M E D I U M V O LTA G E P R O D U C T S
Connection for
actuator coils
Connection for
storage capacitors
Figure 9/15 a: Circuit breaker control unit
Note: Some changes to the settings of the DIP-switches (section 7.1) to become effective.
Input -MS
for voltage
supply
Input for ON/OFF
position signal
Connection for:
(sensor)
• O N button (3)
• O FF button (4)
• " Ready" lamp (2)
Treshold for undervoltage release -MU
I 1001
3
2
1
On Off
3
2
1
On Off
3
2
1
On Off
I 1001
3
2
1
On Off
Inputs:
I 1004
-MU
5
-RL1
-MO2
Delay time undervoltage release -MU
-MO1
I 1004
-MC
4
3
I 1004
2
On Off
4
3
2
On Off
4
3
2
On Off
4
3
2
On Off
I 1002
4
3
2
On Off
4
3
2
On Off
4
3
2
On Off
4
3
2
On Off
Outputs:
AUTO-OFF at declining capacitor voltage
-BB4
I 1004
-DN
1
-DR
On Off
-DC2
1
-DO2
On Off
-DC1
-DO1
I 1002
3
On Off
2
On Off
1
On Off
Rated voltage
Treshold
range
35 % ... 70%
220-240 V AC DC
84 V ... 154 V AC DC
100-127 V AC DC
45 V ... 70 V AC DC
48-60 V DC
21 V ... 33 V DC
24 -30 V DC
11 V ... 16 V DC
For VM1-T: ON
Undervoltage release deactivated
No delay
delay:
0,5 s
delay:
1 s
delay:
2 s
delay:
3 s
delay:
4 s
delay:
5 s
Deactivated (normal delivery status)
Activated (on customer demand)
Closing support for -MU
If the DIP-switch is in ON position, the
VM1-T with activated undervoltage release
-MU can be closed even if no voltage is applied
to -MU.
For VM1-T: OFF
Always ON (enables -MO2) in spite of failure
of the microprocessor)
25