Contents Start Up Getting Other Information and Publications General ............... 13 Topping Off System Charge ........13 Wall Mount General Information Safety Practices ............13 Wall Mount Model Nomenclature ......4 Important Installer Note ........... 14 Shipping Damage ............. 4 High Pressure Switch ..........
GettinG Other infOrmatiOn and PublicatiOns fOr mOre infOrmatiOn, cOntact These publications can help you install the air conditioner or heat pump. You can usually find these these Publishers: at your local library or purchase them directly from the publisher. Be sure to consult current edition of each ACCA Air Conditioning Contractors of America standard.
Wall mOunt General infOrmatiOn air cOnditiOner Wall mOunt mOdel nOmenclature – cOntrOl mOdules reVisiOns mOdel number (See Spec. Sheet) caPacitY 42 - 3½ Ton VOlts & Phase cOil OPtiOns 48 - 4 Ton A - 230/208/60/1 X - Standard cOlOr OPtiOns 60 - 5 Ton B - 230/208/60/3 1 - Phenolic Coated Evaporator...
Any grille that meets with 5/8 inch louver criteria may be A plastic drain hose extends from the drain pan at used. It is recommended that Bard Return Air Grille Kit the top of the unit down to the unit base. There are RG5 or RFG5 be installed when no return duct is used.
installatiOn instructiOns Wall mOuntinG infOrmatiOn WarninG 1. Two holes for the supply and return air openings must be cut through the wall as shown in Figure 3. 2. On wood frame walls, the wall construction must be Failure to provide the 1/4 inch clearance strong and rigid enough to carry the weight of the between the supply duct and a combustible unit without transmitting any unit vibration.
4 electric heat clearance h42a1, h42l1, h48a1, h48l1, h60a1, h60l1 nOte 1: SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1/4 INCH CLEARANCE TO COMBUSTIBLE SURFACES. WarninG A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials.
fiGure 5 Wall mOuntinG instructiOns WALL STRUCTURE SEE FIGURE 3 – MOUNTING INSTRUCTIONS FACTORY SUPPLIED RAIN FLASHING. MOUNT ON UNIT BEFORE INSTALLATION SUPPLY AIR SUPPLY AIR SUPPLY AIR DUCT OPENING OPENING RETURN AIR RETURN AIR RETURN AIR OPENING OPENING OPENING BOTTOM MOUNTING WOOD OR STEEL SIDING BRACKET.
fiGure 7 cOmmOn Wall mOuntinG installatiOns SUPPLY DUCT MAY BE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN RAIN RAIN FLASHING RAFTERS FLASHING RAFTERS FINISHED CEILING SURFACE SUPPLY AIR DUCT SUPPLY AIR DUCT FINISHED CEILING SURFACE W/ GRILLE RETURN AIR RETURN AIR OPENING W/ GRILLE...
WirinG – main POWer WirinG – lOW VOltaGe WirinG Refer to the unit rating plate for wire sizing information 230/208V, 1 phase and 3 phase equipment dual primary and maximum fuse or “HACR” type circuit breaker voltage transformers. All equipment leaves the factory size.
Off sYstem charGe 8. Store cylinders in a cool area, out of direct sunlight. If a leak has occurred in the system, Bard Manufacturing recommends reclaiming, evacuating 9. Never heat cylinders above 125°F. (see criteria above), and charging to the nameplate 10.
start uP (continued) imPOrtant installer nOte Phase mOnitOr For improved start up performance wash the indoor coil All units with three phase scroll compressors are with a dish washing detergent. equipped with a 3 phase line monitor to prevent compressor damage due to phase reversal. hiGh Pressure sWitch The phase monitor in this unit is equipped with two LEDs.
seQuence Of OPeratiOn alarm relay Output COOLING – Circuit R-Y makes at thermostat pulling Alarm terminal is output connection for applications where alarm relay is employed. This terminal is powered in compressor contactor, starting the compressor and outdoor motor. The G (indoor motor) circuit whenever the compressor is locked out due to HPC or is automatically completed on any call for cooling LPC sequences as described.
Pressure temperature 75 deg. DB Low Side 62 deg. WB High Side 80 deg. DB Low Side h42a1/l1 67 deg. WB High Side 85 deg. DB Low Side 72 deg. WB High Side 75 deg. DB Low Side 62 deg. WB High Side 80 deg.
Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B H42A1 - A00, A0Z 230/208-1 1 or 2 1 or 2 H42A1 - B00, B0Z 230/208-3 H42A1 - C00, C0Z 460-3 H48A1 - A00, A0Z...
table 4 Electrical Specifications — H**L Series single circuit dual circuit Rated Minimum Maximum Field Maximum Field Volts Field Ground Model Circuit External Fuse Power Minimum External Power Power Wire Size Ground Ampacity or Ckt.