Download Print this page

Reference Documents; Safety Statements - ABB Infinity S Quick Start Manual

Hide thumbs Also See for Infinity S:

Advertisement

Specifications and Application
• Specifications
and
abbpowerconversion.com
External Surge Protective Device (SPD) is required on all AC inputs.
Equipment and subassembly ports: 1. are suitable for connection to intra-building or unexposed wiring or
Grounding / Bonding Network – Connect to an Isolated Ground Plane (Isolated Bonding Network) or an
Integrated Ground Plane (Mesh-Bonding Network or Common Bonding Network). Failure to properly bond
the power plant to ground may void the warranty in the event of excessive fault or surge current.
Installation Environment - Install in Network Telecommunication Facilities, OSP, or where NEC applies.
Battery return may be either Isolated DC return (DC-I) or Common DC return (DC-C).

Reference Documents

These documents are available at
Document
Title
CC848815341
Galaxy Pulsar Plus Product Manual
CPB-NES
Infinity S Power System Brochure
CC848815325
Infinity NE Install Guide

Safety Statements

Do not install this equipment over combustible surfaces.
Rules and Regulations - Follow all national and local rules and regulations when making field connections.
Compression Connectors
• U. S. or Canada installations - use Listed/Certified compression connectors to terminate Listed/
Certified field-wire conductors.
• All installations - apply the appropriate connector to the correct size conductor as specified by the
connector manufacturer, using only the connector manufacturer's recommended or approved tooling
for that connector.
Electrical Connection Securing: Torque to the values specified on labels or in the product documentation.
Cable Dress - dress to avoid damage to the conductors and undue stress on the connectors.
Circuit Breakers and Fuses
• Use only those specified in the equipment ordering guide.
• Size as required by the National Electric Code (NEC) and/or local codes.
Safety Tested Limits - Refer to the equipment ratings to assure current does not exceed:
Continuous Load (List 1) - 60% of protector rating
Maximum Load (List 2 - typically end of discharge) - 80% of protector rating.
• GMT Style Fuses - Use only fuses provided with safety caps.
Field-wired Conductors - Follow all National Electric Code (NEC) and local rules and regulations.
• Insulation rating: 90°C minimum; 105°C (minimum) if internal to enclosed equipment cabinets.
• Size AC field-wired conductors with 75°C ampacity (NEC) equal to or greater than their panel board
circuit breaker rating.
AC and DC input disconnect/protection - Provide accessible devices to remove input power in an emergency.
Alarm Signals - Provide external current limiting protection. Rating 60V, 0.5A unless otherwise noted.
Grounding - Connect the equipment chassis directly to ground. In enclosed equipment cabinets connect to the
cabinet AC service ground bus. In huts, vaults, and central offices connect to the system bonding network.
Page 8
© 2020 ABB. All rights reserved.
ordering
information
cabling;
2. can be connected to shielded intra-building cabling grounded at both
ends.
abbpowerconversion.com
are
in
the
Infinity
S
Ordering
Guide
available
at

Advertisement

loading

This manual is also suitable for:

Infinity ne-s