E96-440 ® ® Analog Input Termination Unit (NTAI06) Process Control and Automation Solutions from Elsag Bailey Group...
Page 2
The information contained in this document is subject to change without notice. Elsag Bailey, its affiliates, employees, and agents, and the authors and contributors to this publication specif- ically disclaim all liabilities and warranties, express and implied (including warranties of merchantability and...
Page 3
This manual explains how to install and use the NTAI06 on the INFI 90 system. It has sections that describe the setup and cabling. Appendix A contains quick reference information about the IMASI03 module. ® INFI 90 is a registered trademark of Elsag Bailey Process Automation. I-E96-440A...
Page 4
® List of Effective Pages Total number of pages in this instruction is 30, consisting of the following: Page No. Change Date Preface Original List of Effective Pages Original iii through vi Original 1-1 through 1-5 Original 2-1 through 2-1 Original Original 4-1 through 4-2...
Page 5
Safety Summary GENERAL Equipment Environment WARNINGS All components, whether in transportation, operation or storage, must be in a noncorrosive environment. Electrical Shock Hazard During Maintenance Disconnect power or take precautions to insure that contact with energized parts is avoided when servicing. SPECIFIC Remove modules (slave or termination) from their assigned slots CAUTIONS...
Page 6
® Sommaire de Sécurité AVERTISSEMENTS Environnement de l’équipement D’ORDRE Ne pas soumettre les composants à une atmosphère corrosive lors GÉNÉRAL du transport, de l’entreposage ou l’utilisation. Possibilité de chocs électriques durant l’entretien Débrancher l’alimentation ou prendre les précautions pour éviter tout contact avec des composants sous tension durant l’entretien.
Table of Contents Page SECTION 1 - INTRODUCTION ....................1-1 OVERVIEW ........................1-1 INTENDED USER ......................1-1 TERMINATION UNIT DESCRIPTION ................1-1 FEATURES........................1-2 INSTRUCTION CONTENT .....................1-3 HOW TO USE THIS MANUAL ..................1-4 GLOSSARY OF TERMS AND ABBREVIATIONS .............1-4 REFERENCE DOCUMENTS..................1-4 NOMENCLATURE ......................1-5 SPECIFICATIONS ......................1-5 SECTION 2 - INSTALLATION .....................2-1 INTRODUCTION......................2-1 SPECIAL HANDLING ....................2-1...
Page 8
® List of Figures Title Page 1-1. Application Example for NTAI06 ................1-2 2-1. Jumper Locations and Terminal Assignments for NTAI06 Revision A Hardware (6639364A1) ..................2-3 2-2. Jumper Locations and Terminal Assignments for NTAI06 Revision B Hardware (6639364B1)..................2-4 2-3.
SECTION 1 - INTRODUCTION OVERVIEW The IMASI03 Universal Analog Slave Module uses the NTAI06 Analog Input Termination Unit to terminate sixteen analog sig- nals from field equipment. The signals pass through the IMASI03 IMMFP01, IMMFP02 IMMFP03 Multi-Function Processor. This manual explains the purpose, set up, handling precautions and steps to install the NTAI06 termination unit.
INTRODUCTION ® COMMUNICATION HIGHWAY (INFI-NET OR PLANT LOOP) COMMUNICATION MODULES CONTROLWAY IMMFP01 IMMFP02 IMMFP03 OTHER MODULES SLAVE EXPANDER BUS IMASI03 OTHER SLAVES NTAI06 ANALOG INPUTS T00719A Figure 1-1. Application Example for NTAI06 FEATURES The design of the NTAI06, as with all INFI 90 devices, allows for flexibility in creating a process management system.
Details how to replace a TU. Repair/Replacement Procedures Support Services Describes the support services (spare parts, training, docu- mentation, etc.) available from Bailey Controls Company. Appendix A Shows the jumper settings, board layout and cabling for the IMASI03 Universal Analog Slave Input Module. INSTRUCTION CONTENT...
NTAI06. Table 1-2. Reference Documents Number Document I-E96-301 Universal Analog Input Slave Module (IMASM03) I-E96-500 Site Planning and Preparation ® Network 90 is a registered trademark of Elsag Bailey Process Automation. HOW TO USE THIS MANUAL 1 - 4 I-E96-440A...
Sea level to 3 km (1.86 miles) Air Quality Noncorrosive Cooling Requirements No cooling is necessary when used in Bailey Controls cabinets and operated within stated limits. Certification CSA certified for use as process control equipment in an ordinary (nonhazardous) location.
SPECIAL H ANDLING Observe these steps when handling electronic circuitry: NOTE: Always use the Bailey Controls Field Static Kit (part number 1948385A1 - consisting of two wrist straps, ground cord assembly, alligator clip, and static dissipating work surface) when working with modules.
They are 31.25 milliamp, 125 volt fuses, (Bailey part number 1945820A10310). Revision A (assembly number 6639364A1) also has one fuse F17. It is a 2.0 amp, 250 volt fuse, (Bailey part number 1948182A32001). The fuse is shipped installed on the revision A assembly termination units in fuse clip F17.
INSTALLATION BAILEY REPLACEMENT FUSE PART NUMBER FOR F1-F16: 1945820A10310 FIELD INPUT J33-J48 J1-J16 F1-F16 TO IMASI03 FIELD INPUT –V J49-J64 J17-J32 250 Ω TO IMASI03 –V FIELD INPUT TO IMASI03 SUPPLY +24 V I/O COM INPUT INPUT INPUT INPUT INPUT...
INSTALLATION ® Table 2-2. NTAI06 Input Types Input Type Signal Type Thermocouple TC Types: E, J, K, L, N, (14 AWG), N (28 AWG), R, S, T, U, Chinese E, Chinese S Millivolt mV range: -100 mV to +100 mV High Level H.L.
INSTALLATION STANDOFF TABS CHASSIS COMMON MOUNTING SCREWS SCREW FIELD TERMINATION PANEL T00592A Figure 2-4. Installation for Revision A and B Hardware NTAI06 Remove modules (slave or termination) from their assigned CAUTION slots before installing a cable to that slot. Failure to do so could result in damage to the module or station.
INSTALLATION ® ANALOG SLAVE TERMINATION UNIT CABLE CHANNELS 11-16 FIELD IMASI03 NTAI06 WIRING NKAS01/11 (NOTE 1) CHANNELS 1-10 NOTES: 1. NKAS01 HAS PVC INSULATION (SPECIFY LENGTH UP TO 200 FT). NKAS11 HAS NON-PVC INSULATION (SPECIFY LENGTH UP TO 200 FT). 2.
INSTALLATION Terminal Block Wiring We strongly recommend turning off power before doing any termination unit wiring. Failure to do so could result in equip- CAUTION ment damage. Do not apply power without verifying all wire connections. Il est fortement recommande de debracher l'alimentation elec- trique avant d'effectuer tout connexion aux cartes de raccord- ATTENTION ment des units.
INSTALLATION ® NTAI06 TERMINATION UNIT IMASI03 NKAS01/11 CABLE ISOLATED COMMON – DIFFERENTIAL VOLTAGE ISOLATED FROM I/O COMMON NTAI06 TERMINATION UNIT TRANSMITTER IMASI03 +24 V FUSE NKAS01/11 CABLE – 1-5 V SYSTEM-POWERED – 4-20 mA I/O COM NON-ISOLATED IMASI03 NKAS01/11 CABLE -10 V TO +10 V SO UR CE –...
Page 24
INSTALLATION If input or output circuits are a shock hazard after disconnect- ing system power at the power entry panel, then the door of the CAUTION cabinet containing these externally powered circuits must be marked with a warning stating that multiple power sources exist.
SECTION 3 - MAINTENANCE INTRODUCTION The RTD analog input termination unit requires limited main- tenance. This section contains a maintenance schedule. MAINTENANCE SCHEDULE Execute the tasks in Table at the specified intervals. Table 3-1. Maintenance Schedule Task Interval Clean and tighten all power and Every 6 months or during plant grounding connections shutdown, whichever occurs first.
SECTION 4 - REPAIR/REPLACEMENT PROCEDURES INTRODUCTION This section explains the replacement procedures for the NTAI06 Analog Input Termination Unit. REPLACEMENT PROCEDURES If a TU is faulty, replace it with a new one. DO NOT try to repair the TU. Replacing components may affect performance and certification.
REPAIR/REPLACEMENT PROCEDURES ® 8. Insert the tabs of the circuit board into the proper slots of the field termination panel standoff and slide the circuit board into position. 9. Secure the termination unit circuit board to the field termi- nation panel with two screws. Do not overtighten. 10.
SECTION 5 - SUPPORT SERVICES INTRODUCTION Bailey Controls Company is ready to help in the use, applica- tion and repair of its products. Contact the nearest sales office to make requests for sales, applications, installation, repair, overhaul and maintenance contract services.
APPENDIX A - UNIVERSAL ANALOG SLAVE INPUT MODULE (IMASI03) INTRODUCTION The IMASI03 Universal Analog Slave Input Module uses the NTAI06 to terminate analog inputs. Jumpers on the NTAI06 Termination Unit configure up to 16 analog inputs for the IMASI03. Each NTAI06 accepts analog inputs for either system powered four to 20 milliamp, externally powered four to 20 mil- liamp, three-wire RTD, differential or single ended voltage.