OPERATION • STATIC CHECKOUT
Jumper
Number
Description
JR1
Pilot Flame Establishing
Period (PFEP)
JR2
Pilot Valve
Establishing Period (MFEP)
JR3
Start-up Interlock Check
a
A 30 second MFEP can be accomplished by adding a
jumper wire between terminals 19 and 5.
b
Pilot Valve /First Stage Oil Valve (Valv/Start) terminal 21.
SERVICE NOTE: Clipping and removing a site-con-
figurable jumper enhances the level of safety.
!
CAUTION
1. Use extreme care while testing the system. Line
voltage is present on most terminal connections
when power is on.
2. Open the master switch before installing or
removing a jumper on the subbase.
3. Before continuing to the next test, be sure to
remove test jumper(s) used in the previous test.
4. Replace all limits and interlocks that are not
operating properly. Do not bypass limits and
interlocks.
5. Close all manual fuel shutoff valve(s) before
starting these tests.
After checking all wiring, perform this checkout before
installing the RM7800 on the subbase. These tests verify
the Q7800 Wiring Subbase is wired correctly, and the exter-
nal controllers, limits, interlocks, actuators, valves, trans-
formers, motors and other devices are operating properly.
TABLE 6—SITE CONFIGURABLE JUMPER OPTIONS.
Intact
10 Seconds
b
/Main Flame
10 Seconds Intermittent
Disabled
Clipped
4 Seconds
15 or 30 Seconds Interrupted
Enabled
Fig. 32—Selectable site-configurable jumpers.
SELECTABLE CONFIGURATION JUMPERS
RUN/TEST SWITCH

Static Checkout

NOTE: Do not perform a dielectric test with the RM7800
installed. Internal surge protectors will break down and
conduct a current. This could cause the RM7800 to fail
the dielectric test or possibly destroy the internal light-
ning and high current protection.
EQUIPMENT RECOMMENDED
1. Voltmeter (20 kohm/volt minimum sensitivity) set on
the 0-300 Vac scale.
2. Two jumper wires; no. 14 wire, insulated, 12 inches
[304.8 mm] long with insulated alligator clips at both ends.
GENERAL INSTRUCTIONS
1. Perform all applicable tests listed in Static Checkout,
Table 7, in the order listed.
2. Make sure all manual fuel shutoff valve(s) are closed.
3. Perform only those tests designated for the specific
RM7800 model being tested.
4. Raise the setpoint of the operating controller to simu-
late a call for heat.
32
RM7800 Type
(All)
a
(RM7800G)
(All)