Specifications
Voltage
15.2 to 19.95 VDC
Current
Normal
45 µA
Alarm
45 µA
Stand-alone alarm
18 mA
Ionization source
Americium 241, 0.14 μCi
Alarm point
60 to 70°F (33 to 38°C) above ambient
temperature
Air velocity
0 to 5,000 ft./min (0 to 25.39 m/s)
UL/ULC smoke
0.67 to 3.70%/ft. obscuration
sensitivity
Environmental
Automatic
compensation
Distance from ceiling
12 in. (305 mm) max.
(wall mounted)
Compatible bases
Standard
GSA-SB, GSA-SB4
Relay
GSA-RB, GSA-RB4
Isolator
GSA-IB, GSA-IB4
Audible
GSA-AB4, GSA-AB4G, GSA-SBT,
SIGA-AB4G-LF
Operating environment
Temperature
32 to 120°F (0 to 49°C)
Relative humidity
0 to 93% noncondensing
Altitude
6,000 ft. (1,828 m) max.
Storage temperature
−4 to 140°F (−20 to 60°C)
Contact information
For contact information, see www.kiddelifesafety.com.
© 2016 Walter Kidde Portable Equipment, Inc.
All rights reserved.
2 / 2
P/N P-047550-1818-EN • REV 03 • ISS 10MAR16

Advertisement

loading

This manual is also suitable for:

Gsa-iphs