ELECTRIC AND ELECTRONIC
THE UNIT IS ELECTRICALLY POWERED AND ALL THE RELEVANT ELECTRICAL WIRES ARE PROPERLY CONNECTED.
10
ELECTRICAL SUPPLY HAS BEEN INSTALLED IN ACCORDANCE WITH THE INSTRUCTIONS PROVIDED IN THE NAME
PLATE AND IN THE TECHNICAL DOCUMENTATION. (ELECTRICAL POWER SUPPLY: 230V/400V +/- 10% - MAXIMUM "%" OF
11
PHASE IMBALANCE: +/- 2% ) . IT IS RECOMMENDABLE TO CHECK BY USING A TESTER THE VOLTAGE VALUE (
BETWEEN PHASES AND BETWEEN PHASE AND NEUTRAL)
PHASES ARE CONNECTED IN THE PROPER SEQUENCE.
12
13
ELECTRICAL CABLES SIZE ARE CONFORM TO FLA MAX VALUE.
14
BOTH EXTERNAL AND INTERNAL ELECTRICAL WIRES ARE WELL TIGHTENED.
THE COMPRESSOR CRANCKCASE HEATERS HAVE BEEN POWERED AND HEATED AT LEAST 8 HOURS BEFORE THE
15
START-UP
16
AN ELECTRONIC SUPERVISOR (OR ANY ADDITIONAL CONTROLLER) HAS BEEN INSTALLED.
17
THE CONNECTION WIRES ARE SHIELDED.
REMOTE CONTROL DEVICES OR INTERFACES ARE CONNECTED TO THE ELECTRICAL PANEL IN CONFORMITY
18
WITH TRANE WIRING DIAGRAMS
19
ELECTRONIC DEVICES ARE INTACT AND DON'T DISPLAY ANY DAMAGE.
20
THE ELECTRICAL ABSORPTION IS STANDARD.
REFRIGERANT CIRCUIT
21
ALL CONNECTIONS ON THE REFRIGERANT CIRCUITS ARE WELL TIGHTENED.
THE ELECTRONIC LEAKAGE DETECTOR OR THE PRESSURE GAUGE LEVEL INSTALLED ON THE REFRIGERANT
CIRCUIT HAVE DETECTED ANY LEAKAGE.
22
IF ANY, SPECIFY BELOW:
23
THE COMPRESSOR OIL INDICATOR LIGHT POINTS THE MAXIMUM LEVEL.
THE FILTER INDICATOR LIGHT ON THE LIQUID LINE IS GREEN.
24
WARNING:
THE YELLOW INDICATOR LIGHT INDICATES PRESENCE OF MOISTURE IN THE CIRCUIT. IN THIS CASE
PLEASE CONTACT TRANE.
DATE:
AUTHORIZED SERVICE:
NAME AND SIGNATURE
CUSTOMER:
NAME AND SIGNATURE
Page 26
COMPLIANCE
YES
NO
COMPLIANCE
YES
NO