Carrier PG96VAT Manual page 72

Two-stage 4-way multipoise condensing gas furnace
Table of Contents

Advertisement

SET UP
SW IT CH
SW1 -1
SW1 -2
SW1 -3
SW1 -4
SW1 -5
SW1 -6
SW1 -7 & SW1 -8
SW2-1
SW2-2
SW 2-6, 7, 8
SW 2-3, 4, 5
BASED ON 350 CFM/TON (Factory Default: SW1−5 = OFF, SW2−2 = OFF)
Model
Size
ON
5
4
3
5
4
30040
525
525
42060
525
525
48080
525
525
60080
700
700
60100
700
700
66120
875
700
Furnace Setup Switch Description
NORMAL
SW IT CH NAME
POSIT ION
Status Code Recovery
Low Heat Only
(Adaptive Heat Mode
when SW1 -2 is OFF)
Low Heat Rise
Adjustment
Comfort/Efficiency
Adjustment
CFM per ton adjust
Component Self Test
Blower OFF delay
ON or OFF
Twinning
CFM per ton Adjust
AC (Cooling Airflow)
CF (Continuous Fan)
ON
ON
3
5
4
3
5
4
3
700
875
700
875
700
875
875
1050
875
1050
875
1050
Fig. 66 − Furnace Setup Switch Description
DESCRIPT ION OF USE
Turn ON to retrieve up to 7 stored status codes for
OFF
troubleshooting assistance when R thermostat lead is
disconnected.
When SW1 -2 is OFF allows two-stage operation with a single
stage thermostat. Turn ON when using two- stage thermostat to
OFF
allow Low Heat operation when R to W/W1 closes and High Heat
operation when R to W/W1 and W2 close.
Turn ON to increase Low Heat airflow by 1 8 percent. This
OFF
compensates for increased return air temperature caused with
bypass humidifier.
Turn ON to decrease low heat airflow by approximately 7 percent
ON
and high heat by approximately 1 0 percent for maximum comfort
Turn ON for 400 CFM per ton, Turn OFF for 350 CFM per ton.
OFF
See also SW2.
Turn ON to initiate Component Self Test for troubleshooting
OFF
assistance when R thermostat lead is disconnected. Turn OFF
when Self Test is completed.
Blower Off Delay time – adjustable 90 seconds to 1 80 seconds.
See table in Adjustments section or refer to unit wiring diagram.
Allows for selection of furnace Main (OFF) or Secondary (ON)
OFF
when Twinned furnace setup is required. See kit instructions for
further directions on installation and setup.
Allows additional CFM per ton selections when used with SW 1 -5
325 CFM per ton (nominal) when SW 2-2 ON and SW 1 -5 OFF
350 CFM per ton (nominal) when SW 2-2 OFF and SW 1 -5 OFF
OFF
370 CFM per ton (nominal) when SW2-2 ON and SW 1 -5 ON
400 CFM per ton (nominal) when SW 2-2 OFF and SW 1 -5 ON
See Air Delivery Tables for model specific CFM vs. static
pressure
The AC setup switches select desired cooling or high stage
OFF
cooling (two stage units) airflow. See Cooling Air Delivery Tables
for specific switch settings.
The CF setup switches select desired Continuous Fan Airflow
The CF switch position is the low cooling airflow selection for two
stage cooling units.
OFF
The CFM values are shown in the Air Delivery Tables below for
SW 2 settings. SW 2-3, 4, 5 cannot be set for airflow higher than
SW 2-6, 7, 8. See Continuous Fan Air Flow Table for specific
switch settings.
ON
ON
5
4
3
5
4
3
875
875
1050
1225
1050
1225
1225
1400
1225
1400
1225
1400
72
ON
ON
ON
5
4
3
5
4
3
875
875
1225
1225
1400
1400
1750
1750
1750
1750
1750
1925
A14402