TriangleTube INSRKIT08 Instructions Manual

Natural gas to propane conversion

Advertisement

Quick Links

Natural Gas to Propane Conversion Instructions
Kit Part Number
INSRKIT08 (Solo 110)
INSRKIT10 (Solo/Combi 155)
INSRKIT12 (Solo/Combi 199)
Kit Includes
Rating Label
Conversion Label
(1) Propane Gas Venturi
Acoustic Foam (required for 110 and 155 models ONLY)
WARNING
!
Indicates a potentially hazardous situation
which, if ignored, can result in serious injury or
substantial property damage.
NOTICE
When converting the appliance from Natural Gas to Propane ensure that the conversion is completed before fully installing
the air inlet piping.
WARNING
!
For your safety, turn off electrical power supply
at service panel and allow unit to cool before
proceeding to avoid possible electrical shock and
scald hazard. Failure to do so can cause severe
personal injury or death.
NOTICE
Upon completion of the conversion from Natural Gas to
Propane, affix the new rating label included in the kit to
the unit adjacent to the existing rating label. DO NOT
affix the new label over the existing rating label. Add
propane conversion labelling to the gas valve.
227797 A02
Revision Date: 05/2021
Instinct Solo/Combi
Recommended Tools
Adjustable Wrench / 10 mm Socket & Ratchet
Phillips Head Screwdriver
Flat Head Screwdriver
Calibrated Combustion Analyzer
NOTICE
Indicates special instructions on installation, operation
or maintenance, which are important to equipment
but not related to personal injury hazards.
WARNING
!
Failure to follow instructions below can result in
severe personal injury or damage if ignored.
Instructions are for a qualified installer/
service technician only.
Read all instructions before proceeding.
Follow instructions in proper order.
NOTICE
These instructions cover NG to LP conversion for Instinct
boilers only. Each kit is supplied with one venturi suitable
for use with that particular boiler model.
2019-18 Instinct NG to LP Conversion

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the INSRKIT08 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for TriangleTube INSRKIT08

  • Page 1 Instinct Solo/Combi Natural Gas to Propane Conversion Instructions Kit Part Number Recommended Tools • INSRKIT08 (Solo 110) • Adjustable Wrench / 10 mm Socket & Ratchet • INSRKIT10 (Solo/Combi 155) • Phillips Head Screwdriver • INSRKIT12 (Solo/Combi 199) • Flat Head Screwdriver •...
  • Page 2 INSTINCT NATURAL TO PROPANE CONVERSION INSTRUCTIONS 1. Preliminary Instructions: 1. Verify that the venturi replacement kit is correct for Acoustic Foam the model of boiler. See page 1. 2. Turn off electrical power supply to the boiler. 3. Close the manual gas shut off valve to the unit. 7"...
  • Page 3 INSTINCT NATURAL TO PROPANE CONVERSION INSTRUCTIONS 3. Removal of Natural Gas Venturi Venturi Venturi Interface 1. Remove the silicone tube from the air inlet elbow, then remove the air inlet elbow. Pipe to Venturi 2. Rotate the venturi interface approximately 60° clockwise to release the clamping mechanism and Air Inlet Gas Valve...
  • Page 4 INSTINCT NATURAL TO PROPANE CONVERSION INSTRUCTIONS WARNING WARNING Failure to retain the O-ring gasket between the venturi Do not check for gas leaks with an open flame. Use a and the blower will cause an improper seal resulting bubble test. Failure to test for gas leaks can result in in a potential risk of a gas leak.
  • Page 5 INSTINCT NATURAL TO PROPANE CONVERSION INSTRUCTIONS 5. Combustion Test and Adjustments 4. Press the CENTER button while the FAN icon is highlighted to manually fire the burner and power the CH circulator. See Fig. 6. NOTICE The installer MUST perform a complete combustion check to ensure the following combustion levels are met at high and NOTICE low input firing rates and the burner is operating at optimum...
  • Page 6 INSTINCT NATURAL TO PROPANE CONVERSION INSTRUCTIONS Table 1: Combustion Settings Propane 110, 155 Propane 199 Range 10.0 - 11.0% Target 10.8% Range 5.7 - 4.2% Target 4.5% CO Max <200 ppm @ 10.8% CO Range 10.0 - 11.0% Target 10.8% 10.4% Target values are equivalent to High Fire values, ensure CO₂...

This manual is also suitable for:

Insrkit10Insrkit12

Table of Contents