CONTAMINANTS

Combustion air drawn from an interior
or exterior space must be free of any
chemical fumes which could be corrosive to
the water heater. Burning chemical fumes
results in the formation of corrosive acids
which attack the water heater, cause
improper combustion and premature failure
of the water heater and vent.
These fumes are often present in areas
where refrigerants, salts, and solvents are
used. Therefore, be mindful of swimming
pool equipment, water softening, and
cooling system placement.
VENTING
IMPORTANT!
This appliance is a high
General
efficiency unit. It
Vent installations for connection to gas vents
operates at an efficiency
or chimneys must be in accordance with
level which could yield a
Part 7, "Venting of Equipment," of the latest
condensing condition.
edition of the National Fuel Gas Code,
Care should be taken in
ANSI Z223.1, or applicable provisions
providing the proper
of the local building codes.
venting and employing
the best principles of
The connection from the appliance vent to
application and sizing.
the stack must be as direct as possible and
sized correctly. The horizontal breeching of
a vent must have at least 1/4" rise per
linear foot. The horizontal portions should
also be supported for the design and weight
of the material employed to maintain
clearances, prevent physical damage and
separation of joints.
The connection from the appliance vent to
the stack or vent termination outside the
building must be made with appropriate
6
L o c h i n v a r
'
D E S I G N E R
S G U I D E P O W E R
vent category connectors and sized
according to vent sizing tables (FAN column)
in the latest edition of the National Fuel Gas
Code.
The vent and accessories, such as firestop
spacers, thimbles, caps, etc., must be
installed in accordance with the vent
manufacturer's listing. The vent connector
and firestop must provide correct spacing to
combustible surfaces and seal to the vent
connector on the upper and lower sides of
each floor or ceiling through which the vent
connector passes.
Any improper operation of the common
venting system in an existing building should
be corrected when new equipment is
installed, so the installation conforms to the
latest edition of the National Fuel Gas Code,
ANSI Z223.1.
When resizing any portion of the common
venting system, it should be resized to
approach the minimum size as determined
using the appropriate tables in the National
Fuel Gas Code.
The weight of the venting system must not
rest on the unit. The venting system must be
adequately supported in compliance with
local codes and other applicable codes.
Vent Terminations
The vent terminal should be vertical and
exhaust outside the building at least 2 feet
(0.6 m) above the highest point of the roof
when within a 10 foot (3.05 m) radius.
-