Page 1
B E T W E E N Y O U A N D Gainesville, Texas 76241 A R C - F L A S H D A N G E R ? ® Copyright CBS ArcSafe 2019 Printed in the United States of America 2616 Sirius Road...
Page 2
RRS-4 – PLC Based Universal Remote Racking System (Rotary) The CBS ArcSafe® RRS-4 universal remote racking system is an updated PLC based version of the best selling RRS-1. The dual mode, source programmable, PLC based control system offers two different operating modes to choose from based on user preference or the application.
ANGER Before servicing any breaker, make sure that it matches the breaker discussed. If the breaker does not match the breaker described above, please call CBS ArcSafe® for more information. TTENTION The location of certain items such as mimic bus, stickers, and/or placards may interfere with the proper installation of the RSA.
Page 4
4. Secure the RSA-184F to the switch by turning the handles of the two magnets 180 degrees clockwise. 5. The RSA-184F is ready for remote operations. RSA-184D Installation and Operation...
5. Ensure that the Auto Retract (AR) function is set according to the placard on the RSA. If not specified, leave AR turned OFF. 6. Press and hold CLOSE to turn ON the breaker. 7. Press and hold TRIP to turn OFF the breaker. RSA-184D Installation and Operation...
The motor can be repositioned vertically to ensure a proper fit over the switch arm. 1. Loosen the four bolts securing the motor bracket to the frame. 2. Slide the motor bracket up or down to position the motor arm. 3. Re-tighten the four bolts. RSA-184D Installation and Operation...
Page 7
3.3 Hard Stop Adjustment The hard stops on the RSA-184F may need adjustment to ensure that the motor does not over-rotate and damage the switch. 6. Loosen the bolts holding the hard stops to the frame. RSA-184D Installation and Operation...
Page 8
8. Rotate the motor arm by hand to match the switch arm. 9. Slide the upper hard stop to contact the arm at that position. 10. Tighten the hard stop bolt. 11. Repeat with the switch in the off position using the lower hard stop. RSA-184D Installation and Operation...
Page 9
Notes RSA-184D Installation and Operation...
Page 10
Notes RSA-184D Installation and Operation...
Page 12
RSA-184D Installation and Operation 2616 Sirius Road Denton, TX 76208 Tel: 877-4-SAFETY Fax: 940-382-9435 Website: www.CBSArcSafe.com Email: info@CBSArcSafe.com ANGER Ensure that personnel using this equipment are adequately trained in the operation of the switchgear they are planning to work with; that they are correctly stationed outside the arc flash boundary;...