Alm-Horn-Wf/-Mrtu Address Mapping - ICP DAS USA ALM-Horn Series User Manual

Table of Contents

Advertisement

4.4 ALM-Horn-WF/-MRTU Address Mapping

Address
00001
00002
00003
00004
Address
10001
Address
CH/Length
40011
Always 1
Table 5-8: FC03 Read multiple AO address (4xxxx)
Address
00001
00002
00003
00004
Address
40011
ALM-Horn Series
ALM-Horn Series User's Manual
CH
Descriptions
1
Alarm with Tone index 0
2
Alarm with Tone index 1
3
Alarm with Tone index 2
4
Alarm with Tone index 3
Table 5-6: FC01 Read DO address (0xxxx)
CH
Descriptions
1
Digital Input
Table 5-7: FC02 Read DI address (1xxxx)
Descriptions
Read Idle Timeout value
CH
Descriptions
1
Set Alarm with Tone index 0
2
Set Alarm with Tone index 1
3
Set Alarm with Tone index 2
4
Set Alarm with Tone index 3
Table 5-8: FC05 Write DO address (0xxxx)
CH
Descriptions
-
Write Idle Timeout value
Table 5-9: FC06 Write single AO address (4xxxx)
User's Manual (Rev1.0, NOV/2020) ------------- 24
Range
0=OFF, 1=ON
0=OFF, 1=ON
0=OFF, 1=ON
0=OFF, 1=ON
Range
0=OFF, 1=ON
Range/Value
16bit Word
Range
0x00=OFF, 0xFF=ON
0x00=OFF, 0xFF=ON
0x00=OFF, 0xFF=ON
0x00=OFF, 0xFF=ON
Range/Value
16bit Word(1~65000)
Access Type
R
R
R
R
Access Type
R
Access Type
R
Access Type
W
W
W
W
Access Type
W

Advertisement

Table of Contents
loading

Table of Contents