Section 3: Installation Details; Gas Requirements - Prism Hardscapes Embarcadero 60 Installation, Operation & Maintenance Manual

Table of Contents

Advertisement

 
Section 3   
 
 
 
 
 
Installation Details 
3.1 Gas Requirements 
The fire table should be placed on a flat and level surface. It will arrive with the burner and burner plate 
set inside the unit. Burner hardware has been installed at the factory but will need to be checked for 
proper tightness after transportation. Refer to the corresponding section below for set‐up on your unit. 
All units must have clearance to combustible surface of 4ft on sides & 6ft from the top. Refer to the 
section below for the according to the gas type you purchased. Contact technical support if an orifice 
change is required. Tech‐support@prismhardscapes.com. 
3.1.1 Natural Gas 
Gas Pressure: 7 inches water column 
Gas Input Flow: 65,000 BTUs/HR (Manual Ignition), 85,000 BTUs/HR (PH‐Ignite), Up to 125,000 BTUs/HR 
with orifice change. 
Prior to installation, a gas professional will need to run a gas line underground below the foundation 
where your fire feature will reside. In order to do this, your gas professional will first need to determine 
the best pipe size based on fuel input requirements (BTU's/HR), gas pressure and distance from gas 
pressure regulator to fire feature. Once you have created a trench underground for your pipe, the 
stubbed‐out end should be fitted with a ½" NPT ball valve shutoff (rated for gas usage) and a flare fitting 
sized for the same size gas hose that is attached to the key valve and burner. Connect your flex hose to 
the stubbed‐out gas pipe then connect the other end to the key valve in your fire feature. The arrow on 
the key valve should be pointing the direction of the gas flow (towards the burner plate on your fire 
feature). Tighten all fittings with a wrench, do not hand tighten! Test the gas lines for leaks and loss of 
pressure over a 24‐hour period. When you are finished testing and have found no leaks, cover the pipes, 
level the ground and finish setting the foundation. Once everything is tightly sealed and connected, 
gently place your burner plate back down into your fire feature; your fire table is now ready to be 
positioned in its final location. 
Note: Check with your gas supplier to verify gas flows and pressures available at the location of your 
installation. In many cases utility companies will install larger meters at no charge to accommodate 
larger flows. 
3.1.2 Propane Gas 
Gas Pressure: 11 inches water column 
Gas Input Flow: 65,000 BTUs/HR (Manual ignition), 85,000 BTUs/HR (PH‐Ignite), Up to 125,000 BTUs/HR 
with orifice change. 
 
 