RM7800E,G,L,M
SPECIFICATIONS
SEQUENCE TIMING FOR NORMAL OPERATION
Device
Initiate Standby
RM7800E 10 sec.
RM7800G 10 sec.
RM7800L 10 sec.
RM7800M 10 sec.
* STANDBY and RUN can be an infinite time period.
** PURGE will be determined by which ST7800A purge card is selected.
1
The MFEP will be determined by which terminal is used, configuration jumper selected or jumper wire added, see
Figs. 8, 9, 10, 11 and 30.
APPROVAL BODIES:
Underwriters Laboratories Inc. listed, File No. MP268,
Guide No. MCCZ.
Canadian Standards Association certified, LR9S329-3.
Factory Mutual approved, Report No. JI1V9A0.AF.
IRI acceptable.
Federal Communications Commission, Part 15, Class B—
Emissions.
Fig. 1—Mounting dimensions of RM7800 Relay Module and Q7800A Subbase, in inches [millimeters].
POWER
PILOT
FLAME
MAIN
ALARM
RESET
Flame Establishing Period
Purge
Pilot
*
**
4 or 10 sec.
*
**
4 or 10 sec.
*
**
4 or10 sec.
*
**
4 or 10 sec.
BURNER CONTROL
SCROLL
MODE
SAVE
5 [127]
1
REMOVE ONLY FOR TERMINAL TEST ACCESS.
Post
Purge
Main
Run
Timing
10 or 15 sec.
*
15 sec.
10, 15 sec. or
*
15 sec.
Intermittent
10 or 15 sec.
*
15 sec.
10 sec. or
*
15 sec.
Intermittent
MOUNTING: Q7800A for panel mount or Q7800B for wall
or burner mount.
REQUIRED COMPONENTS:
Plug-in Flame Signal Amplifier, see Table 2.
Plug-in Purge Timer Cards: selectable ST7800A: two
seconds to 30 minutes.
Q7800A or Q7800B.
5
[127]
4
Firing
Energy
Interlock
Rate
Saving
Circuits
Circuit
Prepurge
Preignition,
4-wire
Yes
Lockout,
modulating
High and
Low Fire
Preignition,
No
Running,
Low Fire
Preignition,
No
Lockout,
High and
Low Fire
Preignition,
2-wire
No
Running,
isoltated
Low Fire On-Off-On
contacts
1
5
[133]
4
Approval
Code
Bodies
FM/IRI
Modulating
UL/CSA
Modulating
FM/IRI
Modulating
UL/CSA
On/Off
1
M1984A