RCx-AC-xxxAx-8.09 (110-240 VAC; 4-20 mA Control) CSA/IECEX Rated* USER MANUAL Contents INSTALLATION Mounting Wiring Wiring for Explosion Proof Actuators Wiring for Non-Explosion Proof actuators Power Supply and Current Draw Control Signal and Feedback OPERATION DIP Switches Controlling the Actuator Changing the number of turns Torque Settings Speed and Torque Details Signal Loss and Calibration...
User Manual RCx-AC-xxxAx-8.09 INSTALLATION Mounting The holes indicated in the image are intended for a mounting bracket. They are threaded for ¼-20 and are 0.4” deep. The other two visible holes are threaded 10-32, 0.50” deep, and are intended to be used to lock the lid in position with screws. For detailed dimensions see p.13.
User Manual RCx-AC-xxxAx-8.09 Once the cable and cable gland are installed, connect the wires to the pins on the terminal block as indicated here: Function Terminal Pre-wired to transformer 1 2 3 4 5 6 Connect live wire to loose black cable with crimp connector (see p.4) Pre-wired to transformer Remove R66 to...
User Manual RCx-AC-xxxAx-8.09 Power Supply and Current Draw AC Voltages The RCx-AC-xxxAx actuator may be connected to voltages within 110-240 VAC. The current draw will range from minimum 10 mA to maximum 1.5 A while the actuator is active. When not moving, the actuator draws approx. 5 mA. AC power is connected to the WHITE &...
The potential of the external GND after the sensing resistor may not be more than +6 VDC / -2 VDC away from the power GND of the actuator. This feedback signal output is only available in HANBAY RCx-AC-xxxAF model actuators. Page 5 of 17 www.hanbayinc.com | 1 800 315 4461...
User Manual RCx-AC-xxxAx-8.09 OPERATION DIP Switches The DIP switches allow you to change the settings on your actuator. To flip a switch, gently use a small flat-head screwdriver. See table below for DIP switch functionality. In this example DIPs 1, 2, 5 and 12 are on. Function Speed: Choose how quickly the actuator will turn the valve.
User Manual RCx-AC-xxxAx-8.09 Controlling the Actuator The 4-20 mA (or 1-5 V / 1-10 V) input signal represents a total span of a number of turns. I.e.: If you set the number of turns to 2, then a signal of 12 mA will set the actuator to exactly 1 turn from the fully closed position.
User Manual RCx-AC-xxxAx-8.09 Torque Settings To accommodate different valves and other applications Seating power settings: with different torque requirements, the actuator can be set to apply different torque on the valve stem when in the DIP 10 DIP 11 Power seating mode.
Page 9
User Manual RCx-AC-xxxAx-8.09 RCM-AC-xxxAx Actuators Speed: Torque: Time for Seating Torque DIP 1 DIP 2 DIP 10 DIP 11 1 turn (sec) (in-lbs) Operating torque is 100% NOTE: If actuator is RCK-AC-xxxAx, divide torque values by 3. To convert in-lbs to Nm, divide by 9. RCH-AC-xxxAx Actuators Speed: Torque:...
User Manual RCx-AC-xxxAx-8.09 Signal Loss and Calibration 1. For actuators that are not connected to a UPS (Uninterruptible Power Supply), the loss of signal will be simultaneous with power loss. Consequently, the actuator will not be able to move anywhere. In the shutdown process, the actual position is automatically saved to the internal EEPROM.
A sticking valve may be the problem. Remove the valve from the actuator, and re-test the actuator. Remove power. Re-check the wiring and the power/signal apparatus. Power actuator and re-calibrate. If the problem persists, please call Hanbay for technical support. Page 11 of 17 www.hanbayinc.com | 1 800 315 4461...
User Manual RCx-AC-xxxAx-8.09 EXPLOSION PROOF CERTIFICATIONS Actuator model number: RCx-AC-BxxAx IECEX Standards & Editions: IEC 60079-0:2017, 7th Edition IEC 60079-1:2014, 7th Edition *Serial number will be engraved on the lid. Standards: Class I, Div 1, Groups B, C, D (T6) Class II, Groups E, F, G (T6) CAN/CSA Std.
User Manual RCx-AC-xxxAx-8.09 PART NUMBER BREAKDOWN Full Hanbay Part Number: Page 16 of 17 www.hanbayinc.com | 1 800 315 4461 Rev.2021.11 hanbaysales@hanbayinc.com...