Download Print this page

Siemens SICAM A8000 Series Quick Start Manual page 2

Do-8230 digitale ausgabe transistor 16x 24-60 vdc
Hide thumbs Also See for SICAM A8000 Series:

Advertisement

Available languages

Available languages

Read and understand these instructions and the relevant manual before installing,
operating, or maintaining the device. The manual is available in the download area of the
internet at http://www.siemens.com/sicam.
Further Support
If special problems arise, or further information are required, please contact your Siemens
representative. The Siemens Customer Support Center provides around-the-clock support.
Disclaimer of Liability
Although we have carefully checked the contents of this publication for conformity with the
hardware and software described, we cannot guarantee complete conformity since errors
cannot be excluded.
The information provided in this document is checked at regular intervals and any
corrections that might become necessary are included in the next releases. Any
suggestions for improvement are welcome. Subject to change without prior notice.
Copyright
Copyright © Siemens AG 2019 – All Rights Reserved
The reproduction, transmission or use of this document or its contents is not permitted
without express written authority. Offenders will be liable for damages. All rights, including
rights created by patent grant or registration of a utility model or design, are reserved.
Notes on Safety
This document contains notes that must be adhered to for your own personal safety and to
avoid damage to property. Keep it safe for later usage.
However, it does not constitute a complete description of all safety measures required for
installation, service, and maintenance of the device in question. Details are to be taken from
the manuals and those are mandatory.
Warning: Danger of severe personal injury or substantial damage to property
Hazardous voltages may occur in devices and modules during operation depending on
the design and application. Always observe the instructions given in "Qualified
Electrical Engineering Personnel" below.
Qualified Electrical Engineering Personnel
Qualified electrical engineering personnel may commission and operate the device
described in this document. Qualified electrical engineering personnel in the sense of this
document are people who can demonstrate up to date technical qualifications as electrical
technicians including safety and first aid training. These persons may commission, isolate,
ground and label devices, systems and circuits according to the standards of safety
engineering.
Use as Prescribed
The device may only be used for such applications as set out in the catalogs and the
technical description, and only in combination with third party equipment recommended and
approved by Siemens.
Correct and safe operation of the product requires adequate transportation, storage,
installation and mounting in a control cabinet, as well as appropriate use and maintenance.
During operation of electrical equipment, it is unavoidable that certain parts of this
equipment will carry dangerous voltages. Severe injury or damage to property can occur if
the appropriate measures are not taken:
• Before making any connections, ground the equipment and the grounding terminal.
• Hazardous voltages can be present on all switching components connected to the power
supply.
• The device does not represent a safety-oriented application.
• Even after the supply voltage has been disconnected, hazardous voltages can still be
present in the equipment (capacitor storage).
• The limit values indicated in the manual must not be exceeded; that also applies to
testing and commissioning.
Statement of Conformity
The product described conforms to the regulations of the following European
Directives:
• EMC Directive 2014/30/EU
(observance of the harmonized standard EN 60870-2-1:1996)
• Low Voltage Directive 2014/35/EU
(observance of the harmonized standard EN 61010-1:2010, EN 61010-2-201:2013)
• RoHS Directive 2011/65/EU
(observance of the harmonized standard EN 50581:2012)
Used Symbols (additional symbols are described in the manual)
Warning, risk of electric shock
Caution, risk of danger. The
documentation must be observed.
Application
The SICAM I/O Module DO-8230 is a transistor based digital output module. It is used to
expand SICAM A8000 systems with additional digital outputs.
The SICAM A8000 series is suitable for electrical distribution substations, gas distribution
substations, hydropower plants, pipelines and railway power supplies.
Note: In SICAM CP-8000 this module can only be used in combination with the
coupling module CM-8811. See corresponding product information.
Unpacking a Device
• Check the package for external transport damage. A damaged packing may indicate that
the device inside is also damaged.
• Unpack the device carefully; do not use force.
• Visually check the device to ensure that it is in perfect mechanical condition.
• Return a damaged device to the manufacturer or dispose it correctly. A defective device
may not either be used nor repaired by the user.
Note: Before commissioning the device, leave it in the operating room for at least
2 hours. This allows it to reach room temperature and prevents dampness and
condensation.
DO-8230 Product Information
C53207-A5084-C481-1A-7483 / DC8-092-2.00; Edition 07.2019
Protection class II / protective
insulation
CE conformity
Mounting
Precondition for mounting the I/O module is that the SICAM A8000 system to be expanded
has already been mounted on the DIN rail.
Then mount the bus connector (which is delivered with the I/O module), to the right of the
system on the DIN rail and press it into the connector of the left adjacent module.
Afterwards plug the I/O module on the bus connector.
Note: For details about the mounting refer to the respective product manual.
Commissioning
• Check the adherence of the specified limit values.
• Connect the process-devices to the screw terminals. Cabinet-internal wiring is preferably
carried out with plastic-insulated cables according to DIN VDE 298 T4 2/89.
Types: H05V-K, H05V2-K (0.5...1 mm²) or H07V-K, H07V2-K (1.5...2.5 mm²).
Use only copper wires.
• The SICAM I/O module is supplied with voltage via the bus.
Technical Data
Digital Outputs
16 digital outputs
2 groups, 8 outputs each; galvanical insulation
Nominal voltage
DC 24/48/60 V
Maximum continuous current
Standard circuitry
16 outputs, max. 0.5 A each
Power augmentation
Max. 1 A on 1 channel and 0.5 A on 15 channels
• 12 W at DC 24 V
Nominal switching capacity
• 24 W at DC 48 V
(resistive load, U
)
N
• 30 W at DC 60 V
Overload proof
No
Proof against continued short-
10 A Current limitation (if the current limitation
operates, current is cut off within 10 μs)
circuit
Cyclic reclosing:
Switching cycles
Unlimited
Output circuit voltage drop
< 0.5 V at 0.5 A
• Capacitive load max. 100 nF at 60 V
Dynamic withstand capability
• Inductive
• Lines Z ≥ 100 Ω, line length up to 3 km
• Lamps I
Output circuits
DC 18...78 V (operated with external voltage)
Power Supply
Operating voltage
DC 4.75 to 5.5 V, 500 mW (from bus)
Mechanics and Connectors
Terminals
Removable screw terminals (grid size 5.08)
IP 20
Protection type acc. IEC60529
II
Protection class acc. IEC61140
Rated impulse voltage
4 kV, category III / AC 230 V
Climatic Ambient Conditions
Operation temperature
-40...+70 °C
≤ 30 °C/h
Temperature gradient
Relative air humidity
5...95 % (condensation not permissible)
Air pressure
70...106 kPa (up to 3000 m)
Temperature for storage and
-30...+85 °C
transport
Pollution degree
2
Block Diagram and Circuitry Variant
DO-8230
Reinforced
insulation
U+
U-
Note: The connectors X1 and X2 are to be connected or disconnected in de-energized
state only.
SICAM A8000 Series
DO-8230 Digital Output Transistor 16x 24-60 VDC
Parallel connections are not
allowed
Break time > 240 μs
< 10 μs
Make time
����
≤ 500 ms (with any external free-
wheeling diode)
≤ 150 mA (I
≤ 1.8 A)
N
ON
BUS
Controller
Reinforced
insulation
U+
U-
2

Advertisement

loading