IOTA D Series Instruction Manual

Compact lamp emergency lighting equipment

Advertisement

Quick Links

IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
CAUTION – To prevent electrical shock, do not mate unit connector until installation is complete and A.C.
1.
power is supplied to the unit.
CAUTION – This fixture provides more than one power supply output source. To reduce the risk of electrical
2.
shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit and by discon-
necting the unit connector.
CAUTION – This is a sealed unit. The integral, high temperature Ni-Cad battery is not replaceable. Replace
3.
the entire unit when necessary and recycle or dispose of the nickel-cadmium battery properly.
4.
DO NOT USE OUTDOORS. The I-13-EM-J is for use with grounded, UL Listed, indoor fixtures. Not for use in
heated air outlets or hazardous locations.
The I-13-EM-J requires an unswitched A.C. power source of either 120 or 277 volts. Properly cap the unused
5.
A.C. lead.
The I-13-EM-J and A.C. ballast must be on the same branch circuit.
6.
7.
Do not mount near gas or electric heaters.
8.
The I-13-EM-J should be mounted in locations and at heights where it will not readily be subjected to tamper-
ing by unauthorized personnel.
The I-13-EM-J will cold strike and operate one 5W, 7W, or 9W, twin tube, double twin tube, 180ma or 13W twin
9.
tube, double twin tube, 285ma fluorescent lamp, each with a single lampholder per lamp.
The I-13-EM-J is for use with fluorescent downlight fixtures.
10.
11.
The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
12.
Do not use this equipment for other than intended use.
13.
Install in accordance with the National Electrical Code and local regulations.
14.
Installation and servicing should be performed by qualified personnel.
INSTRUCTION MANUAL
SAVE THESE INSTRUCTIONS
I-13-EM-J
SERIES D
COMPACT LAMP
EMERgENCY
LIgHTINg EqUIPMENT
THIS UNIT CONTAINS A
RECHARGEABLE NICKEL-
CADMIUM BATTERY. PLEASE
RECYCLE OR DISPOSE OF
PROPERLY.

Advertisement

loading

Summary of Contents for IOTA D Series

  • Page 1 I-13-EM-J SERIES D COMPACT LAMP EMERgENCY LIgHTINg EqUIPMENT INSTRUCTION MANUAL IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed, including the following: READ AND FOLLOW ALL SAFETY INSTRUCTIONS CAUTION – To prevent electrical shock, do not mate unit connector until installation is complete and A.C. power is supplied to the unit.
  • Page 2: Installation Instructions

    INSTALLATION INSTRUCTIONS CAUTION: Before installing, make certain the A.C. power is off and the I-13-EM-J unit connector is disconnected. 1. MOUNTING THE I-13-EM-J When used with ceiling mounted downlight fixtures, the I-13-EM-J should be mounted on the fixture above the ceiling. When battery packs are remote mounted, the remote distance can not exceed of the distance from ballast to lamp specified by the A.C.
  • Page 3: Operation

    OPERATION General – This unit is primarily designed to be used with compact fluorescent lamp downlight fixtures. It will wire in con- junction with the existing A.C. ballast(s) and lamp(s) to provide the emergency function. It can also be wired for emer- gency only operation.
  • Page 4: Typical Wiring Diagrams

    TYPICAL WIRING DIAGRAMS For use with 2 pin, 5 through 13 watt lamps with integral starter only ONE LAMP MAGNETIC BALLAST ONE LAMP HIGH POWER FACTOR MAGNETIC BALLAST 1. ONE LAMP MAGNETIC BALLAST 2. ONE LAMP HIGH POWER FACTOR MAGNETIC BALLAST BLK (120V) TEST BLK (120V)
  • Page 5 TYPICAL WIRING DIAGRAMS For use with 2 pin, 5 through 13 watt lamps with integral starter only. TWO NORMAL POWER FACTOR MAGNETIC BALLASTS 9. TWO NORMAL POWER FACTOR MAGNETIC BALLASTS BLK (120V) TEST UNSWITCHED LINE SWITCH WHITE � ORG (277V) EMERGENCY I-13-EM-J WHT/BLK...

This manual is also suitable for:

I-13-em-j