Data - Mitsubishi Electric PUZ-ZM60VHA2 Service Manual

Split-type, heat pump air conditioners
Hide thumbs Also See for PUZ-ZM60VHA2:
Table of Contents

Advertisement

DATA

5
5-1. REFILLING REFRIGERANT CHARGE (R32: kg)
Service Ref.
PUZ-ZM60VHA2(-ET/-ER).UK
PUZ-ZM71VHA2(-ET/-ER).UK
PUZ-ZM100VKA2(-ET/-ER).UK
PUZ-ZM100YKA2.(-ET/-ER).UK
PUZ-ZM125VKA2(-ET/-ER).UK
PUZ-ZM125YKA2(-ET/-ER).UK
PUZ-ZM140VKA2.(-ET/-ER).UK
PUZ-ZM140YKA2(-ET/-ER).UK
PUZ-ZM200YKA2.UK
PUZ-ZM250YKA2.UK
Additional charge is required
for pipes longer than 30m
(ZM60/71/200/250)
When the total length of the piping exceeds 70 m, calculate the amount of additional charge based on the following requirements.
Note: If the calculation produces a negative number (i.e. a "minus" charge), of if calculation results in an amount that is less than the "Additional charge
amount for 70", perform the additional charge using the amount shown in "Additional charge amount for 70 m".
Main piping:
Amount of additional
Liquid line size
=
ø12.7 overall length
charge
o 0.06
[kg]
[m] o 0.06 [kg/m]
Maximum additional
ZM200
charge
ZM250
Additional charge amount
ZM200
for 70 m
ZM250
5-2. COMPRESSOR TECHNICAL DATA
Service Ref.
Compressor model
Winding Resistance
U-V
(Ω)
U-W
W-V
Service Ref.
Compressor model
Winding Resistance
U-V
(Ω)
U-W
W-V
OCH771
10 m
20 m
30 m
2.8
2.8
2.8
2.8
2.8
2.8
3.1
3.3
3.5
3.1
3.3
3.5
3.1
3.3
3.5
5.7
6.0
6.3
6.2
6.8
6.8
Main piping:
Liquid line size
+
ø9.52 overall length [m]
o 0.04 (Gas line: ø25.4)
[m] o 0.04 [kg/m]
2.9 kg
2.4 kg
1.6 kg
2.4 kg
PUZ-ZM60VHA2(-ET/-ER).UK
PUZ-ZM71VHA2(-ET/-ER).UK
SVB172FFUM1
1.160
1.160
1.160
PUZ-ZM100YKA2(-ET/-ER).UK
DVB28FCJMT
1.240
1.240
1.240
Piping length (one way)
40 m
50 m
55 m
60 m
3.2
3.6
3.6
3.2
3.6
3.6
3.6
4.0
4.2
4.4
3.6
4.0
4.2
4.4
3.6
4.0
4.2
4.4
6.7
7.1
7.3
7.5
7.4
8.0
8.3
8.6
Additional charge is required
for pipes longer than 40m
(ZM100/125/140)
Branch piping:
Liquid line size
+
+
ø9.52 overall length
o 0.03 (Gas line: ø15.88)
[m] o 0.03 [kg/m]
PUZ-ZM100VKA2(-ET/-ER).UK
DVB28FCGMT
0.480
0.480
0.480
PUZ-ZM125YKA2(-ET/-ER).UK
PUZ-ZM140YKA2(-ET/-ER).UK
DVB36FCKMT
0.750
0.750
0.750
15
70 m
75 m
100 m
4.8
5.0
6.0
4.8
5.0
6.0
4.8
5.0
6.0
"Calculate the amount
7.9
of additional refrigerant
charge using formula
9.2
provided below"
Branch piping:
Liquid line size
ZM200
ø6.35 overall length
ZM250
o 0.01
[m] o 0.01 [kg/m]
(Winding temperature at 20°C)
PUZ-ZM125VKA2(-ET/-ER).UK
PUZ-ZM140VKA2(-ET/-ER).UK
DVB36FCHMT
0.320
0.320
0.320
PUZ-ZM200YKA2.UK
PUZ-ZM250YKA2.UK
AVB52FBAMT
0.305
0.305
0.305
Initial
charged
2.8
2.8
3.6
3.6
3.6
6.3
6.8
1.2 kg
1.8 kg