(110-240 VAC; 4-20 mA Control)
CSA/IECEX Rated*
USER MANUAL
Contents
2
2
2
2
3
4
5
6
6
7
7
8
8
10
11
11
12
13
16
17
*Only model numbers:
RCx-AC-BxxAx w/ ex-proof
lid engraving (see p.12)
www.hanbayinc.com | 1 800 315 4461
hanbaysales@hanbayinc.com

Advertisement

Table of Contents
loading

Summary of Contents for Hanbay RC-AC Series

  • Page 1: Table Of Contents

    RCx-AC-xxxAx-8.09 (110-240 VAC; 4-20 mA Control) CSA/IECEX Rated* USER MANUAL Contents INSTALLATION Mounting Wiring Wiring for Explosion Proof Actuators Wiring for Non-Explosion Proof actuators Power Supply and Current Draw Control Signal and Feedback OPERATION DIP Switches Controlling the Actuator Changing the number of turns Torque Settings Speed and Torque Details Signal Loss and Calibration...
  • Page 2: Installation

    User Manual RCx-AC-xxxAx-8.09 INSTALLATION Mounting The holes indicated in the image are intended for a mounting bracket. They are threaded for ¼-20 and are 0.4” deep. The other two visible holes are threaded 10-32, 0.50” deep, and are intended to be used to lock the lid in position with screws. For detailed dimensions see p.13.
  • Page 3: Wiring For Non-Explosion Proof Actuators

    User Manual RCx-AC-xxxAx-8.09 Once the cable and cable gland are installed, connect the wires to the pins on the terminal block as indicated here: Function Terminal Pre-wired to transformer 1 2 3 4 5 6 Connect live wire to loose black cable with crimp connector (see p.4) Pre-wired to transformer Remove R66 to...
  • Page 4: Power Supply And Current Draw

    User Manual RCx-AC-xxxAx-8.09 Power Supply and Current Draw AC Voltages The RCx-AC-xxxAx actuator may be connected to voltages within 110-240 VAC. The current draw will range from minimum 10 mA to maximum 1.5 A while the actuator is active. When not moving, the actuator draws approx. 5 mA. AC power is connected to the WHITE &...
  • Page 5: Control Signal And Feedback

    The potential of the external GND after the sensing resistor may not be more than +6 VDC / -2 VDC away from the power GND of the actuator. This feedback signal output is only available in HANBAY RCx-AC-xxxAF model actuators. Page 5 of 17 www.hanbayinc.com | 1 800 315 4461...
  • Page 6: Operation

    User Manual RCx-AC-xxxAx-8.09 OPERATION DIP Switches The DIP switches allow you to change the settings on your actuator. To flip a switch, gently use a small flat-head screwdriver. See table below for DIP switch functionality. In this example DIPs 1, 2, 5 and 12 are on. Function Speed: Choose how quickly the actuator will turn the valve.
  • Page 7: Controlling The Actuator

    User Manual RCx-AC-xxxAx-8.09 Controlling the Actuator The 4-20 mA (or 1-5 V / 1-10 V) input signal represents a total span of a number of turns. I.e.: If you set the number of turns to 2, then a signal of 12 mA will set the actuator to exactly 1 turn from the fully closed position.
  • Page 8: Torque Settings

    User Manual RCx-AC-xxxAx-8.09 Torque Settings To accommodate different valves and other applications Seating power settings: with different torque requirements, the actuator can be set to apply different torque on the valve stem when in the DIP 10 DIP 11 Power seating mode.
  • Page 9 User Manual RCx-AC-xxxAx-8.09 RCM-AC-xxxAx Actuators Speed: Torque: Time for Seating Torque DIP 1 DIP 2 DIP 10 DIP 11 1 turn (sec) (in-lbs) Operating torque is 100% NOTE: If actuator is RCK-AC-xxxAx, divide torque values by 3. To convert in-lbs to Nm, divide by 9. RCH-AC-xxxAx Actuators Speed: Torque:...
  • Page 10: Signal Loss And Calibration

    User Manual RCx-AC-xxxAx-8.09 Signal Loss and Calibration 1. For actuators that are not connected to a UPS (Uninterruptible Power Supply), the loss of signal will be simultaneous with power loss. Consequently, the actuator will not be able to move anywhere. In the shutdown process, the actual position is automatically saved to the internal EEPROM.
  • Page 11: Manual Override

    A sticking valve may be the problem. Remove the valve from the actuator, and re-test the actuator. Remove power. Re-check the wiring and the power/signal apparatus. Power actuator and re-calibrate. If the problem persists, please call Hanbay for technical support. Page 11 of 17 www.hanbayinc.com | 1 800 315 4461...
  • Page 12: Explosion Proof Certifications

    User Manual RCx-AC-xxxAx-8.09 EXPLOSION PROOF CERTIFICATIONS Actuator model number: RCx-AC-BxxAx IECEX Standards & Editions: IEC 60079-0:2017, 7th Edition IEC 60079-1:2014, 7th Edition *Serial number will be engraved on the lid. Standards: Class I, Div 1, Groups B, C, D (T6) Class II, Groups E, F, G (T6) CAN/CSA Std.
  • Page 13: Actuator Dimensions

    User Manual RCx-AC-xxxAx-8.09 ACTUATOR DIMENSIONS RCJ/ RCL/ RCM -AC-xxxAx models Page 13 of 17 www.hanbayinc.com | 1 800 315 4461 Rev.2021.11 hanbaysales@hanbayinc.com...
  • Page 14 User Manual RCx-AC-xxxAx-8.09 RCH-AC-xxxAx model Page 14 of 17 www.hanbayinc.com | 1 800 315 4461 Rev.2021.11 hanbaysales@hanbayinc.com...
  • Page 15 User Manual RCx-AC-xxxAx-8.09 RCF-AC- xxxAx models Page 15 of 17 www.hanbayinc.com | 1 800 315 4461 Rev.2021.11 hanbaysales@hanbayinc.com...
  • Page 16: Part Number Breakdown

    User Manual RCx-AC-xxxAx-8.09 PART NUMBER BREAKDOWN Full Hanbay Part Number: Page 16 of 17 www.hanbayinc.com | 1 800 315 4461 Rev.2021.11 hanbaysales@hanbayinc.com...
  • Page 17: Label Breakdown

    User Manual RCx-AC-xxxAx-8.09 LABEL BREAKDOWN Firmware Version AF-1.05 MM = Multiturn AB-1.05 MML = Multiturn Low Torque AS-1.05 MMUL = Multiturn Extra Low Torque Actuator Supply Voltage QM = Quarter turn 12-24 VDC @ 3.0 A or QM97 = Quarter turn 97° 110-240 VAC @ 1.5 A DT-2.01 DC-2.01...