6)* Setting is available when there is only 1 indoor unit connection and while the indoor unit operation is not operating.
7)* You can see no.0(no use) and no.1(use) while mode master indoor unit setting.
For the mode master indoor unit setting, select the no.1(use). And you can release the mode master unit setting
by selecting the no.2(release).
8)* Power master reset is a setting needed to supply optimized power to wired remote controller when multiple indoor units
are connected to wired remote controller in a group.
The example of installation/service mode setting
1. Press the top right corner (hidden button) of the display for more than 3 seconds
and drop it. Then you can press [ + ]/[ - ] buttons and select No.3 and press [ OK ]
button.
- Main menu will be displayed. Press [ + ]/[ - ] buttons and select No.1.
2. Press [ Mode ] button to select the number you will set.
- Press [ + ]/[ - ] buttons and select No.1.
3. Press [ Mode ] button to enter the data setting stage.
- When you enter the setting stage, the current setting value will be displayed.
4. Press [ + ]/[ - ] buttons to select No.1
- The wired remote controller option is set from both cooling and heating to
cooling only.
5. Press the [ Fan ] button to select page No.2, then Press [ + ]/[ - ] buttons to select
No.0
- The wired remote controller option is set to no use of wireless remote controller.
6. Press the [ OK ] button to save the current settings.
- Press the [ Cancel ] button for more than three seconds to exit to normal mode
without saving settings.