TAMCO UL/ULC APPROVED SMOKE DAMPER | Installation Guidelines
For Series 1000 SM & 1000 SM-M
Applies to all Options and Install Types
CALL TAMCO CUSTOMER SERVICE WITH ANY
QUESTIONS CONCERNING TAMCO SMOKE DAMPERS.
DO NOT ADJUST LINKAGE MECHANISM.
IF PROBLEM STILL EXISTS AFTER VERIFICATION AND
CORRECT ACTION, CALL TAMCO CUSTOMER SERVICE.
GENERAL INSTALLATION NOTES:
> Smoke dampers must be installed square and free from racking, to
ensure proper operation and performance.
> Dampers must be installed without stretching or compression, to
allow them to maintain their original factory adjustment, thereby
retaining their low leakage rating.
> TAMCO Smoke Dampers are approved to be installed either standing
in the vertical plane, or lying in the horizontal plane. If smoke
dampers are installed standing in the vertical plane, damper blades
must be horizontal.
> Only lift dampers via sleeve or damper frame. Never lift damper by
holding on to the damper blades or actuator.
> All connections on the back or rear side of the smoke damper frame
(opposite to sticker side), where the damper makes contact with the
duct, sleeve, or substrate must be sealed using a ⅛"
silicone sealant. (See "Installation Procedures for Smoke Damper Install
Types" for recommended silicone seal brands.)
> When installing a multiple-section smoke damper assembly, all joints
where damper frames meet must be sealed, using a bead of silicone
sealant.
> TAMCO Smoke Dampers must be kept in an environment that is free
of dirt, dust, wall texture, paint over-spray, and other contaminants,
prior to and after installation, to ensure proper damper operation and
to guard against damage.
MANUFACTURER'S RECOMMENDATIONS:
> When smoke dampers arrive at the job site, inspect all material for
obvious and hidden damage. Report any damage or missing parts to
TAMCO Customer Service.
> Store dampers indoors to protect them from environmental
conditions and to avoid damage.
> All moving parts of the damper must be inspected and cycled at
intervals not greater than every twelve (12) months or in accordance
with the latest edition of NFPA 80, 90A, 92A, local codes and the
actuator manufacturer.
> Dry lubricants are recommended.
> Smoke dampers do not typically require maintenance, if the
environment they are installed in is kept dry and clean.
© T.A. Morrison & Co. Inc., 2017
&
> Any alteration to or deviation from TAMCO's UL Classified, Smoke
> Angle clips described in these installation guidelines are minimum
> Smoke dampers must be installed at, or adjacent to, but no more
> Duct air inlets, outlets or branches shall not be located between the
bead of
(3.2 mm)
> Smoke dampers must not be installed in fiberglass-lined ducts in a
> Provide a duct hanger at a smoke damper location, when the duct
> An access door must be provided, if the damper actuator is mounted
OPTIONS FOR SERIES 1000 SM & 1000 SM-M:
&
> MR ̶ Moisture Resistance Option
> SW ̶ Salt Water Resistance Option
READ ENTIRE INSTALLATION GUIDELINES MANUAL
BEFORE INSTALLING DAMPERS.
CHECK ALL DAMPER SIZES AND TAGS TO ENSURE
THAT SMOKE DAMPERS ARE INSTALLED IN THEIR
CORRESPONDING OPENINGS.
Note that all technical information available on TAMCO's website at
www.tamcodampers.com supersedes and takes precedence over all
information contained within the printed catalog.
FRONT / TOP END UP / RIGHT HAND
Damper Installation Guidelines must be approved by the local AHJ
(Authority Having Jurisdiction).
16 ga
zinc-plated or stainless steel or .125"
(1.5 mm)
aluminum. Angle legs are to be a minimum 1" x 1"
and are to be a minimum ½"
25.4 mm)
diameter screw holes. Continuous or full-length zinc-plated,
(4 mm)
extruded aluminum, or stainless steel angles are also acceptable.
than 24"
from the point where the duct or opening passes
(609 mm)
through the smoke barrier. This must be done in accordance with
NFPA 90A.
smoke damper and the smoke barrier.
manner that will damage the lining material, or interfere with damper
blade operation.
strength is inadequate for the damper and its operator.
inside the duct.
www.tamcodampers.com
extruded
(3 mm)
(25.4 mm x
wide with 0.15"
(12.7 mm)
&

Advertisement

loading

Summary of Contents for Tamco 1000 SM Series

  • Page 1 > TAMCO Smoke Dampers must be kept in an environment that is free > An access door must be provided, if the damper actuator is mounted of dirt, dust, wall texture, paint over-spray, and other contaminants, inside the duct.
  • Page 2 OPTIONS FOR ACTUATOR MOUNTING JACKSHAFT MOUNTED (side view) ACTUATOR WIRING GUIDE: & Sealant or fire stopping, See specific mounting > Wiring used to connect each actuator shall be, as a minimum, as required by local codes details on next page No.
  • Page 3 A minimum of 1 (152 mm) fastener is required per side. *LEGEND: ²APPROVED SILICONE CAULK: 1. TAMCO Smoke Damper 4. Fastener 7. Extended flange frame 2. Silicone caulk 5. Sleeve /duct 8. Substrate fastener  Dow Corning: RTV Silicone Silastic 732, Xiameter 732, Xiameter SLT 5100 3.
  • Page 4 INSTALLATION PROCEDURES FOR | MULTI-SECTION SMOKE DAMPER ASSEMBLIES INSTRUCTIONS BELOW ARE IN ADDITION TO APPLICABLE INSTALL TYPE INSTALLATION PROCEDURES. MULTIPLE SECTION SMOKE DAMPER ASSEMBLIES SHOULD BE INSTALLED USING SAME FASTENERS AND FASTENING PATTERNS AS DESCRIBED IN THE INSTRUCTIONS FOR SINGLE-SECTION SMOKE DAMPERS. 2"...

This manual is also suitable for:

1000 sm-m series