LG MULTI V WATER II ARWN Series Installation Manual page 72

Table of Contents

Advertisement

Test Run
Display
number
Master outside unit inverter compressor opera-
2 6 1
tion failure error
Slave1 outside unit inverter compressor opera-
2 6 2
tion failure error
Slave2 outside unit inverter compressor opera-
2 6 3
tion failure error
2 7 1 Master PSC/PFC Fault error
2 7 2 Slave1 PSC/PFC Fault error
2 7 3 Slave2 PSC/PFC Fault error
Master outside unit inverter DC link over-volt-
2 8 1
age error
Slave1 outside unit inverter DC link over-volt-
2 8 2
age error
Slave2 outside unit inverter DC link over-volt-
2 8 3
age error
Master outside unit inverter compressor over-
2 9 1
current
Slave1 outside unit inverter compressor over-
2 9 2
current
Slave2 outside unit inverter compressor over-
2 9 3
current
Master outside unit inverter CT under-current
3 1 1
error
Slave1 outside unit inverter CT under-current
3 1 2
error
Slave2 outside unit inverter CT under-current
3 1 3
error
Master outside unit inverter compressor dis-
3 2 1
charge temperature over-rise
Slave1 outside unit inverter compressor dis-
3 2 2
charge temperature over-rise
Slave2 outside unit inverter compressor dis-
3 2 3
charge temperature over-rise
Master outside unit static speed compressor
3 3 1
discharge temperature over-rise
Slave1 outside unit static speed compressor
3 3 2
discharge temperature over-rise
Slave2 outside unit static speed compressor
3 3 3
discharge temperature over-rise
3 4 1 Master outside unit high pressure over-rise
3 4 2 Slave1 outside unit high pressure over-rise
3 4 3 Slave2 outside unit high pressure over-rise
Master outside unit low pressure over-drop.
3 5 1
3 5 2 Slave1 outside unit low pressure over-drop.
3 5 3 Slave2 outside unit low pressure over-drop.
Master Communication error between Master
3 9 1
outside unit PFC and inverter board
Master Communication error between Master
3 9 2
outside unit PFC and inverter board
Master Communication error between Master
3 9 3
outside unit PFC and inverter board
72
Outside Unit
Error item
Root cause of error
Initial operation failure due to master outside unit inverter compressor
error
Initial operation failure due to slave1 outside unit inverter compressor
error
Initial operation failure due to slave2 outside unit inverter compressor
error
Master PSC/PFC Communication error
Slave1 PSC/PFC Communication error
Slave2 PSC/PFC Communication error
Compressor turned Off due to master outside unit inverter DC voltage
over-charge
Compressor turned Off due to slave1 outside unit inverter DC voltage
over-charge
Compressor turned Off due to slave2 outside unit inverter DC voltage
over-charge
Master outside unit inverter compressor error or operating component
(IPM/IGBT) error operation
Slave1 outside unit inverter compressor error or operating component
(IPM/IGBT) error operation
Slave2 outside unit inverter compressor error or operating component
(IPM/IGBT) error operation
Compressor turned off due to master outside unit inverter CT under-
current
Compressor turned off due to slave1 outside unit inverter CT under-
current
Compressor turned off due to slave2 outside unit inverter CT under-
current
Compressor turned off due to master outside unit inverter compressor
discharge temperature over-rise
Flow rate insufficiency or flow switch trouble of master outside unit
Compressor turned off due to slave1 outside unit inverter compressor
discharge temperature over-rise
Flow rate insufficiency or flow switch trouble of slave1 outside unit
Compressor turned off due to slave2 outside unit inverter compressor
discharge temperature over-rise
Flow rate insufficiency or flow switch trouble of slave2 outside unit
Compressor turned off due to master outside unit static speed com-
pressor discharge temperature over-rise
Compressor turned off due to slave1 outside unit static speed com-
pressor discharge temperature over-rise
Compressor turned off due to slave2 outside unit static speed com-
pressor discharge temperature over-rise
Compressor turned off due to master outside unit high pressure over-rise
Flow rate insufficiency or flow switch trouble of master outside unit
Compressor turned off due to slave1 outside unit high pressure over-rise
Flow rate insufficiency or flow switch trouble of slave1 outside unit
Compressor turned off due to slave2 outside unit high pressure over-rise
Flow rate insufficiency or flow switch trouble of slave2 outside unit
Compressor turned off due to master outside unit low pressure over-
drop.
Compressor turned off due to slave1 outside unit low pressure over-drop.
Compressor turned off due to slave2 outside unit low pressure over-drop.
Master outside unit inverter compressor current detection (CT) sensor
disconnection or short circuit
Slave1 outside unit inverter compressor current detection (CT) sensor
disconnection or short circuit
Slave2 outside unit inverter compressor current detection (CT) sensor
disconnection or short circuit

Advertisement

Table of Contents
loading

Table of Contents