LG MULTI V WATER II ARWN Series Installation Manual page 61

Table of Contents

Advertisement

Dip switch setting
1. Location of setting switch
2. Dip switch setting
1) Set the dip switch and turn on the power of the outside unit to check whether the set value is correctly
entered in the 7 segment.
2) This function is shown for only 2 seconds after the power is connected.
n Check outside unit setting
• The number on the 7 segment is displayed in order after the power is connected.
• This number represents the setting condition.
Order
Number
1
2
3
4
25
5
130
n Mode code
Model Code
133
134
130
131
135
131, 130
134, 130
134, 131
135, 134
130, 130
131, 130
131, 131
135, 131
135, 135
134, 130, 130
134, 131, 130
134, 131, 131
135, 131, 134
135, 135, 134
131, 131, 130
135, 131, 130
135, 131, 131
135, 135, 131
135, 135, 135
SW01B SW02B
-
Model code
-
Total capacity(HP)
2
Heat pump model
Normal mode display (If the dip switch is set incorrectly, it is not displayed.)
Model type (Normal, 380V)
Capacity (HP)
8
10
16
18
20
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
60
7 segment
SW01B
ON
1 2 3 4
5
6 7
If the applicable dip switch is not set correctly,
the product may not operate properly.
Item
Electrical Wiring
SW02B
ON
1 2 3 4
5
6 7
Refrigerant
R410A
Installation Manual 61

Advertisement

Table of Contents
loading

Table of Contents