CONTENTS Start Up ..............17 Getting Other Information and Publications ..3 General.............. 17 Topping Off System Charge ........17 Wall Mount General Information ......4 Safety Practices ..........17 Air Conditioner Wall Mount Model Nomenclature ..4 Important Installer Note ........17 Shipping Damage ..........
GETTING OTHER INFORMATION AND PUBLICATIONS These publications can help when installing the For more information, contact these publishers: furnace. They can usually be found at the local library or purchased directly from the publisher. Be sure to ACCA Air Conditioning Contractors of America consult the current edition of each standard.
WALL MOUNT GENERAL INFORMATION AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE – CONTROL MODULES REVISIONS MODEL SERIES (See Spec. Sheet) CAPACITY 12 – 1 Ton COIL OPTIONS VOLTS & PHASE 24 – 2 Ton X – Standard A – 230/208/60/1 COLOR OPTIONS 36 –...
5/8". Any grille that meets with 5/8" louver criteria may be used. It is recommended that Bard Return Air Grille Kit RG2W thru RG5W or RFG2W thru RFG5W be installed when no return duct is used. Contact distributor or factory for ordering information.
INSTALLATION WALL MOUNTING INFORMATION Clearances Required for Service Access and Adequate Condenser Airflow 1. Two holes for the supply and return air openings must be cut through the wall as shown in Figures LEFT RIGHT DISCHARGE MODELS 3A-D on pages 9-12. SIDE SIDE SIDE...
FIGURE 3A H12AA Mounting Instructions SEAL WITH BEAD OF CAULKING RAIN FLASHING ALONG ENTIRE LENGTH OF TOP. SUPPLIED FOAM AIR SEAL WALL WALL STRUCTURE SUPPLY AIR DUCT 17.000 7.031 7.031 2.500 RETURN AIR OPENING 5.000 19.719 10.000 5.000 6.969 17.000 19.719 NOTE: IT IS RECOMMENDED THAT A BEAD OF SILICONE...
FIGURE 4 Electric Heat Clearance NOTE: SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1/4" CLEARANCE TO COMBUSTIBLE SURFACES. WARNING A minimum of 1/4" clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3' of ducting.
FIGURE 5 Wall Mounting Instructions WALL STRUCTURE FACTORY SUPPLIED RAIN FLASHING. MOUNT ON UNIT BEFORE INSTALLATION SUPPLY AIR SUPPLY AIR SUPPLY AIR DUCT OPENING OPENING RETURN AIR RETURN AIR RETURN AIR OPENING OPENING OPENING BOTTOM MOUNTING WOOD OR STEEL SIDING BRACKET.
FIGURE 7 Common Wall Mounting Installations SUPPLY DUCT MAY BE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN RAIN RAIN FLASHING RAFTERS FLASHING RAFTERS FINISHED CEILING SURFACE SUPPLY AIR DUCT SUPPLY AIR DUCT FINISHED CEILING SURFACE W/ GRILLE RETURN AIR RETURN AIR OPENING W/ GRILLE...
WIRING – LOW VOLTAGE WIRING Filter Switch Adjustment 1. Turn off unit power. Low Voltage Connection 2. Remove upper front door. Front screws on unit top These units use a 24-volt AC low voltage circuit. Tables can be removed for ease of removing upper front 11 and 12 on pages 29 and 30 show the low voltage door.
8. Store cylinders in a cool area, out of direct TOPPING OFF SYSTEM CHARGE sunlight. If a leak has occurred in the system, Bard 9. Never heat cylinders above 125°F. Manufacturing recommends reclaiming, evacuating 10. Never trap liquid R-410A in manifold sets, gauge (see criteria above) and charging to the nameplate lines or cylinders.
HIGH PRESSURE AND LOW PRESSURE The phase monitor in this unit is equipped with two LEDs. If the Y signal is present at the phase monitor SWITCHES and phases are correct, the green LED will light. All H**A/H**L wall mounted air conditioner series If phases are reversed, the red fault LED will be lit and models are supplied with a remote reset for the high compressor operation is inhibited.
TABLE 1 Sequence of Operation Revision "2" Terminal Description Reference Compressor on Output Signal from Jade to MV Economizer Only "A" 24VAC HOT from Terminal 2 Connected to Unit Transformer 24V HOT "R" 24VAC COMMON from Unit Transformer to MV 24V COMMON "C"...
NOTE: Both high and low pressure switch controls are inherently automatic reset devices. The high pressure switch and low pressure switch cut out and cut in settings are fixed by specific air conditioner unit model. The lockout features, both soft and manual, are a function of the compressor control module.
SERVICE REMOVAL OF FAN SHROUD FAN BLADE SETTING DIMENSIONS 1. Disconnect all power to the unit. The correct fan blade setting for proper air delivery across the outdoor coil is shown in Figure 8. Refer to 2. Remove screws holding both grilles, one on each Table 2 for unit specific dimension.
TABLE 3 Cooling Pressure Air Temperature Entering Outdoor Coil °F Return Air Temp Model Pressure (DB/WB) Low Side 75/62 High Side Low Side H12A 80/67 High Side Low Side 85/72 High Side Low Side 75/62 High Side Low Side H24A/L 80/67 High Side Low Side...
TABLE 4A Electrical Specifications H***A Series Single Circuit Multiple Circuit Minimum Maximum Circuit External Fuse or Field Power Ground No. Field Rated Volts Ampacity Circuit Breaker Wire Size Wire Size Maximum Field MODEL Power Minimum...
TABLE 4B Electrical Specifications H***L Series Single Circuit Dual Circuit Minimum Maximum Circuit External Fuse or Field Power Ground No. Field Maximum Ampacity Circuit Breaker Wire Size Wire Size Rated Volts MODEL Power Minimum External...
TABLE 11 Unit Low Voltage Terminal Connection Chart – MV Series Controller Revision Terminal Description MV Terminal Connection "2" Reference Compressor on Output Signal from Jade to MV "A" on Relay Board "A" 24VAC HOT from Terminal 2 Connected to Unit Transformer to MV "R"...
TABLE 12 Unit Low Voltage Terminal Connection Chart – Cooling/Heating Thermostat Revision Terminal Description Thermostat Connection "2" Reference Compressor on Output Signal from Jade Not Used "A" 24VAC HOT from Terminal 2 Connected to Unit Transformer to Thermostat "R" on Tstat "R"...
FIGURE 11 H***A Low Voltage Ladder Diagram for Unit and MV Connections Blk/Wht Filter Light Pin 6 on Vent Plug Low Voltage Pin 9 on Vent Plug Terminal Strip Controller Rd/W Bk/W R on Filter Red/Wht Compressor Switch Control Module Filter Reset Button Org/Blk Red/Wht...
Need help?
Do you have a question about the H42AA-B and is the answer not in the manual?
Questions and answers