5 Water loop connection

Please pay attention to below matters when the water pipe is connected: Try
to reduce the resistance to the water from the piping.
The piping must be clear and free from dirty and blocks. Water leakage test must be
carried out to ensure there is no water leaking. And then the insulation can be made.
Attention that the pipe must be tested by pressure separately. DO NOT test it together with
the heat pump.
There must be expansion tank on the top point of the water loop, and the water level in the
tank must be at least 0.5 meter higher than the top point of the water loop.
The flow switch is installed inside of the heat pump, check to ensure that the wiring and
action of the switch is normal and controlled by the controller.
Try to avoid air stayed inside of the water pipe, and there must be air vent on the top point
of the water loop.
There must be thermometer and pressure meter at the water inlet and outlet, for easy
inspection during running.

6 Power supply connection

Open the front panel, and open the power supply access.
The power supply must go through the wire access and be connected to the power
supply terminals in the controlling box. Then connect the 3-signal wire plugs of the wire
controller and main controller.
If the outside water pump is needed, please insert the power supply wire into the wire
access also and connect to the water pump terminals.
If an additional auxiliary heater is need to be controlled by the heat pump controller, the
relay (or power) of the aux-heater must be connected to the relevant output of
the controller.

7 Location of the unit

11