Download Print this page

iNels Elko AirTM-100NB Quick Start Manual

Pulse converter

Advertisement

Quick Links

ELKO EP, s.r.o.
Palackého 493
769 01 Holešov, Všetuly
Czech Republic
Tel.: +420 573 514 211
e-mail: elko@elkoep.com
www.elkoep.com
Made in Czech Republic
02-22/2019 Rev.: 0
Characteristics
• The Pulse converter counting quantities of pulses from the energy meters (electric-
ity, water, gas).
• The Pulse converter is designed for use on existing gauges even without impulse
output „S0" (gauge must support sensing).
• AirTM-100 converts gauge consumption using sensors - LS (LED sensor), WS (mag-
netic sensor for water meter), MS (magnetic sensor) or pulse output.
• For each power meter it is necessary to have one Pulse converter AirTM-100.
• With the wireless solution and NB-IoT communication, it can communicate instant-
ly to your chosen location and be operated immediately.
• Data is sent to the server from which it can be subsequently displayed as a smart-
phone, application, or Cloud notifi cation
• Anti-sabotage: If access to the device is unauthorized, a message is immediately
sent to the server.
• Power supply: 5-12 V DC or 1x 3.6 V batteries SAFT.
• In the case of external power, the battery is automatically disconnected and serves
as backup power.
• Protection degree IP65.
Description
1
2
3
4
5
+ -
6
7
Cloud app assignment
It is done in your Smartphone application. Enter the relevant information on the product
cover into the application.
Set the sensing type (sensor LS, WS, MS or pulse output S0).
1. Tamper
8
2. NanoSIM slot
6
3. Programming pins
4. Button SET
5. Setting pins for 3V3 / GND clamp
6. Hole for mounting on the wall Ø
4.3 mm / 0.2"
9
10
7. Power terminal
8. Antenna
9. Battery
11
10. LED indication
11. Sensor connection terminal
12
12. Bushing M16x1.5 for connecting
cable with max. diameter of 10 mm
AirTM-100NB
Pulse converter
General instrucions
Internet of Things (IoT)
• The IOT wireless communications category describes the Low Power Wide Area
(LPWA). This technology is designed to provide full-range coverage both inside and
outside buildings, energy-saving and low-cost operation of individual devices. The
NarrowBand network is available to use this standard.
Information about the NarrowBand network
• The network provides two-way communication and the only one to use the licensed
LTE band. Our devices allow band 1 (2100MHz), Band 3 (1800MHz), Band 8 (900MHz),
Band 5 (850MHz), Band 20 (800MHz) and Band 28 (700MHz).
• It uses this SIM card technology for each device.
• The advantage of NarrowBand is the use of already built-up grids, which ensures suf-
fi cient reception outside and inside buildings.
• For more information on this technology, please visit www.vodafone.cz
Caution for proper operation:
• Products are installed according to the wiring diagram given for each product.
• For proper device functionality, it is necessary to have suffi cient coverage of the se-
lected network at the installation site.
• At the same time, the device must be registered in the network. Successful device reg-
istration on a given network requires a charge for traffi c.
• Each network off ers diff erent tariff options - it always depends on the number of mes-
sages you want to send from your device. Information on these tariff s can be found in
the current version of the ELKO EP pricelist.
Assembly
1
5a
5b
+
-
5-12 V DC
1. Using a fl at-blade screwdriver gradually slide it into one groove and the other in the lid
and swing open the cover.
2. Carefully insert nanoSIM (the device must not be energized when inserting or replacing
nanoSIM!)
3. The product can be attached in two ways:
a) Directly on a fl at surface by gluing * - apply a suitable adhesive to the bottom of the
base. Place the base in the desired location and let it dry.
b) Using a suitable fastener ** by screwing - drill holes into the base with two holes of
suitable diameter corresponding to the position of the holes in the bottom of the box.
Place the base at the desired location and attach it with suitable bonding material
according to the substrate.
4. Thread the sensor through the bushing and plug it in according to the required function
- see chapter Functions, remove jumper (only after setting the function).
5. Connect the supply voltage (via the power supply the transmitter functionality message
is sent to the application)
a. on the clamp
b. Insert the battery and check the correct location.
1 / 4
2
3b
6
8
EN
Click!

Advertisement

loading

Summary of Contents for iNels Elko AirTM-100NB

  • Page 1 ELKO EP, s.r.o. AirTM-100NB Palackého 493 769 01 Holešov, Všetuly Czech Republic Pulse converter Tel.: +420 573 514 211 e-mail: elko@elkoep.com www.elkoep.com Made in Czech Republic 02-22/2019 Rev.: 0 Characteristics General instrucions • The Pulse converter counting quantities of pulses from the energy meters (electric- Internet of Things (IoT) ity, water, gas).
  • Page 2 6. Set the required function (see chapter Function) Restart 7. Fill the jumper onto the adjustment pins (see the Function chapter). • Open the cover. Power interruption (remove the battery from the device). 8. Replace and snap the front cover. When closing, the handles have to be snapped to their •...
  • Page 3 UPLINK / DOWNLINK UPLINK Byte 0-14 Function 0x01 - 0x01 Counter[0] Counter[1] Counter[2] Counter[3] Tamper: Battery: notifi cation IMEI Reserved for future use 1 - opened 1 - low level 0x02 - 0 - closed 0 - OK heartbeat ENERGY_METERING 0x02 Counter[0] Counter[1]...
  • Page 4 - this prevents Transmitting power consumption: transmission of the radio frequency signal. iNELS Air is not recommended for control- Setting ling life-saving instruments or for controlling hazardous devices such as pumps, heaters...