■ Calculation of additional refrigerant charge amount
Additional refrigerant charge amount (lbs) = [1] + [2]
[1]. Compensation by capacity of outdoor unit (Table1)
[2]. (Actual length of liquid pipe × Additional refrigerant charge amount per liquid pipe 1 ft (Table2)) × 1.3
NOTE
If the additional refrigerant amount indicates minus as the result of calculation, use the air conditioner without
additional refrigerant.
(Table1)
Compensation by capacity of outdoor unit
Outdoor unit
Model name
capacity type
(Standard Model)
072 type
MMY-MAP0726FT9P-UL
096 type
MMY-MAP0966FT9P-UL
120 type
MMY-MAP1206FT9P-UL
144 type
MMY-MAP1446FT9P-UL
168 type
MMY-MAP1686FT9P-UL
192 type
MMY-AP1926FT9P-UL
216 type
MMY-AP2166FT9P-UL
240 type
MMY-AP2406FT9P-UL
264 type
MMY-AP2646FT9P-UL
288 type
MMY-AP2886FT9P-UL
312 type
MMY-AP3126FT9P-UL
336 type
MMY-AP3366FT9P-UL
360 type
MMY-AP3606FT9P-UL
384 type
MMY-AP3846FT9P-UL
408 type
MMY-AP4086FT9P-UL
432 type
MMY-AP4326FT9P-UL
456 type
MMY-AP4566FT9P-UL
Outdoor unit
Model name
capacity type
(Space Saving Model)
192 type
MMY-AP192S6FT9P-UL
240 type
MMY-AP240S6FT9P-UL
288 type
MMY-AP288S6FT9P-UL
336 type
MMY-AP336S6FT9P-UL
(Table2)
Actual length of liquid pipe × Additional refrigerant charge amount per liquid pipe 1 ft
Liquid pipe outer diameter
Additional refrigerant amount
29-EN
Compensation by
capacity type outdoor unit
(lbs)
4.4
6.6
17.6
24.3
30.9
8.8
13.2
22.1
26.5
30.9
33.1
13.2
24.3
28.7
30.9
33.1
37.5
Compensation by
capacity type outdoor unit
(lbs)
8.8
22.1
30.9
37.5
(in)
Ø1/4"
Ø3/8"
Ø1/2"
Ø5/8"
Ø3/4"
lbs/ft
0.017
0.037
0.071
0.108
0.168
– 15 –
Example:
120 type (MMY-MAP1206FT9P-UL)
L2
L1
L4
048 type
Pipe
Liquid pipe size
L1
Ø1/2"
L2
Ø1/2"
L3
Ø3/8"
L4
Ø3/8"
L5
Ø3/8"
L6
Ø1/4"
L7
Ø1/4"
Additional refrigerant charge amount(lbs) = [1] + [2]
=
17.6 lbs + 5.798 lbs
=
23.40 lbs
[1]. Compensation by capacity of outdoor unit (Table1)
=
Compensation by 120 type
=
17.6 lbs
[2]. (Actual length of liquid pipe × Additional refrigerant charge amount per liquid pipe 1 ft (Table2)) × 1.3
=
(Lx × 0.017 lbs/ft + Ly × 0.037 lbs/ft + Lz × 0.071 lbs/ft) × 1.3
=
((L6+L7) × 0.017 lbs/ft + (L3+L4+L5) × 0.037 lbs/ft+(L1+L2) × 0.071 lbs/ft) × 1.3
=
((20 ft) × 0.017 lbs/ft + (25 ft) × 0.037 lbs/ft+(45 ft) × 0.071 lbs/ft) × 1.3
=
(0.34 lbs + 0.925 lbs + 3.195 lbs) × 1.3
=
(4.46 lbs ) × 1.3
=
5.798 lbs
Lx : Actual total length of liquid pipe Ø1/4" (ft)
Ly : Actual total length of liquid pipe Ø3/8" (ft)
Ø7/8"
Lz : Actual total length of liquid pipe Ø1/2" (ft)
0.235
L3
L5
L6
L7
036 type
018 type
015 type
Actual Piping length
30 ft
15 ft
10 ft
10 ft
5 ft
10 ft
10 ft
30-EN