Download Print this page
Honeywell Fire-Lite Alarms SD365TA Installation And Maintenance Instructions

Honeywell Fire-Lite Alarms SD365TA Installation And Maintenance Instructions

Intelligent photoelectric and temperature sensors

Advertisement

Quick Links

INSTALLATION AND MAINTENANCE INSTRUCTIONS
SD365TA and SD365TA-IV
Intelligent Photoelectric and Temperature Sensors
SPECIFICATIONS
Operating Voltage Range:
Operating Current @ 24 VDC:
Maximum Alarm Current:
Maximum Current:
Operating Humidity Range:
Operating Temperature Range:
Air Velocity:
Height:
Diameter:
Weight:
Isolator Load Rating:
*Please refer to your isolator base/module manual for isolator calculation instructions.
CAN/ULC S529 listed for Open Air Protection
CAN/ULC S530 listed for Heat Detectors
This sensor must be installed in compliance with the control panel system
installation manual. The installation must meet the requirements of the Au-
thority Having Jurisdiction (AHJ). Sensors offer maximum performance when
installed in compliance with CAN/ULC S524.
GENERAL DESCRIPTION
Models SD365TA and SD365TA-IV are plug-in type multi-sensor smoke sensors
that combine a photoelectronic sensing chamber and 135°F (57.2°C) fixed
temperature heat detector across addressable-analog communications. The
sensors transmit an analog representation of smoke density over a communi-
cation line to a control panel. Rotary dial switches are provided for setting the
sensor's address. (See Figure 1.) The intelligent photoelectric and temperature
sensors also transmit an alarm signal due to heat at 135°F (57.2°C) per CAN/
ULC S530.
FIGURE 1. ROTARY ADDRESS SWITCHES:
7
8
9
6
5
10
4
3
13
2
14
1 0
15
TENS
Two LEDs on the sensor are controlled by the panel to indicate sensor status.
An output is provided for connection to an optional remote LED annunciator
(P/N RA100ZA).
Fire-Lite panels offer different features sets across different models. As a re-
sult, certain features of the photoelectric and temperature sensors may be
available on some control panels, but not on others. SD365TA will support
only LiteSpeed® protocol mode. SD365TA-IV will support either LiteSpeed or
CLIP (Classic Loop Interface Protocol) mode. The possible features available if
supported by the control panel are:
1. The sensor's LEDs can operate in three ways—on, off, and blinking–and
they can be set to red, green, or amber. This is controlled by the panel.
2. The remote output may be synchronized to the LED operation or con-
trolled independent of the LEDs.
3. Devices are point addressable up to 159 addresses.
Please refer to the operation manual for the UL listed control panel for spe-
cific operation. The photoelectric and temperature sensors require compatible
addressable communications to function properly. Connect these sensors to
listed-compatible control panels only.
SPACING
Fire-Lite recommends spacing sensors in compliance with CAN/ULC S524.
In low air flow applications with smooth ceilings, space sensors 30 feet apart
(9.1 m). When using the photoelectric and temperature sensors as a heat de-
tector in FM3210 compliant applications, space sensors 20 feet apart (6 m).
For specific information regarding sensor spacing, placement, and special ap-
plications, refer to CAN/ULC S524 or the System Smoke Detector Application
Guide, available from Fire-Lite.
15 to 32 VDC
200 uA (one communication every 5 seconds with green LED blink on communication)
2 mA @ 24 VDC (one communication every 5 seconds with red LED solid on)
4.5 mA @ 24 VDC (one communication every 5 seconds with amber LED solid on)
10% to 93% Relative Humidity, Non-condensing
32°F to 100°F (0°C to 38°C)
0 to 4000 ft./min. (0 to 1219.2 m/min.)
2.0˝ (51 mm) installed in B300A-6 Base
6.2˝ (156 mm) installed in B300A-6 Base; 4.1˝ (104 mm) installed in B501 Base
3.4 oz. (95 g)
0.0063*
7
8
6
9
5
11
4
12
3
2
1 0
ONES
WIRING GUIDE
All wiring must be installed in compliance with the Canadian Electrical Code,
applicable local codes, and any special requirements of the Authority Having
Jurisdiction. Proper wire gauges should be used. The installation wires should
be color-coded to limit wiring mistakes and ease system troubleshooting. Im-
proper connections will prevent a system from responding properly in the
event of a fire.
Remove power from the communication line before installing sensors.
1. Wire the sensor base (supplied separately) per the wiring diagram, Figure 2.
2. Set the desired address on the sensor address switches, see Figure 1.
3. Install the sensor into the sensor base. Push the sensor into the base while
turning it clockwise to secure it in place.
4. After all sensors have been installed, apply power to the control panel and
activate the communication line.
5. Test the sensor(s) as described in the TESTING section of this manual.
Dust covers provide limited protection against airborne dust particles during
shipping. Dust covers must be removed before the sensors can sense smoke.
Remove sensors prior to heavy remodeling or construction.
C0162-00
FIGURE 2. WIRING DIAGRAM:
Remote
Annunciator
+
(+)
+
2
RA
3
(–)
(–)
CLASS A OPTIONAL WIRING
(+)
TAMPER-RESISTANCE
Photoelectric and temperature sensors include a tamper-resistant capability
that prevents their removal from the base without the use of a tool. Refer to
the base manual for details on making use of this capability.
1
Woodbridge, Ontario L4L-7Z4
CAUTION
CAUTION: Do not loop wire under
terminal 1 or 2. Break wire run to
-
supervise connections.
+
+
+
2
RA
1
1
3
10 Whitmore Road
Phone: 1-800-778-9958
+
+
2
RA
1
3
C0129-11
I56-9117-001
08/08/2018

Advertisement

loading

Summary of Contents for Honeywell Fire-Lite Alarms SD365TA

  • Page 1 INSTALLATION AND MAINTENANCE INSTRUCTIONS SD365TA and SD365TA-IV 10 Whitmore Road Woodbridge, Ontario L4L-7Z4 Intelligent Photoelectric and Temperature Sensors Phone: 1-800-778-9958 SPECIFICATIONS Operating Voltage Range: 15 to 32 VDC Operating Current @ 24 VDC: 200 uA (one communication every 5 seconds with green LED blink on communication) Maximum Alarm Current: 2 mA @ 24 VDC (one communication every 5 seconds with red LED solid on) Maximum Current:...
  • Page 2 This Class B digital apparatus complies with Canadian ICES-003. violation. Fire-Lite ® and LiteSpeed ® are registered trademarks of Honeywell International, Inc. Testifire ® is a registrered trademark of SDi, LLC. I56-9117-001 ©2018 Fire-Lite. 08/08/2018...

This manual is also suitable for:

Fire-lite alarms sd365ta-iv