Hydraulic balancing of UFH manifold
The heating manifold can be delivered in sizes of 2-15 loops. The
necessary hydraulic balancing within the circuits have to be set at
regulation valves placed in the return manifold as follow:
1 Remove the cap from the valve inlet in return manifold bar.
2 Turn the cap over so that the square connector is down.
Put the cap on the regulation valve and close it.
3 Open the cap 0,25 x.
4 Open the cap as many turns as necessary until you reach the
planning documentation.
Warning!
Hazard to life due to valves under pressure:
When completely unscrewed, the valves will shoot out of
the thread.
Never tum the valves counter clockwise more than 4
times.
1
3
OPEN
0,25 x
1,5 L/min
Uponor floor heating calculations
Uponor Fußbodenheizungsberechnung
Uponor vloerverwarmingsberekening
Calculation du chauffage par le sol Uponor
Calcolo riscaldamento a pannelli radianti Uponor
Room heating circuit data
Raum-Heizkreis-Daten
Ruimte- en verwarminggroepsgegevens
Données des pièces - circuits de chauffage
Dati circuito riscaldamento locale
Room No.
Heating circuit No.
Quantity of water
Valve adjustment
Raum-Nr.
Heizkreis-Nr.
Wassermenge
Ventileinstellung
Ruimte-Nr.
Verwarmingsgroep nr.
Hoeveelheid water
Ventielvoorinstelling
N° de la pièce
N° du circuits de
Quantité d'eau
Réglage de la vanne
Num. locale
chauffage
Quantità di acqua
Tartura della valvola
Num. circuito
L/min
riscaldamento locale
1
1
2
0,5
1
2
5
2
3
2
3
4
4
1,5
4
5
Uponor Combi Port BASE XU l Installation manual l 21
2
CLOSE
4
3
1
4
2
Need help?
Do you have a question about the KaMo Combi Port BASE XU and is the answer not in the manual?