Bard H24AA-A Installation Instructions Manual

Wall-mounted packaged
Hide thumbs Also See for H24AA-A:
Table of Contents

Advertisement

Quick Links

INSTALLATION INSTRUCTIONS

WALL-MOUNTED PACKAGED
Bard Manufacturing Company, Inc.
Bryan, Ohio 43506
www.bardhvac.com

AIR CONDITIONER

Models:
H24AA-A
H36AA-A
H42AA-A
H48AA-A
H60AA-A
H24LA-A
H36LA-A
H42LA-A
H48LA-A
H60LA-A
Manual:
Supersedes: NEW
Date:
2100-647
9-3-15
Page
1 of 28

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the H24AA-A and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Bard H24AA-A

  • Page 1: Installation Instructions

    INSTALLATION INSTRUCTIONS WALL-MOUNTED PACKAGED AIR CONDITIONER Models: H24AA-A H24LA-A H36AA-A H36LA-A H42AA-A H42LA-A H48AA-A H48LA-A H60AA-A H60LA-A Bard Manufacturing Company, Inc. Manual: 2100-647 Supersedes: NEW Bryan, Ohio 43506 Date: 9-3-15 www.bardhvac.com Page 1 of 28...
  • Page 2: Table Of Contents

    CONTENTS Start Up ..............15 Getting Other Information and Publications ..3 General ..............15 Topping Off System Charge ........15 Wall Mount General Information ......4 Air Conditioner Wall Mount Model Nomenclature ..4 Safety Practices............ 15 Important Installer Note ........15 Shipping Damage ...........
  • Page 3: Getting Other Information And Publications

    GETTING OTHER INFORMATION AND PUBLICATIONS These publications can help when installing the For more information, contact these furnace. They can usually be found at the local library publishers: or purchased directly from the publisher. Be sure to consult the current edition of each standard. ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave.
  • Page 4: Wall Mount General Information

    WALL MOUNT GENERAL INFORMATION AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE – CONTROL MODULES REVISIONS MODEL SERIES (See Spec. Sheet) CAPACITY 24 – 2 Ton COIL OPTIONS VOLTS & PHASE 36 – 3 Ton X – Standard A – 230/208/60/1 42 – 3½ Ton COLOR OPTIONS 1 –...
  • Page 5: Duct Work

    5/8". Any grille that meets with 5/8" louver criteria may be used. It is recommended that Bard Return Air Grille Kit RG2W thru RG5W or RFG2W thru RFG5W be installed when no return duct is used. Contact distributor or factory for ordering information.
  • Page 6: Installation

    INSTALLATION WALL MOUNTING INFORMATION Clearances Required for Service Access and Adequate Condenser Airflow 1. Two holes for the supply and return air openings must be cut through the wall as shown in Figure 2. LEFT RIGHT DISCHARGE MODELS SIDE SIDE SIDE 2.
  • Page 7: Figure 1 Unit Dimensions

    H60A, L FIGURE 1 Dimensions of Basic Unit for Architectural and Installation Requirements (Nominal) SUPPLY RETURN WIDTH DEPTH HEIGHT MODEL H24A, L 33.300 17.125 74.563 7.88 19.88 11.88 19.88 35.00 10.88 29.75 20.56 30.75 32.06 33.25 31.00 2.63 34.13 26.06 10.55 4.19 12.00 9.00 H36A, L 38.200...
  • Page 8: Figure 2A H24 Mounting Instructions

    Manual 2100-647 Page 8 of 28...
  • Page 9: Figure 2B H36 Mounting Instructions

    Manual 2100-647 Page 9 of 28...
  • Page 10: Figure 2C H42, 48, 60 Mounting Instructions

    Manual 2100-647 Page 10 of 28...
  • Page 11: Figure 3 Electric Heat Clearance

    FIGURE 3 Electric Heat Clearance NOTE: SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1/4" CLEARANCE TO COMBUSTIBLE SURFACES. WARNING A minimum of 1/4" clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3' of ducting.
  • Page 12: Figure 4 Wall Mounting Instructions

    FIGURE 4 Wall Mounting Instructions WALL STRUCTURE FACTORY SUPPLIED RAIN FLASHING. MOUNT ON UNIT BEFORE INSTALLATION SUPPLY AIR SUPPLY AIR SUPPLY AIR DUCT OPENING OPENING RETURN AIR RETURN AIR RETURN AIR OPENING OPENING OPENING BOTTOM MOUNTING WOOD OR STEEL SIDING BRACKET.
  • Page 13: Wiring - Main Power

    FIGURE 6 Common Wall Mounting Installations SUPPLY DUCT MAY BE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN RAIN RAIN FLASHING RAFTERS FLASHING RAFTERS FINISHED CEILING SURFACE SUPPLY AIR DUCT SUPPLY AIR DUCT FINISHED CEILING SURFACE W/ GRILLE RETURN AIR RETURN AIR OPENING W/ GRILLE...
  • Page 14: Wiring - Low Voltage Wiring

    WIRING – LOW VOLTAGE WIRING Filter Switch Adjustment 1. Turn off unit power. Low Voltage Connection 2. Remove upper front door. Front screws on unit top These units use a 24-volt AC low voltage circuit. can be removed for ease of removing upper front Tables 11 –...
  • Page 15: Start Up

    8. Store cylinders in a cool area, out of direct TOPPING OFF SYSTEM CHARGE sunlight. If a leak has occurred in the system, Bard 9. Never heat cylinders above 125°F. Manufacturing recommends reclaiming, evacuating 10. Never trap liquid R-410A in manifold sets, gauge (see criteria above) and charging to the nameplate lines or cylinders.
  • Page 16: High Pressure And Low Pressure Switches

    HIGH PRESSURE AND LOW PRESSURE control module is an anti-short cycle/lockout timer with high and low pressure switch monitoring and alarm SWITCHES relay output. All H**A/H**L wall mounted air conditioner series models are supplied with a remote reset for the high Adjustable Delay-on-Make and Delay-on-Break Timer and low pressure switches.
  • Page 17: Pressure Service Ports

    Adjustments Typical Settings for Dual Unit Installation: Adjustable Delay-on-Make and Delay-on-Break Timer Unit 1: DOB set at 2 minutes and DOM is 132 seconds Unit 2: DOB set at 4 minutes and DOM is 144 seconds The potentiometer is used to select delay-on-break time from 30 seconds to 5 minutes.
  • Page 18: Figure 7 Fan Blade Setting

    SERVICE REMOVAL OF FAN SHROUD FAN BLADE SETTING DIMENSIONS 1. Disconnect all power to the unit. The correct fan blade setting for proper air delivery across the outdoor coil is shown in Figure 7. Refer to 2. Remove the screws holding both grilles, one on Table 2 for unit specific dimension.
  • Page 19: Table 3 Cooling Pressure

    TABLE 3 Cooling Pressure Air Temperature Entering Outdoor Coil °F Return Air Temp Model Pressure (DB/WB) Low Side 75/62 High Side Low Side H24A/L 80/67 High Side Low Side 85/72 High Side Low Side 75/62 High Side Low Side H36A/L 80/67 High Side Low Side...
  • Page 20: Table 4A Electrical Specifications H**A Series

    TABLE 4A Electrical Specifications H***A Series Single Circuit Multiple Circuit  Minimum  Maximum     Rated No. Field  Maximum Field Circuit External Fuse or Field Power Ground  MODEL Volts & Power Minimum External Power Ground Ampacity Ckt.
  • Page 21: Table 5 Recommended Airflow

    TABLE 5 Recommended Airflow Nominal Nominal Recommended Factory Speed Model Rated Rated Airflow Range Connection CFM * ESP * H24A, H24L 700 - 950 Single H36A, H36L 1100 1000 - 1300 High H42A, H42L 1350 1250 - 1600 H48A, H48L 1550 1450 - 1750 High...
  • Page 22: Table 9 Optional Accessories

    TABLE 9 Optional Accessories Right Hand Units Left Hand Units EHWA02-A05B EHWA02A-A05LB EHW02A-A08B EHW02A-A08LB EHWA02A-A10B EHWA02-A10LB EHWA24-A04B EHWA03-A05LB EHWA03-A05B Heater Kits EHWA03-A10LB EHWA03-A08B EHWA03-A15LB Heater Kits EHWA03-A10B EHW4TA-A05L EHWA03-A15B EHWA05-A10LB EHW4TA-A05 EHWA05-A15LB EHWA05-A10B WMCB-03A Circuit Breakers (WMCB) EHWA05-A15B WMCB-05A & EHWA05-A20B WMCB-08A Pull Disconnects...
  • Page 23: Chart - Mv Series Controller

    TABLE 11 Unit Low Voltage Terminal Connection Chart – MV Series Controller Series "2" Terminal Description MV Terminal Connection Reference Compressor on Output Signal from Jade to MV "A" on Relay Board "A" 24VAC HOT from Terminal 2 Connected to Unit Transformer to MV "R"...
  • Page 24: Chart - Mc Series Controller

    TABLE 12 Unit Low Voltage Terminal Connection Chart – MC Series Controller Series "2" Terminal Description MC Terminal Connection Reference Compressor on Output Signal from Jade to MC "A" on Relay Board "A" 24VAC HOT from Terminal 2 Connected to Unit Transformer to MC "R"...
  • Page 25: Chart - Cooling/Heating Thermostat

    TABLE 13 Unit Low Voltage Terminal Connection Chart – Cooling/Heating Thermostat Series "2" Terminal Description MC Terminal Connection Reference Compressor on Output Signal from Jade Not Used "A" 24VAC HOT from Terminal 2 Connected to Unit Transformer to Thermostat "R" on Tstat "R"...
  • Page 26: Figure 8A H***A Wiring Diagram - Top

    FIGURE 8A H***A Wiring Diagram – Top Manual 2100-647 Page 26 of 28...
  • Page 27: Figure 8B H***A Wiring Diagram - Bottom

    FIGURE 8B H***A Wiring Diagram – Bottom Manual 2100-647 Page 27 of 28...
  • Page 28: Figure 9 H***A Low Voltage Diagram For Unit And Mv Connections

    FIGURE 9 H***A Low Voltage Ladder Diagram for Unit and MV Connections Blk/Wht Filter Light Pin 6 on Vent Plug Low Voltage Pin 9 on Vent Plug Terminal Strip Controller Rd/W Bk/W R on Filter Red/Wht Compressor Switch Control Module Filter Reset Button Org/Blk Red/Wht...