Bailey INFI 90 NTAI06 Instruction

Analog input termination unit

Advertisement

Quick Links

E96-440
®
®
Analog Input Termination Unit
(NTAI06)
Process Control and
Automation Solutions
from Elsag Bailey Group

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the INFI 90 NTAI06 and is the answer not in the manual?

Questions and answers

Summary of Contents for Bailey INFI 90 NTAI06

  • Page 1 E96-440 ® ® Analog Input Termination Unit (NTAI06) Process Control and Automation Solutions from Elsag Bailey Group...
  • Page 2 The information contained in this document is subject to change without notice. Elsag Bailey, its affiliates, employees, and agents, and the authors and contributors to this publication specif- ically disclaim all liabilities and warranties, express and implied (including warranties of merchantability and...
  • Page 3 This manual explains how to install and use the NTAI06 on the INFI 90 system. It has sections that describe the setup and cabling. Appendix A contains quick reference information about the IMASI03 module. ® INFI 90 is a registered trademark of Elsag Bailey Process Automation. I-E96-440A...
  • Page 4 ® List of Effective Pages Total number of pages in this instruction is 30, consisting of the following: Page No. Change Date Preface Original List of Effective Pages Original iii through vi Original 1-1 through 1-5 Original 2-1 through 2-1 Original Original 4-1 through 4-2...
  • Page 5 Safety Summary GENERAL Equipment Environment WARNINGS All components, whether in transportation, operation or storage, must be in a noncorrosive environment. Electrical Shock Hazard During Maintenance Disconnect power or take precautions to insure that contact with energized parts is avoided when servicing. SPECIFIC Remove modules (slave or termination) from their assigned slots CAUTIONS...
  • Page 6 ® Sommaire de Sécurité AVERTISSEMENTS Environnement de l’équipement D’ORDRE Ne pas soumettre les composants à une atmosphère corrosive lors GÉNÉRAL du transport, de l’entreposage ou l’utilisation. Possibilité de chocs électriques durant l’entretien Débrancher l’alimentation ou prendre les précautions pour éviter tout contact avec des composants sous tension durant l’entretien.
  • Page 7: Table Of Contents

    Table of Contents Page SECTION 1 - INTRODUCTION ....................1-1 OVERVIEW ........................1-1 INTENDED USER ......................1-1 TERMINATION UNIT DESCRIPTION ................1-1 FEATURES........................1-2 INSTRUCTION CONTENT .....................1-3 HOW TO USE THIS MANUAL ..................1-4 GLOSSARY OF TERMS AND ABBREVIATIONS .............1-4 REFERENCE DOCUMENTS..................1-4 NOMENCLATURE ......................1-5 SPECIFICATIONS ......................1-5 SECTION 2 - INSTALLATION .....................2-1 INTRODUCTION......................2-1 SPECIAL HANDLING ....................2-1...
  • Page 8 ® List of Figures Title Page 1-1. Application Example for NTAI06 ................1-2 2-1. Jumper Locations and Terminal Assignments for NTAI06 Revision A Hardware (6639364A1) ..................2-3 2-2. Jumper Locations and Terminal Assignments for NTAI06 Revision B Hardware (6639364B1)..................2-4 2-3.
  • Page 9: Section 1 - Introduction

    SECTION 1 - INTRODUCTION OVERVIEW The IMASI03 Universal Analog Slave Module uses the NTAI06 Analog Input Termination Unit to terminate sixteen analog sig- nals from field equipment. The signals pass through the IMASI03 IMMFP01, IMMFP02 IMMFP03 Multi-Function Processor. This manual explains the purpose, set up, handling precautions and steps to install the NTAI06 termination unit.
  • Page 10: Features

    INTRODUCTION ® COMMUNICATION HIGHWAY (INFI-NET OR PLANT LOOP) COMMUNICATION MODULES CONTROLWAY IMMFP01 IMMFP02 IMMFP03 OTHER MODULES SLAVE EXPANDER BUS IMASI03 OTHER SLAVES NTAI06 ANALOG INPUTS T00719A Figure 1-1. Application Example for NTAI06 FEATURES The design of the NTAI06, as with all INFI 90 devices, allows for flexibility in creating a process management system.
  • Page 11: Instruction Content

    Details how to replace a TU. Repair/Replacement Procedures Support Services Describes the support services (spare parts, training, docu- mentation, etc.) available from Bailey Controls Company. Appendix A Shows the jumper settings, board layout and cabling for the IMASI03 Universal Analog Slave Input Module. INSTRUCTION CONTENT...
  • Page 12: How To Use This Manual

    NTAI06. Table 1-2. Reference Documents Number Document I-E96-301 Universal Analog Input Slave Module (IMASM03) I-E96-500 Site Planning and Preparation ® Network 90 is a registered trademark of Elsag Bailey Process Automation. HOW TO USE THIS MANUAL 1 - 4 I-E96-440A...
  • Page 13: Nomenclature

    Sea level to 3 km (1.86 miles) Air Quality Noncorrosive Cooling Requirements No cooling is necessary when used in Bailey Controls cabinets and operated within stated limits. Certification CSA certified for use as process control equipment in an ordinary (nonhazardous) location.
  • Page 14: Section 2 - Installation

    SPECIAL H ANDLING Observe these steps when handling electronic circuitry: NOTE: Always use the Bailey Controls Field Static Kit (part number 1948385A1 - consisting of two wrist straps, ground cord assembly, alligator clip, and static dissipating work surface) when working with modules.
  • Page 15: Unpacking And Inspection

    They are 31.25 milliamp, 125 volt fuses, (Bailey part number 1945820A10310). Revision A (assembly number 6639364A1) also has one fuse F17. It is a 2.0 amp, 250 volt fuse, (Bailey part number 1948182A32001). The fuse is shipped installed on the revision A assembly termination units in fuse clip F17.
  • Page 16: Jumper Settings

    3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 +24V 2 AMP BAILEY REPLACEMENT CHASSIS FUSE PART NO. GROUND 1948182 32001 T00720A Figure 2-1. Jumper Locations and Terminal Assignments for NTAI06 Revision A Hardware (6639364A1)
  • Page 17: Installing The Termination Unit

    INSTALLATION ® J 33 T B 2 J 41 T B 1 J 2 5 J 57 J1 7 J 49 J 1 0 J 42 J 34 J 2 6 J 58 J 18 J 50 J 11 J 43 J 35 J 2 7 J 59...
  • Page 18: Typical Input Circuit For Ntai06

    INSTALLATION BAILEY REPLACEMENT FUSE PART NUMBER FOR F1-F16: 1945820A10310 FIELD INPUT J33-J48 J1-J16 F1-F16 TO IMASI03 FIELD INPUT –V J49-J64 J17-J32 250 Ω TO IMASI03 –V FIELD INPUT TO IMASI03 SUPPLY +24 V I/O COM INPUT INPUT INPUT INPUT INPUT...
  • Page 19: Cable Connections

    INSTALLATION ® Table 2-2. NTAI06 Input Types Input Type Signal Type Thermocouple TC Types: E, J, K, L, N, (14 AWG), N (28 AWG), R, S, T, U, Chinese E, Chinese S Millivolt mV range: -100 mV to +100 mV High Level H.L.
  • Page 20: Installation For Revision A And B Hardware Ntai06

    INSTALLATION STANDOFF TABS CHASSIS COMMON MOUNTING SCREWS SCREW FIELD TERMINATION PANEL T00592A Figure 2-4. Installation for Revision A and B Hardware NTAI06 Remove modules (slave or termination) from their assigned CAUTION slots before installing a cable to that slot. Failure to do so could result in damage to the module or station.
  • Page 21: Cable Connections For Ntai06

    INSTALLATION ® ANALOG SLAVE TERMINATION UNIT CABLE CHANNELS 11-16 FIELD IMASI03 NTAI06 WIRING NKAS01/11 (NOTE 1) CHANNELS 1-10 NOTES: 1. NKAS01 HAS PVC INSULATION (SPECIFY LENGTH UP TO 200 FT). NKAS11 HAS NON-PVC INSULATION (SPECIFY LENGTH UP TO 200 FT). 2.
  • Page 22: Terminal Block Wiring

    INSTALLATION Terminal Block Wiring We strongly recommend turning off power before doing any termination unit wiring. Failure to do so could result in equip- CAUTION ment damage. Do not apply power without verifying all wire connections. Il est fortement recommande de debracher l'alimentation elec- trique avant d'effectuer tout connexion aux cartes de raccord- ATTENTION ment des units.
  • Page 23: Ntai06 Connection Examples

    INSTALLATION ® NTAI06 TERMINATION UNIT IMASI03 NKAS01/11 CABLE ISOLATED COMMON – DIFFERENTIAL VOLTAGE ISOLATED FROM I/O COMMON NTAI06 TERMINATION UNIT TRANSMITTER IMASI03 +24 V FUSE NKAS01/11 CABLE – 1-5 V SYSTEM-POWERED – 4-20 mA I/O COM NON-ISOLATED IMASI03 NKAS01/11 CABLE -10 V TO +10 V SO UR CE –...
  • Page 24 INSTALLATION If input or output circuits are a shock hazard after disconnect- ing system power at the power entry panel, then the door of the CAUTION cabinet containing these externally powered circuits must be marked with a warning stating that multiple power sources exist.
  • Page 25: Section 3 - Maintenance

    SECTION 3 - MAINTENANCE INTRODUCTION The RTD analog input termination unit requires limited main- tenance. This section contains a maintenance schedule. MAINTENANCE SCHEDULE Execute the tasks in Table at the specified intervals. Table 3-1. Maintenance Schedule Task Interval Clean and tighten all power and Every 6 months or during plant grounding connections shutdown, whichever occurs first.
  • Page 26: Section 4 - Repair/Replacement Procedures

    SECTION 4 - REPAIR/REPLACEMENT PROCEDURES INTRODUCTION This section explains the replacement procedures for the NTAI06 Analog Input Termination Unit. REPLACEMENT PROCEDURES If a TU is faulty, replace it with a new one. DO NOT try to repair the TU. Replacing components may affect performance and certification.
  • Page 27: Replacing Fuses

    REPAIR/REPLACEMENT PROCEDURES ® 8. Insert the tabs of the circuit board into the proper slots of the field termination panel standoff and slide the circuit board into position. 9. Secure the termination unit circuit board to the field termi- nation panel with two screws. Do not overtighten. 10.
  • Page 28: Section 5 - Support Services

    SECTION 5 - SUPPORT SERVICES INTRODUCTION Bailey Controls Company is ready to help in the use, applica- tion and repair of its products. Contact the nearest sales office to make requests for sales, applications, installation, repair, overhaul and maintenance contract services.
  • Page 29: Appendix A - Universal Analog Slave Input Module (Imasi03

    APPENDIX A - UNIVERSAL ANALOG SLAVE INPUT MODULE (IMASI03) INTRODUCTION The IMASI03 Universal Analog Slave Input Module uses the NTAI06 to terminate analog inputs. Jumpers on the NTAI06 Termination Unit configure up to 16 analog inputs for the IMASI03. Each NTAI06 accepts analog inputs for either system powered four to 20 milliamp, externally powered four to 20 mil- liamp, three-wire RTD, differential or single ended voltage.
  • Page 30 UNIVERSAL ANALOG SLAVE INPUT MODULE (IMASI03) ® Table A-1. IMASI03 Address Switch Settings (SW1) Address Address Example 1 2 3 4 5 6 7 8 Example 1 2 3 4 5 6 7 8 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 1 0 0 1 0 0 1 0 1 0 0 1...
  • Page 31 Index Application example ........... 1-2 Jumper configurations..........2-5 Jumper locations Revision A Hardware (6639364A1) 2-3 Jumper locations Revision B Hardware (6639364B1) 2-4 Cable applications ............2-6 Cable connections ............2-6 Connection examples ..........2-9 Maintenance ...............3-1 Maintenance schedule ..........3-1 Features ..............1-2 Fuses..............
  • Page 32 ® Index (continued) Termination unit description ........1-1 Training............... 5-1 Technical documentation ..........5-1 Terminal assignments Revision A Hardware (6639364A1) ...............2-3 Terminal assignments Revision B Hardware Unpacking and inspection .......... 2-2 (6639364B1) ...............2-4 Index - 2 28 February 1994 DSD I-E96-XXXXXXXXX...
  • Page 33 Telefax 39-10-6582-941 Telephone 49-69-799-0 Telefax 65-292-9011 Telefax 49-69-799-2406 Form I-E96-440A Litho in U.S.A. 692 Copyright © 1992 by Elsag Bailey Process Automation, As An Unpublished Work ® Registered Trademark of Elsag Bailey Process Automation ™ Trademark of Elsag Bailey Process Automation...