler sys-
tems for residential occupancies up
to and including four stories in height
per NFPA 13R
• wet pipe sprinkler systems for the
residential portions of any occu-
pancy per NFPA 13
The recessed version of the Series
LFII Residential Sprinklers is intended
for use in areas with finished walls.
It employs a two-piece Style 20
Recessed Escutcheon. The Recessed
Escutcheon provides 1/4 in. (6,4 mm)
of recessed adjustment or up to 1/2 in.
(12,7 mm) of total adjustment from the
flush mounting surface position. The
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
Installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 6
adjustment provided by the Recessed
Escutcheon reduces the accuracy to
which the pipe nipples to the sprinklers
must be cut.
The Series LFII Residential Sprinklers
has been designed with heat sensitivity
and water distribution characteristics
proven to help in the control of residen-
tial fires and to improve the chance for
occupants to escape or be evacuated.
NOTICE
The Series LFII Residential Horizontal
Sidewall Sprinklers (TY2334) described
herein must be installed and main-
tained in compliance with this docu-
ment and with the applicable standards
of the NATIONAL FIRE PROTECTION
ASSOCIATION, in addition to the stan-
dards of any authorities having jurisdic-
tion. Failure to do so may impair the
performance of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identification
Number (SIN)
TY2334
Technical
Data
Approvals
UL and C-UL Listed
Certified to all requirements of
NSF/ANSI 61
(Refer to the Design Criteria section for
details on these approvals.)
Maximum Working Pressure
Maximum 175 psi (12,1 bar)
Discharge Coefficient
K= 4.4 GPM/psi
½
(63,4 LPM/bar
AUGUST 2018
Worldwide
Contacts
Temperature Rating
155°F (68°C) or 175°F (79°C)
Finishes
Natural Brass, Signal White, or Chrome
Plated
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Button . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Sealing Assembly . Beryllium Nickel w/ TEFLON
Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . 3 mm Glass
Compression Screw . . . . . . . . . . . . . . . . .Bronze
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . Copper
½
)
www.tyco-fire.com
TFP412

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the RAPID RESPONSE LFII Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Tyco RAPID RESPONSE LFII Series

  • Page 1 Escutcheon reduces the accuracy to Description which the pipe nipples to the sprinklers must be cut. The TYCO RAPID RESPONSE Series The Series LFII Residential Sprinklers LFII Residential Horizontal Sidewall has been designed with heat sensitivity Sprinklers (TY2334) are decorative,...
  • Page 2 TFP412 Page 2 of 6 Components: WRENCH FLATS Frame WRENCH Button FLATS Sealing TOP-OF- Assembly 1/2" NPT DEFLECTOR Bulb Compression 7/16" (11,1 mm) 2-7/8" DIA. Screw NOMINAL (73,0 mm) De ector MAKE-IN CENTERLINE Temperature rating OF WATERWAY is indicated on top STYLE 20 of De ector.
  • Page 3 In addition the top-of-deflector-to-ceil- W-Type 6 Sprinkler Wrench is to be ing distance is to be within the range applied to the wrench flats. The TYCO RAPID RESPONSE Series (Ref. Table A) being hydraulically Series LFII Residential Recessed LFII (TY2334) Residential Horizontal calculated.
  • Page 4 TFP412 Page 4 of 6 WET PIPE SYSTEM Minimum Flow and Residual Pressure (b, c) Max. Max. Coverage Spacing Area Ordinary Temp. Rating Intermediate Temp. Rating Minimum 155°F (68°C) 175°F (79°C) Width x Length Deflector to Installation Spacing Ft x Ft Flow Pressure Flow...
  • Page 5 Care and Limited Ordering Maintenance Warranty Procedure The TYCO RAPID RESPONSE Series For warranty terms and conditions, Contact your local distributor for avail- LFII (TY2334) Residential Horizontal visit www.tyco-fire.com. ability. When placing an order, indicate Sidewall Sprinklers must be maintained...
  • Page 6 TFP412 Page 6 of 6 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700 © 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;...

This manual is also suitable for:

Ty233451-215-1-15551-215-4-15551-215-9-15551-215-1-17551-215-4-175 ... Show all