Specifications and Application
• Specifications
and
abbpowerconversion.com
•
External Surge Protective Device (SPD) is required on all AC inputs.
Equipment and subassembly ports: 1. are suitable for connection to intra-building or unexposed wiring or
•
Grounding / Bonding Network – Connect to an Isolated Ground Plane (Isolated Bonding Network) or an
•
Integrated Ground Plane (Mesh-Bonding Network or Common Bonding Network). Failure to properly bond
the power plant to ground may void the warranty in the event of excessive fault or surge current.
Installation Environment - Install in Network Telecommunication Facilities, OSP, or where NEC applies.
•
•
Battery return may be either Isolated DC return (DC-I) or Common DC return (DC-C).
Reference Documents
These documents are available at
Document
Title
CC848815341
Galaxy Pulsar Plus Product Manual
CPB-NES
Infinity S Power System Brochure
CC848815325
Infinity NE Install Guide
Safety Statements
Do not install this equipment over combustible surfaces.
•
Rules and Regulations - Follow all national and local rules and regulations when making field connections.
•
Compression Connectors
•
• U. S. or Canada installations - use Listed/Certified compression connectors to terminate Listed/
Certified field-wire conductors.
• All installations - apply the appropriate connector to the correct size conductor as specified by the
connector manufacturer, using only the connector manufacturer's recommended or approved tooling
for that connector.
Electrical Connection Securing: Torque to the values specified on labels or in the product documentation.
•
Cable Dress - dress to avoid damage to the conductors and undue stress on the connectors.
•
Circuit Breakers and Fuses
•
• Use only those specified in the equipment ordering guide.
• Size as required by the National Electric Code (NEC) and/or local codes.
Safety Tested Limits - Refer to the equipment ratings to assure current does not exceed:
Continuous Load (List 1) - 60% of protector rating
Maximum Load (List 2 - typically end of discharge) - 80% of protector rating.
• GMT Style Fuses - Use only fuses provided with safety caps.
Field-wired Conductors - Follow all National Electric Code (NEC) and local rules and regulations.
•
• Insulation rating: 90°C minimum; 105°C (minimum) if internal to enclosed equipment cabinets.
• Size AC field-wired conductors with 75°C ampacity (NEC) equal to or greater than their panel board
circuit breaker rating.
•
AC and DC input disconnect/protection - Provide accessible devices to remove input power in an emergency.
Alarm Signals - Provide external current limiting protection. Rating 60V, 0.5A unless otherwise noted.
•
Grounding - Connect the equipment chassis directly to ground. In enclosed equipment cabinets connect to the
•
cabinet AC service ground bus. In huts, vaults, and central offices connect to the system bonding network.