INSTALLATION

Mounting

The holes indicated in the image are intended for a mounting
bracket. They are threaded for ¼-20 and are 0.4" deep.
The other two visible holes are threaded 10-32, 0.50" deep, and
are intended to be used to lock the lid in position with screws.
For detailed dimensions see p.13.

Wiring

Wiring for Explosion Proof Actuators

The RCx-AC-BxxAx Explosion-Proof actuator does not come with a pre-installed cable, nor
cable gland. A cable gland that meets site specifications for the appropriate hazardous location
rating is required for installation. The cable gland and the cable for hazardous location should
be installed by qualified personnel in accordance with site and local requirements.
The actuator comes standard with a ½" FNPT thread cable entry. See p.13 for
location of ½" FNPT housing access. A cable with 6 wires is required; it is
recommended to use 3x 16 AWG for wires supplying power and ground, and 3x 20
AWG for wires used for the control and feedback signals.
Standards for cable gland and cable in hazardous locations:
Compliance Standards
Required to be Met
ANSI / UL 514B, ANSI / UL
1203, ANSI / UL 2225, C22.2
ANSI / UL 514B, ANSI / UL
1203, ANSI / UL 2225
ANSI / UL 514B, ANSI / UL
1203, ANSI / UL 2225
ANSI / UL 514B, ANSI / UL
1203, C22.2
* In explosion-proof models, the FNPT thread is not intended for conduit connection. Cable gland only.
Page 2 of 17
Rev.2021.11
Cable Types Permitted in
Class I Division 1
Hazardous Locations
Non-Armored Extra Hard
Usage Cord & TC-ER-HL
Armored IEEE 45 & IEEE
1580 Marine Shipboard Cable
MC-HI, ITC-HL
Teck 90 (Canada Only)
User Manual RCx-AC-xxxAx-8.09